HomeMy WebLinkAboutNC0020389_CSI 04-20-2022_20220523ROY COOPER Governor ELIZABETH S. BISER Secretary RICHARD E. ROGERS, JR. Director NORTH CAROLINA Environ►nental Quality May 23, 2022 Kimberly T. Pickett, MPA, Interim Town Manager Town of Benson PO Box 69 Benson, NC 27504-0069 Subject: Compliance Sampling Inspection Benson WWTP NPDES Permit No. NC0020389 Johnston County Dear Ms. Pickett: On April 20, 2022, Mitch Hayes of the Raleigh Regional Office conducted a compliance sampling inspection at the subject facility. The assistance and cooperation of Brian Leavitt, Operator in Responsible Charge (ORC) and other staff with this inspection was greatly appreciated. Below is a lists of findings developed from the inspection and review of the permit: 1. The permit was issued April 12, 2021, became effective May 5, 2021 and will expire April 30, 2026. 2. Brian Leavitt is listed as the ORC and Christopher M. Brigman is listed as the back-up ORC; however, BIMS status has Mr. Brigman listed as invalid as a result of not having his course certificates not recorded. Please send in copies of Mr. Bridgman's course certificates to certadniin @ncdenr.gav 3. The 1.9 MGD facility consists of the following units: arc bar screen, grit removal, dual manual bar screens, Parshall flume with flow measurement, influent composite sampler, three (3) influent screw pumps, three (3) oxidation ditches (ditches 1 and 3 are used for aeration and ditch 2 is kept anoxic for nutrient removal), five (5) secondary clarifiers, a RAS and WAS pump station, five (5) tertiary filters, a liquid chlorine contact basin, a dechlorination basin with post aeration, an effluent flow meter, effluent composite flow meter, one (1) concrete lined sludge lagoon, two stabilization lagoons/influent flow storage and backup generator. 4. At the time of inspection, the arc bar screen and the grit removal system were operating normally. Screenings are conveyed to a dumpster and disposed in a landfill. One screw pump was in use due to low influent flow, the other two screw pumps are operational but not in use. All rotors in the ditch's 1 and 3 were in operational and run on timers. Foam in the ditches covered less than 50% of the surface area. All five secondary clarifiers were in use. Effluent flowing off the weirs appeared clear. Four out five tertiary filters were on line. The number 1 filter was not operational due to broken aeration disc. Currently there is no repair for the disc. The tertiary filters will be replaced with disc filtration during the next upgrade. Effluent in the dechlorination tank / aeration tank and _EQO r+awrpr� North Carolina Department of Environmental Quality 1 Division of Water Resources Raleigh Regional Office I 3800 Barrett Dnve I Raleigh, North Carolina 27609 919.791.4200 at the effluent appeared clear with no foam or solids. All three sludge lagoons were near full with a staff gage reading of 2.75 feet in lagoon 1. 5. Discharge Monitoring Reports for the period February 2020 through March 2022 were reviewed for compliance with permit limits and monitoring requirements. An NOD was issued for February 2020 for exceeding monthly flow limit; a NOV was issued for exceeding flow for January 2021; a enforcement action was issued for exceeding monthly flow limit for February 2021; a NOD was issued for exceeding weekly BOD average for April 2021; a enforcement action was issued for exceeding weekly average ammonia nitrogen; a enforcement action was issued for exceeding monthly average for BOD and ammonia nitrogen for September 2021; and an enforcement action was issued for exceeding weekly average for BOD and ammonia nitrogen for October 2021. 6. Commercial lab results, chain of custody records, and bench sheets were compared with data submitted on the DMR for the month of March 2022. No discrepancies were noted. 