HomeMy WebLinkAboutWQ0005173_Compliance Evaluation Inspection_20220510Compliance Inspection Report
Permit: WQ0005173 Effective: 03/01/19
SOC: Effective:
County: Carteret
Region: Wilmington
Contact Person: Doris Speicher
Directions to Facility:
System Classifications: WW2,
Primary ORC: Daniel Edward Fortin
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
WQ0004985
WQ0018525
Expiration: 02/29/24
Expiration:
Title: Registered Agent
Certification: 7180
Owner : Cape Royall Dolphin Association Incorporated
Facility: Cape Royall Dolphin WWTP
304 Cape Fear Loop
Emerald Isle NC 28594
Phone: 252-354-4656
Phone: 252-393-8720
Cape Royall Dolphin Association Incorporated - Cape Royall Dolphin Sewer
System
Barnes Environmental Waste and Hauling Inc - Barnes Environmental RLAP
Inspection Date: 05/10/2022 Entry Time 10:30AM
Primary Inspector: Geoff Kegley
Secondary Inspector(s):
Reason for Inspection: Routine
Permit Inspection Type: High Rate Infiltration
Facility Status: Compliant ❑ Not Compliant
Question Areas:
▪ Treatment Flow Measurement -Effluent
▪ Treatment Flow Measurement -Water
Use Records
▪ Treatment Filters
▪ Treatment Sludge Storage/Treatment
▪ End Use -Infiltration
▪ Standby Power
(See attachment summary)
Exit Time: 12:30PM
Phone:
Inspection Type: Compliance Evaluation
▪ Treatment Flow Measurement -Influent Miscellaneous Questions
▪ Treatment Treatment Barscreen
▪ Record Keeping
▪ Treatment Clarifiers
▪ Treatment Flow Measurement
▪ Wells
▪ Treatment Activated Sludge
▪ Treatment Disinfection
▪ Treatment Return pumps
Page 1 of 7
Permit: WQ0005173 Owner - Facility: Cape Royall Dolphin Association Incorporated
Inspection Date: 05/10/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Inspection Summary:
A routine compliance inspection was conducted at the Cape Royall WWTF and disposal site on May 10, 2022. The
evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified in Permit
WQ0005371. The primary ORC, Dan Fortin, was present during the inspection and was very helpful providing assistance
throughout the inspection.
The facility consists of:
• 10,000 gallon aerated flow EQ tank with grinder pumps
• Flow spitter box
• Dual 25,000 gallon aeration tanks
• Dual 4,765 gallon clarifiers
• Dual tertiary filters
• 2,700 gallon clear well and 2,890 gallon mud well
• Dual aerated sludge digester tanks
• Dual tablet type disinfection chlorinators
• 8,500 gallon dosing tank
• Disposal via dual 80 foot diameter rotary distributors with stationary low pressure piping network and washed stone
infiltration system within rotary walls
According to the monitoring reports, the plant has been treating an average of approximately 4,200 gpd for the last few
months, the permitted flow is 50,000 gpd.
One NOV was issued for effluent fecal exceedances in February 2022 and one NOV and civil penalty was issued for
ammonia in January 2022. They were in the process of shutting down one side of the plant and were trying to establish the
mixed liquor. Effluent has been in compliance since. Prior to these exceedances monitoring records have generally shown
consistent compliance with permit limits.
Groundwater monitoring has been generally compliant except for some erratic TDS exceedances which are common in the
barrier island environment. Nitrates in monitoring wells are consistently compliant, despite higher nitrates levels in the
effluent (the plant is not designed to denitrify and does not have a total nitrate effluent limit).
The facility is deemed compliant with the non -discharge permit WQ0005173.
Page 2 of 7
Permit: WQ0005173 Owner - Facility: Cape Royall Dolphin Association Incorporated
Inspection Date: 05/10/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Type
Reuse (Quality)
Lagoon Spray, LR
Single Family Spray, LR
Activated Sludge Spray, LR
Activated Sludge Spray, HR
Activated Sludge Drip, LR
Recycle/Reuse
Single Family Drip
Infiltration System
Treatment
Are Treatment facilities consistent with those outlined in the current permit?
Do all treatment units appear to be operational? (if no, note below.)
Comment:
Treatment Flow Measurement -Influent
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
Comment:
Treatment Flow Measurement -Water Use Records
Is water use metered?
Are the daily average values properly calculated?
Comment:
Treatment Flow Measurement -Effluent
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
Comment: Flow meter was calibrated by Delta on 4/6/2022.
