HomeMy WebLinkAboutWQ0009267_Additional Information Request_20220614
June 14, 2022
WALLY HANSEN – PUBLIC SERVICES DIRECTOR
CITY OF JACKSONVILLE
POST OFFICE BOX 128
JACKSONVILLE, NORTH CAROLINA 28541
Subject: Application No. WQ0009267
Additional Information Request
City of Jacksonville WWTF
Wastewater Irrigation System
Onslow County
Dear Mr. Hansen:
Division of Water Resources’ Central and Regional staff has reviewed the application package
received March 28, 2022. However, additional information is required before the review may be completed.
Please address the items on the attached pages no later than the close of business on July 14, 2022.
Please be aware that you are responsible for meeting all requirements set forth in North Carolina
rules and regulations. Any oversights that occurred in the review of the subject application package are
still the Applicant’s responsibility. In addition, any omissions made in responding to the outstanding items
in Sections A through P, or failure to provide the additional information on or before the above requested
date may result in your application being returned as incomplete pursuant to 15A NCAC 02T .0107(e)(2).
Please reference the subject application number when providing the requested information. All
revised and/or additional documentation shall be signed, sealed and dated (where needed), with an
electronic response submitted to my attention at: https://edocs.deq.nc.gov/Forms/NonDischarge-Branch-
Submittal-Form-Ver2.
If you have any questions regarding this request, please contact me at (919) 707-3660 or
Lauren.Plummer@ncdenr.gov. Thank you for your cooperation.
Sincerely,
Lauren Raup-Plummer, Engineer III
Division of Water Resources
cc: Wilmington Regional Office, Water Quality Regional Operations Section (Electronic Copy)
Laserfiche File (Electronic Copy)
Mr. Wally Hansen
June 14, 2022
Page 2 of 3
A. Cover Letter:
1. Not applicable.
B. Application Fee:
1. Not applicable.
C. Application (WWIS-R 02-21):
1. No comment.
D. Attachment A – Site Map:
1. The City of Jacksonville WWTF was permitted for expansion from 6.0 million gallons per day
(MGD) to 9.0 MGD on July 9, 2008 which constitutes a major modification. Pursuant to 15A
NCAC 02T .0105(d), please submit a site map pursuant to the requirements in 15A NCAC 02T
.0504(d). These requirements are:
a. A scaled map of the site with topographic contour intervals not exceeding 10 feet or
25 percent of total site relief and showing all facility-related structures and fences
within the wastewater treatment, storage, and irrigation areas.
b. Soil mapping units shown on all irrigation sites.
c. The location of all wells (including usage and construction details if available), streams
(ephemeral, intermittent, and perennial), springs, lakes, ponds, and other surface
drainage features within 500 feet of all wastewater treatment, storage, and irrigation
sites.
d. Delineation of the compliance and review boundaries per 15A NCAC 02L .0107 and
.0108, and 15A NCAC 02T .0506(c) if applicable.
e. Setbacks as required by 15A NCAC 02T .0506.
f. Site property boundaries within 500 feet of all wastewater treatment, storage, and
irrigation sites.
g. All habitable residences or places of public assembly within 500 feet of all treatment,
storage, and irrigation sites.
E. Attachment B – Signature Authority Delegation:
1. No comment.
F. Attachment C – Flow Reduction:
1. Not applicable.
Mr. Wally Hansen
June 14, 2022
Page 3 of 3
G. Attachment D – Certificate of Public Convenience and Necessity:
1. Not applicable.
H. Attachment E – Operational Agreement:
1. Not applicable.
I. Attachment F – Demonstration of Future Wastewater Treatment Capacities:
1. No comment.
J. Attachment G – Easement, Encroachment, and Lease Agreements:
1. Not applicable.
K. Attachment H - Affiliations:
1. No comment.
L. Attachment I – Compliance Schedules:
1. No comment.
M. Attachment J – Civil Penalties and Outstanding Violations:
1. No comment.
N. Attachment K – Industrial Wastewater:
1. Not applicable.
O. Attachment L – Setback Waivers:
1. Not applicable.
P. Additional Documentation:
Existing Permit:
1. The facility description, from the current permit version dated November 9, 2017, lists several
modifications to the mixers/aerators, and it is unclear what the horsepower ratings are for the
installed Blue Frog and Gold Frog mixers/aerators. Please provide a table that specifies the
location, brand/type, horsepower, and number of units for the mixers/aerators installed at each
location.