7. The Benson WWTP laboratory # 196 analyzes the following parameters: pH, temperature, DO, TRC, fecal coliform, and conductivity. All other parameters are analyzed by Environment 1 and Meritech Inc. All reagents were within expiration date. 8. The results from the compliance sampling are listed below: A081353 North Carolina Division oLWater Resources Water Sciences Sect on Latroralory Results Loc. been.: sENION 1MY TP County kaktteit Colaetor SAME Vm1D Raydt. Big Report To ffiQ tacaeon ID: Rex Basin WM Curled Date: Mg= Pftorgy Emptying Collect Teem 4$L1. um* mask 218611036185 coc Yee+No Semple Depth Lx. Type: Maul Final Report Bthis report is labeled preliminary report; the results have not been validated. Do not use for Regulatory purposes. Sample iDMOM PO Camber Al Drip Reoand' Tine Recurred tiisl� LAttrorke LogieD newel Method 13108118183810, Final Repot D. ism Ripon Print Deer. 11NI CAS # Aniline Name Sample temperature at receipt by lab It a11Oer LAB 0.s Link c lid Reference .12010 S"Fidaled.Y 42022 MBWIFT MIc BOD 6-Day In liquid 2.0 2.8 06 mplL SM62108-2aot 4211 2 J.JRGEVICH Colitarm. MF Fecal in liquid 1 3000 B3,Q1 CFtY1OO i SM8222D-1887 4n4Y22 J. JRGEVICH NUT 7€84 4 t . fi NH3 as N in liquid 0.02 0.04 nqt ea N EPA 350.1 REV 2 4 28/22 ALWILLUAMS E701177 NO2+NO3 ae N in Riquid 0.04 1.7 P nqR es N EPA 3632 REV 2 42622 ALWILLIAMS 7723-144 Phosphorus total as P in liquid 0.02 0.48 tnW1 u P EPA 365.1 REV 2 4128/22 AIWILLIAMS T[0V. N Total Kjeldah1 N as N in liquid 0.3 netss N EPA 351.2 REV 2 Sf3122 ALWILLIAMs WET Residue Suspended in liquid 2.8 2.8 U,Y not 3M 2540 D 2015 42522 ALWIWAMS MET 7440.02-0 NI by ICPMS 2 0 2.0 U uy+1 EPA200.8 Rev5.4 42722 JJURGEV1CH North Carolina Department of Environmental Quality I Division of Water Resources 512 North Salisbury Street I 1611 Mat] Service Center I Raleigh, North Carolina 27699-161 919 707 9000 VC DNAe. raboralarySeason atinrllr/SampteComments/Qualifirr4Drfmttumr Sample ID ACIIIS$ CAS # Analvte Name EQ. St1>ttlllL LNALthE Unita Mamma Method Date Ito idued.by M IC:Fecal Cd6am•B3-E*Umated-Flbws have counts .60 OR.80 LOC:Fecal Col orm-Q1Sample exceeded holding time poor to receipt at lab UIC. BOD415-Esmnated-GGA standard recovery was a 1080-30 5ngll AC96354 Issalardsoatiala North Carolina Division of Water Resources Water Sciences Scct'on Laboratory Results Lac.Raw B ltegi WWTP County allICSRa Collector Meal Vain) Raglan Btlldeh Report To MCI location I: River BRIM Wm Collect Dee QM= Priority eaMEMnre Emergency Collet Tine. CA Semple Makie Still112161,11 CDC Yeull4o Sample Depth Lac Type InOstat Final Report if this report is labeled preliminary report, the results have not been validated. Da not use for Regulatory purposes. CA3 # Anottsilloox Eca4 dttalllkr twill flag Dale sluludediax LAB Sample temperature at receipt by lab 0.6 'C 420122 MSWIFT SampleID: agnat PO Number ri Date Recir sd: 041202 22 Time Received fJ� Labwa is LoginID Delivery Method iiiedligibmg Final Report Date gm Report Print Date Maga 130D. 5-Day In liquid MIC 2.0 110 GS rig& SPA 5210 B•2001 401/22 .1.1URGEVICH Residue Suspended in liquid 50 WET 142 mg1L SPA 2540 D-2015 4/25122 ALWILLIAMS Vr 1114Ak LaboratorySerhrxo 1 jstd 1SampfiComrmrnls/Qrtd&fur.Drfinrranu S iipl. tD AC16364 CAS # Analyte Name Res U Saimaa& Mattis& Unita Mariam Date ]fit a.male gilt. MIC BOD-05- aurn ed-GGA standad recovery was c tg8*i.30 trngll All results except effluent fecal coliform were within acceptable ranges. The high fecal count could have been due to a contaminated fecal bottle. I would like to thank the staff for their assistance with this inspection. If you have any questions about this letter or the inspection, please contact Mitch Hayes at mitch.haes ncdenr.gpv or at 919.791.4261. Sincerely, WQROS files, Laserfiche Vanessa Manuel, Assistant Regional Supervisor Water Quality Regional Operations Section Raleigh Regional Office Division of Water Resources NC DEQ North Carolina Department of Environmental Quality I Division of Water Resources 512 North Salisbury Street 1 1611 Mail Service Cente; I Raleigh, North Carolina 27699-1611 919 707 9000 K II • ■ 1 AN a !