HomeMy WebLinkAboutNC0058084_Compliance Evaluation Inspection_20220613ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
David Risley, President
Gough Econ, Inc.
Post Office Box 668583
Charlotte, NC 28266
SUBJECT: Notice of Deficiency
Compliance Evaluation Inspection
Gough Econ WWTP
NPDES Permit No. NC0058084
Mecklenburg County
Tracking #: NOD-2022-PC-0094
Dear Mr. Risley:
NORTH CAROLINA
Environmental Quality
June 13, 2022
Enclosed is a copy of the Compliance Evaluation Inspection (CEI) Report for the inspection conducted at the subject
facility on June 2, 2022, by Mr. Wes Bell of this Office. Please advise the facility's Operator -in -Responsible Charge (ORC) of
our findings by forwarding the enclosed report.
This report is being issued as a Notice of Deficiency (NOD) due to the following:
- The septic tank was not accessible for inspection;
- The dosing tank was leaking into the sand filter;
- The mushroom spray nozzles needed to be cleaned and/or replaced;
- The concrete block perimeter wall needed to be repaired/resealed in several sections;
- The facility failed to monitor the second effluent pH in December 2021;
- All of the 2021 monitoring data was not available for review.
Please be advised that the failures to monitor the effluent, maintain records, and provide proper operation and maintenance
are violations of the subject NPDES Permit and North Carolina General Statute (G.S.) 143-215.1. Please note that G.S.
143-215.6A provides for a civil penalty of not more than twenty-five thousand dollars ($25,000.00), or twenty-five thousand
dollars ($25,000.00) per day when the violation is of a continuing nature, against any person who violates or fails to act in
accordance with the terms, conditions, or requirements of any permit issued pursuant to G.S. 143-215.1. Penalties may also be
assessed for any damage to surface waters of the State that may result from the violation.
D_E
o,.mwonmr..edo�
North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1610 East Center Avenue. Suite 301 1 Mooresville. North Carolina 28115
704.663.1699
It is requested that a written response be submitted to this Office by July 5, 2022, detailing the actions taken to address all
violations and maintenance issues discussed in this report. In responding, please address your comments to the attention of Mr.
Wes Bell.
Should you have any questions concerning this Notice, please do not hesitate to contact Mr. Bell at (704) 235-2192 or at
wes.bell@ncdenr.gov.
Enclosure:
Inspection Report
Cc: NPDES Program Files - Laserfiche
D_E
o,.mworkt G.ed o �
Sincerely,
1—DocuSigned by:
`—A14CC681 AF27425...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
Division of Water Resources, NCDEQ
North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1610 East Center Avenue. Suite 301 1 Mooresville. North Carolina 28115
704.663.1699
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code
1 IN I 2 IL
21 1 1 1 1 1
NPDES yr/mo/day Inspection
I 3 I NC0058084 111 121 22/06/02 117
Type
18 i i
I I 1 1 1
Inspector Fac Type
191 S I 201
1 1 1 1 11 1 1 1 I I I 1 1 1 1 1 1 I I I I I
1 11
1 1 1 I 1 P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
67I2.0 I 70I3 I 71IN I 72 I N I 731 I 74 71
I I 1
I I I I I I 1l80
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES oermit Number)
Gough Econ WWTP
9400 N Lakebrook Rd Sr
Charlotte NC 28214
Entry Time/Date
09:15AM 22/06/02
Permit Effective Date
20/10/01
Exit Time/Date
12:50PM 22/06/02
Permit Expiration Date
25/06/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Kellie H Hedrick//980-202-2377 /
Kimberly Dawn Holt/ORC/980-202-2377/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
David P Risley,PO Box 668583 Charlotte NC 28266//704-399-2306/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s)
Wes Bell
of Inspector(s) Agency/Office/Phone and Fax Numbers Date
�Docusigned by: DWR/MRO WQ/704-663-1699 Ext.2192/ 6/13/2022
"-A61696D90CC3437...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger DWR/Division of Water Quality/704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
6/13/2022
Page# 1
"-A14CC681AF27425...
sI
NPDES yr/mo/day
N C 0058084 111 121 22/06/02
I17
Inspection Type
18 [j
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
RECORD KEEPING SECTION cont'd:
The records reviewed during the inspection were organized and well maintained; however, the
majority of the 2021 records (lab analyses, chain of custody forms, operation & maintenance records)
were not available at the time of the inspection as required by the NPDES Permit [Permit Condition
Reference: Part II, Section D(6) & D(7) Records Retention/Recording Results].
Page# 2
Permit: NC0058084
Inspection Date: 06/02/2022
Owner - Facility: Gough Econ WWTP
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new MODE
application?
Is the facility as described in the permit? • ❑ ❑ ❑
# Are there any special conditions for the permit? ❑ El • El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment: Although the facility entrance is gated and there is a perimeter fence, the permittee
should provide locks for the gates to the discharge outfall and fence for the septic
tank/sandfilter. In addition, the access lids for the chlorination and dechlorination
systems should also be secured.
The last compliance evaluation inspection at this facility was performed by DWR staff
on 3/12/2019.
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? ❑ • ❑ ❑
Is all required information readily available, complete and current? ❑ • ❑ ❑
Are all records maintained for 3 years (lab. reg. required 5 years)? El • ❑ ❑
Are analytical results consistent with data reported on DMRs? • El El El
Is the chain -of -custody complete? • El ❑ ❑
Dates, times and location of sampling ■
Name of individual performing the sampling •
Results of analysis and calibration •
Dates of analysis ■
Name of person performing analyses •
Transported COCs ■
Are DMRs complete: do they include all permit parameters? • El El El
Has the facility submitted its annual compliance report to users and DWQ? ❑ El • ❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified El El • El
operator on each shift?
