HomeMy WebLinkAboutNC0034967_Compliance Evaluation Inspection_20220526ROY COOPER
GoNerror
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS. JR.
airrctor
Mr. Daniel Nicholas
Carolina Glove Company
P.O. Box 999
Conover, NC 28613
Dear Mr. Nicholas:
NORTH'CAROLINA
Envircifimented Quality
May 26, 2022
Subject: Compliance Evaluation Inspection
Carolina Glove Company WWTP
NPDES Permit No. NC0034967
Alexander County
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted
at the subject facility on May 25, 2022, by Ori Tuvia and Michel Mellinger. Brian Eades
cooperation during the site visit was much appreciated. Please advise the staff involved with this
NPDES Permit by forwarding a copy of the enclosed report.
The report should be self-explanatory; however, should you have any questions
concerning this report, please do not hesitate to contact Ori Tuvia at (704) 235-2190, or at
ori.tuvia@ncdenr. gov.
Cc: NPDES, MRO Files (Laserfiche)
Cr-
Sincerely,
DocuSigned by:
11.$01414, H P,ue4
"-F161FB69A2D84A3...
for
W. Corey Basinger
Regional Supervisor
Mooresville Regional Office
Division of Water Resources
North Carolina Drpartrncnt of Enviranmcntal Quality I Division of Water Resources
MooresvillektgionakOffice 161OEast Center Avenue. Smote 301 I Mooresville, North.Caralina 28115
704.663.16911
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code
1 IN I 2 L
21 1 1 1 1
I
1
NPDES yr/mo/day Inspection
3 I NC0034967 111 121 22/05/25 117
Type
1810I
I I 1 1 1
Inspector Fac Type
191 S I 2011
1 1 1 1 11 1 1 1 I I I 1 1 1 1 1 1 I I I I I
1 11
1 1 1 I 1 P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
67I1.0 I 70I4 I 71IN I 72 I N I 731 1 74 751
I I 1
I I I I I I 180
l
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Carolina Glove Company
140 Glove Mill Rd
Taylorsville NC 28681
Entry Time/Date
09:30AM 22/05/25
Permit Effective Date
21/02/01
Exit Time/Date
12:OOPM 22/05/25
Permit Expiration Date
25/03/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Steve Brian Eades/ORC/828-632-5280/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Misty Smith, //828-396-4444/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Facility Site Review Effluent/Receiving Wate Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s)
Michael J Meilinger
Ori A Tuvia
of Inspector(s) Agency/Office/Phone and Fax Numbers
Date
5/26/2022
DocuSigned by:
DWR/MRO WQ/704-235-2183/
_ DWR/MRO WQ/704-663-1699/
BB057A2DE017498...
Signature of Man
Andrew Pitn
Olitivklieviewer Agency/Office/Phone and Fax Numbers Date
r A4'�''' ' N P' 13NR/MRO WQ/704-663-1699 Ext.2180/ 5/26/2022
F161FB69A2D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
NPDES yr/mo/day
31 NC0034967 111 121 22/05/25
I17
Inspection Type
18 [j
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page# 2
Permit: NC0034967
Inspection Date: 05/25/2022
Owner - Facility: Carolina Glove Company
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ ❑
application?
Is the facility as described in the permit? • ❑ El El
# Are there any special conditions for the permit? El • El El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment: The current permit expires on March 31, 2025.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
•
• ❑ ❑ ❑
• ❑ • ❑
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The permittee's records were organized and well maintained and records requested
during the inspection were readily retrievable. DMRs, COCs, ORC logs and calibration
logs were reviewed for the period December 2021 through April 2022.
Page# 3
Permit: NC0034967
Inspection Date: 05/25/2022
Owner - Facility: Carolina Glove Company
Inspection Type: Compliance Evaluation
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ ❑ • ❑
Is sample collected below all treatment units? • ❑ ❑ ❑
Is proper volume collected? ■ ❑ ❑ ❑
Is the tubing clean? ❑ ❑ • ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 ❑ ❑ • ❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • El El El
representative)?
Comment: Grab sampling is required by the subject permit.
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ • ❑
Comment: On -site analyses (temperature) are performed under field laboratory certification
#5062 (Town of Taylorsville). A review of the field instrumentation used on site was
performed during the Town of Taylorsville WWTP inspection (performed prior to this
site inspection). Water Tech Labs, Inc. (Certification #50) performs all remaining
permit -required effluent analyses
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable DOME
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The facility appeared to be well operated and maintained at the time of the inspection.
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots? • ❑ El ❑
Are surface aerators and mixers operational? • ❑ ❑ ❑
Are the diffusers operational? ❑ ❑ • ❑
Page# 4
Permit: NC0034967
Inspection Date: 05/25/2022
Owner - Facility: Carolina Glove Company
Inspection Type: Compliance Evaluation
Aeration Basins
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/I)
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ ❑ •
Comment: Since the previous inspection the facility flooded twice, due to the flooding the blowers
were elevated and were placed on mounts.
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • ❑ ❑ ❑
Is the site free of excessive buildup of solids in center well of circular clarifier? ❑ El • El
Are weirs level? ❑ El • El
Is the site free of weir blockage? ❑ ❑ • ❑
Is the site free of evidence of short-circuiting? • ❑ ❑ ❑
Is scum removal adequate? • ❑ ❑ ❑
Is the site free of excessive floating sludge? ■ ❑ ❑ ❑
Is the drive unit operational? ❑ ❑ • ❑
Is the return rate acceptable (low turbulence)? • ❑ ❑ ❑
Is the overflow clear of excessive solids/pin floc? • ❑ ❑ ❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) • ❑ ❑ ❑
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
Comment: The facility was granted a conditional variance on 9/8/04 to use the facility's water
usage records for the flow measurement calculations and these are being used by the
ORC for DMR reporting.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Yes No NA NE
❑ ❑ • ❑
Page# 5
Permit: NC0034967
Inspection Date: 05/25/2022
Owner - Facility: Carolina Glove Company
Inspection Type: Compliance Evaluation
Effluent Pipe
Comment:
Yes No NA NE
Page# 6