=k • • • 7.11 • • • m • • • • • • • r r 7 _ rl • ME ME1 • • 1 _ ■ �� ■ ■ - r El ■ 7 ■ ■ - . 11 iii fir. 4 im— L.= • .. • ■ ■ " 1 • II II • Ai •;•• 01.0 I'mm ill'Imm. ■ • ,t;wL: rol•t_ ■II 71EIz_.!� " •■ ii• J` . `_■` r.I •1r• 1 1am 1. .111 I T • • •• ▪ mm 1 _ R. • • • • I::: • • • • • • L L a�. • _ 1 • • } • IV 1 • •I ■■ m_741Mi■■ • • ti:1 • United States Environmental Protection Agency EPA Washington, D.C. 20460 Water Compliance Inspection Report Form Approved. OMB No. 2040-0057 Approval expires 8-31-98 Section A: National Data System Coding (Le., PCS) Transaction Code NPDES yr/mo/day Inspection 1 H 2 12 I 3 1 NC0020389 111 12 22/04/20 17 Type 181 s I I I l i l Inspector 191 Fac Type I 201 21IIiI 1111I III I I I I I I I I I I I I I I I I I III I I I I I 166 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA 67I I 70 �3 I 71 I I 72 Lill l ! I —I Reserved 731 1 174 71 1 1 1 1 1 1 I80 Section B: FacilityilData Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include POTW name and NPDES permit Number) Benson WWTP 770 Hannah Creek Rd Benson NC 27504 Entry Time/Date 07:30AM 22/04/20 Permit Effective Date 21/05/01 Exit Time/Date 11:OOAM 22/04/20 Permit Expiration Date 26/04/30 Name(s) of Onsite Representative(s)Rtles(s)1Phone and Fax Number(s) 1/1 Brian Peter Leavittl1919-894-2373 / Brian Peter Leavitt/ORC/919-894-2373/ Other Facility Data Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Keith Ryker Langdon,PO Box 69 Benson NC 275040069/Town Manager/919-894-4953/9198941283 No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenar Records/Reports ll Self -Monitoring Progran Sludge Handling Dispos Facility Site Review Effluent/Receiving Wate 1. Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Crate Mitchell S Hayes DWR/RRO WQ/919-791-4200/ /14ay a3, 2.-o2 2- Signa re of Management Q eviewer Agency/Office/Phone and Fax Numbers Dale ifr EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# 1 NPDES NC0020389 Ji1 12 yr/mo/day 22/04/20 17 Inspection Type 18u (Cont.) 1 Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) The permit was issued April 12, 2021, became effective May 5, 2021 and will expire April 30, 2026. Brian Leavitt is listed as the ORC and Christopher M. Brigman is listed as the back-up ORC; however, BIMS status has Mr. Brigman listed as invalid as a result of not having his course certificates not recorded. Please send in copies of Mr. Bridgman's course certificates to certadmin@ncdenr.gov The 1.9 MGD facility consists of the following units: arc bar screen, grit removal, dual manual bar screens, Parshall flume with flow measurement, influent composite sampler, three (3) influent screw pumps, three (3) oxidation ditches (ditches 1 and 3 are used for aeration and ditch 2 is kept anoxic for nutrient removal), five (5) secondary clarifiers, a RAS and WAS pump station, five (5) tertiary filters, a liquid chlorine contact basin, a dechiorination basin with post aeration, an effluent flow meter, effluent composite flow meter, one (1) concrete lined sludge lagoon, two stabilization lagoons/influent flow storage and backup generator. At the time of inspection, the arc bar screen and the grit removal system were operating normally. Screenings are conveyed to a dumpster and disposed in a landfill. One screw pump was in use due to low influent flow, the other two screw pumps are operational but not in use. All rotors in the ditch's 1 and 3 were in operational and run on timers. Foam in the ditches covered Tess than 50% of the surface area. All five secondary clarifiers were in use. Effluent flowing off the weirs appeared clear. Four out five tertiary filters were on line. The number 1 filter was not operational due to broken aeration