Is the ORC visitation log available and current? • El ❑ ❑
Is the ORC certified at grade equal to or higher than the facility classification? • El El El
Is the backup operator certified at one grade less or greater than the facility ■ ❑ ❑ ❑
classification?
Is a copy of the current NPDES permit available on site? • El El El
Facility has copy of previous year's Annual Report on file for review? El El • El
Page# 3
Permit: NC0058084
Inspection Date: 06/02/2022
Owner - Facility: Gough Econ WWTP
Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Comment: Discharge Monitoring Reports (eDMRs) were reviewed for the period May 2021
through April 2022. A daily maximum effluent fecal coliform violation was reported in
January 2022. Monitoring violations were reported in January and February 2022.
The Division has previously addressed the violations through the issuances of Notice
of Violations (NOVs).
Only one effluent pH (twice per month required) was performed in December 2021.
This report will address this monitoring violation. In addition, the July and December
2021 and January and April 2022 eDMRs will be revised to correct transcription errors
and flow values (including days with no flow).
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
Comment: On -site field analyses are performed (as of February 2022) under Environmental
Process Solution's field laboratory certification #5695. Statesville Analytical has been
contracted to provide analytical support (all permit parameters except field).
The ORC and staff must ensure all units of measurement is documented for all
calibration and effluent values.
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ El • El
Is sample collected below all treatment units? • El El El
Is proper volume collected? • El El El
Is the tubing clean? ❑ ❑ • ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 ❑ ❑ • ❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • El ❑ ❑
representative)?
Comment: The subject permit requires effluent grab samples.
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, NEED
and sampling location)?
Comment:
Page# 4
Permit: NC0058084
Inspection Date: 06/02/2022
Owner - Facility: Gough Econ WWTP
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable El El El
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: A new ORC and Backup ORC were designated in February 2022. The wastewater
treatment facility appeared to be adequately treating the wastewater, however;
accessibility and maintenance concerns were observed during the inspection. See
"Septic Tank and Sand Filter Sections for additional comments.
Septic Tank Yes No NA NE
(If pumps are used) Is an audible and visual alarm operational? ❑ El • El
Is septic tank pumped on a schedule? • ❑ El El
Are pumps or syphons operating properly? • El El El
Are high and low water alarms operating properly? ❑ El • ❑
Comment: The ORC indicated that the septic tank is pumped once per year.
The septic tank is not accessible for inspection due to the heavy concrete lids. The
permittee must either provide a lift system or replace the lids to allow access to inspect
the septic tank. In addition, the NPDES Permit (Part II, Section D(8) Inspection & Entry)
requires the permittee to allow inspection of any facilities and equipment required
under this permit.
Sand Filters (Low rate)
(If pumps are used) Is an audible and visible alarm Present and operational?
Is the distribution box level and watertight?
Is sand filter free of ponding?
Is the sand filter effluent re -circulated at a valid ratio?
# Is the sand filter surface free of algae or excessive vegetation?
# Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1)
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: Although not excessive, all vegetation needs to be removed and any spent sand
replaced with approved new sand.
The dosing tank was leaking into the sand filter and the mushroom spray nozzles
needed to be either replaced and/or cleaned (if possible). The sand filter's perimeter
block wall also needed maintenance (new coating, etc.) in several locations. Please be
advised that the subject NPDES Permit requires the permittee to properly operate and
maintain the facility at all times [Permit Condition Reference: Part II, Section C(2)
Proper Operation and Maintenance].
Disinfection -Tablet Yes No NA NE
Are tablet chlorinators operational? • El El El
Are the tablets the proper size and type? • ❑ El El
Number of tubes in use? 4
Page# 5
Permit: NC0058084
Inspection Date: 06/02/2022
Owner - Facility: Gough Econ WWTP
Inspection Type: Compliance Evaluation
Disinfection -Tablet Yes No NA NE
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
• ❑ ❑ ❑
Comment: The permittee should provide a means to access the chlorination and dechlorination
contact tanks (concrete lids) as discussed in the Septic Tank Section. The permittee
must ensure that the new accessible lids (if installed) are sealed/elevated to prevent
any stormwater from entering the treatment tanks.
De -chlorination Yes No NA NE
Type of system ? Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)? • ❑ ❑ ❑
Is storage appropriate for cylinders? ❑ ❑ • ❑
# Is de -chlorination substance stored away from chlorine containers? El • ❑ ❑
Are the tablets the proper size and type? • El El El
Comment: The chlorine and dechlor tablets should be stored separately and outside of the metal
cabinet housing the recirculation timer to prevent corrosion and equipment
deterioration.
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
• ❑ ❑ ❑
2
Yes No NA NE
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
Comment: Flow calculations are based on the bucket and stop watch method. This Office
recommends the permittee to investigate the installation of an in -line flow meter due to
the infrequent effluent discharges.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Yes No NA NE
Page# 6
Permit: NC0058084
Inspection Date: 06/02/2022
Owner - Facility: Gough Econ WWTP
Inspection Type: Compliance Evaluation
Effluent Pipe Yes No NA NE
Comment: The facility was not discharging at the time of the inspection. The wastewater inside
the chlorination and dechlorination tanks appeared clear with no floatable solids or
foam. The receiving stream did not appear to be negatively impacted.
Page# 7