disc. Currently there is no repair for the disc. The tertiary filters will be replaced with disc filtration during the next upgrade. Effluent in the dechiorination tank / aeration tank and at the effluent appeared clear with no foam or solids. All three sludge lagoons were near full with a staff gage reading of 2.75 feet in lagoon 1. Discharge Monitoring Reports for the period February 2020 through March 2022 were reviewed for compliance with permit limits and monitoring requirements. An NOD was issued for February 2020 for exceeding monthly flow limit; a NOV was issued for exceeding flow for January 2021; a enforcement action was issued for exceeding monthly flow limit for February 2021; a NOD was issued for exceeding weekly BOD average for April 2021; a enforcement action was issued for exceeding weekly average ammonia nitrogen; a enforcement action was issued for exceeding monthly average for BOD and ammonia nitrogen for September 2021; and an enforcement action was issued for exceeding weekly average for BOD and ammonia nitrogen for October 2021. Commercial lab results, chain of custody records, and bench sheets were compared with data submitted on the DMR for the month of March 2022. No discrepancies were noted. The Benson WWTP laboratory # 196 analyzes the following parameters: pH, temperature, DO, TRC, fecal coliform, and conductivity. All other parameters are analyzed by Environment 1 and Meritech Inc. All reagents were within expiration date. Page# 2 Permit: NC0020389 Owner - Facility: Benson WWTP Inspection Date: 04/20/2022 Inspection Type: Compliance Sampling Operations & Maintenance Yes No NA NE Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑ Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable • ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the perrnittee submitted a new ❑ ❑ • ❑ application? Is the facility as described in the permit? •❑ ❑ ❑ # Are there any special conditions for the permit? ❑ • ❑ ❑ Is access to the plant site restricted to the general public? •❑ ❑ ❑ Is the inspector granted access to all areas for inspection? •❑ ❑ ❑ Comment: No special conditions. Permit was renewed April 12, 2021. Record Keeping Are records kept and maintained as required by the permit? Is all required information readily available, complete and current? Are all records maintained for 3 years (lab. reg. required 5 years)? Are analytical results consistent with data reported on DMRs? Is the chain -of -custody complete? Dates, times and location of sampling Name of individual performing the sampling Results of analysis and calibration Dates of analysis Name of person performing analyses Transported COCs Are DMRs complete: do they include all permit parameters? Has the facility submitted its annual compliance report to users and DWQ? (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift? Is the ORC visitation log available and current? Is the ORC certified at grade equal to or higher than the facility classification? Is the backup operator certified at one grade less or greater than the facility classification? Yes No NA NE • ❑ ❑ ❑ ▪ ❑ ❑ ❑ • ❑ ❑ ❑ 1 ❑ ❑ ❑ • ❑ ❑ ❑ II • • II • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑•❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Page# 3 Permit: NC0020389 Inspection Date: 04/20/2022 Owner - Facility: Benson WWTP Inspection Type: Compliance Sampling Record Keeping Is a copy of the current NPDES permit available on site? Facility has copy of previous year's Annual Report on file for review? Comment: Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ Flow Measurement - Influent Yes No NA NE # Is flow meter used for reporting? 0 • 0 ❑ Is flow meter calibrated annually? • ❑ ❑ ❑ Is the flow meter operational? • 0 0 0 (If units are separated) Does the chart recorder match the flow meter? • 0 0 0 Comment- Effluent flow meter used for reporting. Flow Measurement - Effluent Yes No NA NE # Is flow meter used for reporting? • ❑ 0 0 Is flow meter calibrated annually? • ❑ 0 0 Is the flow meter operational? • 0 ❑ ❑ (If units are separated) Does the chart recorder match the flow meter? MI 0 0 0 Comment: Pump Station - Influent Yes No NA NE Is the pump wet well free of bypass lines or structures? • 0 0 0 Is the wet well free of excessive grease? • ❑ 0 0 Are all pumps present? • 0 0 0 Are all pumps operable? • 0 ❑ 0 Are float controls operable? • 0 0 0 Is SCADA telemetry available and operational? • ❑ 0 0 Is audible and visual alarm available and operational? 0 0 0 • Comment: 4 screw pumps one currently in use due to low influent flow. Bar Screens Type of bar screen a.Manual b.Mechanical Are the bars adequately screening debris? Yes No NA NE • • II ❑ ❑ ❑ Page# 4 Permit: NC0020389 Owner - Facility: Benson WIMP Inspection Date: 04/20/2022 Inspection Type: Compliance Sampling Bar Screens Yes No NA NE Is the screen free of excessive debris? • 0 0 0 Is disposal of screening in compliance? • 0 0 0 Is the unit in good condition? • Cl 0 0 Comment: Grit Removal Type of grit removal a.Manual b.Mechanical Is the grit free of excessive organic matter? Is the grit free of excessive odor? # Is disposal of grit in compliance? Comment: Yes No NA NE o • • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Secondary Clarifier Yes No NA NE Is the clarifier free of black and odorous wastewater? • ❑ ❑ ❑ Is the site free of excessive buildup of solids in center well of circular clarifier? ■ 0 0 0 Are weirs level? • ❑ ❑ ❑ Is the site free of weir blockage? MOOD Is the site free of evidence of short-circuiting? • 0 0 0 Is scum removal adequate? •❑ ❑ ❑ Is the site free of excessive floating sludge? • 0 0 0 Is the drive unit operational? • 0 0 0 Is the return rate acceptable (low turbulence)? • 0 0 0 Is the overflow clear of excessive solids/pin floc? ■ ❑ ❑ ❑ Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) • 0 0 0 Comment' 5 secondary clarifiers. Sludge blankets are kept between 2 to 3 feet. Oxidation Ditches Yes No NA NE Are the aerators operational? II 0 0 0 Are the aerators free of excessive solids build up? • 0 0 0 # Is the foam the proper color for the treatment process? • 0 0 0 Does the foam cover Tess than 25% of the basin's surface? •❑ ❑ ❑ Page# 5 Permit: NC0020389 Owner - Facility: Benson WWTP Inspection Date: 04/20/2022 Inspection Type: Compliance Sampling Oxidation Ditches Is the DO level acceptable? Are settleometer results acceptable (> 30 minutes)? Is the DO level acceptable?(1.0 to 3.0 mg/I) Are settelometer results acceptable?(400 to 800 ml/I in 30 minutes) Yes No NA NE • ❑ ❑ ❑ ❑ ❑ ❑ • • ❑ ❑ ❑ • ❑ ❑ • Comment. Ditches 1 and 3 are used for aeration and ditch 2 is kept anoxic for nutrient removal. Nutrient Removal # Is total nitrogen removal required? # Is total phosphorous removal required? Type # Is chemical feed required to sustain process? Is nutrient removal process operating properly? Comment• chemical feed not required. Filtration (Hiuh Rate Tertiary) Type of operation: Is the filter media present? Is the filter surface free of clogging? Is the filter free of growth? Is the air scour operational? Is the scouring acceptable? Is the clear well free of excessive solids and filter media? Comment: The number one cell is not in operation due to broken discs. Standby Power Is automatically activated standby power available? Is the generator tested by interrupting primary power source? Is the generator tested under load? Was generator tested & operational during the inspection? Do the generator(s) have adequate capacity to operate the entire wastewater site? Is there an emergency agreement with a fuel vendor for extended run on back-up power? Is the generator fuel level monitored? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ Biological ❑ • ❑ ❑ • ❑ ❑ ❑ Yes No NA NE Down flow II ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ II ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Yes No NA NE ▪ ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ■ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Page# 6 Permit: NC0020389 Owner - Facility: Benson WWTP Inspection Date: 04/20/2022 Inspection Type: Compliance Sampling Standby Power Comment: Generators are operated once a week. Yes No NA NE De -chlorination Yes No NA NE Type of system ? Liquid Is the feed ratio proportional to chlorine amount (1 to 1)? 11000 Is storage appropriate for cylinders? ❑ ❑ • 0 # Is de -chlorination substance stored away from chlorine containers? ■ ❑ ❑ ❑ Comment: Are the tablets the proper size and type? ❑ ❑ • 0 Are tablet de -chlorinators operational? ❑ ❑ • ❑ Number of tubes in use? Comment' Liquid Sodium thiosulfate is used for dechlor. Lagoons Yes No NA NE Type of lagoons? Facultative # Number of lagoons in operation at time of visit? 3 Are lagoons operated in? Series # Is a re -circulation line present? 11000 is lagoon free of excessive floating materials? • ❑ ❑ ❑ # Are baffles between ponds or effluent baffles adjustable? ■ ❑ ❑ ❑ Are dike slopes clear of woody vegetation? 111000 Are weeds controlled around the edge of the lagoon? •❑ ❑ ❑ Are dikes free of seepage? • ❑ ❑ ❑ Are dikes free of erosion? • ❑ ❑ ❑ Are dikes free of burrowing animals? •❑ ❑ ❑ # Has the sludge blanket in the lagoon (s) been measured periodically in multiple •❑ ❑ ❑ locations? # If excessive algae is present, has barley straw been used to help control the growth? ❑ ❑ • ❑ Is the lagoon surface free of weeds? 11000 Is the lagoon free of short circuiting? •❑ ❑ ❑ Comment: staff gape reading in lagoon 1 was 2.75 feet. Laboratory Yes No NA NE Page# 7 Permit: NC0020389 Owner - Facility: Benson WWTP Inspection Date: 04/20/2022 Inspection Type: Compliance Sampling Laboratory Yes No NA NE Are field parameters performed by certified personnel or laboratory? • 0 0 0 Are all other parameters(excluding field parameters) performed by a certified lab? • 0 ❑ 0 # Is the facility using a contract lab? • ❑ ❑ Cl # Is proper temperature set for sample storage (kept at less than or equal to 6.0 11 0 0 0 degrees Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? • ❑ 0 ❑ Incubator (BOD) set to 20.0 degrees Celsius +1- 1.0 degrees? ❑ ❑ • 0 Comment. Certified labs used, Environment 1 and Meritech Inc. Disinfection -Liquid Yes No NA NE Is there adequate reserve supply of disinfectant? • ❑ ❑ 0 (Sodium Hypochlorite) Is pump feed system operational? • 0 0 ❑ Is bulk storage tank containment area adequate? (free of leaks/open drains) • ❑ 0 0 Is the level of chlorine residual acceptable? •❑ ❑ ❑ Is the contact chamber free of growth, or sludge buildup? • ❑ ❑ ❑ Is there chlorine residual prior to de -chlorination? • ❑ 0 ❑ Comment: Influent Sampling Yes No NA NE # Is composite sampling flow proportional? • ❑ 0 0 Is sample collected above side streams? 11 0 0 ❑ Is proper volume collected? • ❑ 0 ❑ Is the tubing clean? 11 0 ❑ ❑ # Is proper temperature set for sample storage (kept at less than or equal to 6.0 • 0 0 ❑ degrees Celsius)? Is sampling performed according to the permit? • 0 0 ❑ Comment: Effluent Sampling Yes No NA NE Is composite sampling flow proportional? •❑ ❑ ❑ Is sample collected below all treatment units? • 0 0 0 Is proper volume collected? 11 0 0 0 Is the tubing clean? • 0 0 ❑ Page# 8 Permit: NC0020389 Owner - Facility: Benson WWTP Inspection Date: 04/20/2022 Inspection Type: Compliance Sampling Effluent Sampling # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type representative)? Comment: Yes No NA NE III ❑ ❑ ❑ • ❑ ❑ ❑ Chemical Feed Yes No NA NE Is containment adequate? • ❑ ❑ ❑ Is storage adequate? M 0 ❑ ❑ Are backup pumps available? •❑ ❑ ❑ Is the site free of excessive leaking? • ❑ ❑ ❑ Comment: Sodium hydroxide is added at the influent headworks. Page# 9 11 I I • • • • • 11