Standby Power
Is automatically activated standby power available?
Yes No NA NE
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
Yes No NA NE
❑ ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
II ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
Page 3 of 7
Permit: WQ0005173 Owner - Facility: Cape Royall Dolphin Association Incorporated
Inspection Date: 05/10/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Is generator tested weekly by interrupting primary power source? • ❑ ❑ ❑
Is generator operable? • ❑ ❑ ❑
Does generator have adequate fuel? ❑ ❑ ❑ •
Comment: Auto transfer and generator was tested during inspection and is operational, generator is
leased and on a maintenance contract.
Treatment Barscreen
Is it free of excessive debris?
Is disposal of screenings in compliance?
Are the bars spaced properly?
Is the unit in good condition?
Comment: Grinder pumps in EQ basin.
Yes No NA NE
❑ ❑ • ❑
❑ ❑ • ❑
Treatment Activated Sludge Yes No NA NE
Is the aeration mechanism operable? • ❑ ❑ ❑
Is the aeration basin thoroughly mixed? • ❑ ❑ ❑
Is the aeration equipment easily accessed? • ❑ ❑ ❑
Is Dissolved Oxygen adequate? ❑ ❑ ❑ •
Are Settleometer results acceptable? ❑ ❑ ❑ •
Is activated sludge an acceptable color? • ❑ ❑ ❑
Comment: Regional water supply is from an RO system therefore the ORC is adding sodium bicarbonate
routinely to maintain alkalinity.
Treatment Clarifiers
Are the weirs level?
Are the weirs free of solids and algae?
Is the scum removal system operational?
Is the scum removal system accessible?
Is the sludge blanket at an acceptable level?
Is the effluent from the clarifier free of excessive solids?
Comment:
Treatment Return pumps
Are they in place?
Are they operational?
Comment:
Treatment Filters
Is the filter media present?
Is the filter media the correct size and type?
Is the air scour operational?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
▪ ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
Page4of7
Permit: WQ0005173 Owner - Facility: Cape Royall Dolphin Association Incorporated
Inspection Date: 05/10/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Is the scouring acceptable?
Is the clear well free of excessive solids?
Is the mud well free of excessive solids and filter media?
Does backwashing frequency appear adequate?
Comment: Filters do not have auto backwash, therefore it is performed manually on a daily basis.
Operation was tested during inspection.
Treatment Sludge Storage/Treatment
Is the aeration operational?
Is the aeration pattern even?
If required, are Sanitary "Ts" present in tankage?
Comment: Residuals are hauled by Barnes Environmental (WQ0018525).
Treatment Disinfection
Is the system working?
Do the fecal coliform results indicate proper disinfection?
Is there adequate detention time (>=30 minutes)?
Is the system properly maintained?
If gas, does the cylinder storage appear safe?
Is the fan in the chlorine feed room and storage area operable?
Is the chlorinator accessible?
If tablets, are tablets present?
Are the tablets the proper size and type?
Is contact chamber free of sludge, solids, and growth?
If UV, are extra UV bulbs available?
If UV, is the UV intensity adequate?
# Is it a dual feed system?
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000- - )
If yes, then when was the RMP last updated?
Comment:
Record Keeping
Is a copy of current permit available?
Are monitoring reports present: NDMR?
NDAR?
Are flow rates less than of permitted flow?
Are flow rates less than of permitted flow?
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
•
• ❑ ❑ ❑
▪ •
❑ ❑•❑
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
❑ ❑•❑
• ❑ ❑ ❑
❑ ❑ • ❑
❑ ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page5of7
Permit: WQ0005173 Owner - Facility: Cape Royall Dolphin Association Incorporated
Inspection Date: 05/10/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Are application rates adhered to?
Is GW monitoring being conducted, if required (GW-59s submitted)?
Are all samples analyzed for all required parameters?
Are there any 2L GW quality violations?
Is GW-59A certification form completed for facility?
Is effluent sampled for same parameters as GW?
Do effluent concentrations exceed GW standards?
Are annual soil reports available?
# Are PAN records required?
# Did last soil report indicate a need for lime?
If so, has it been applied?
Are operational logs present?
Are lab sheets available for review?
Do lab sheets support data reported on NDMR?
Do lab sheets support data reported on GW-59s?
Are Operational and Maintenance records present?
Were Operational and Maintenance records complete?
Has permittee been free of public complaints in last 12 months?
Is a copy of the SOC readily available?
No treatment units bypassed since last inspection?
Comment:
End Use -Infiltration
# Is the application High Rate or Low Rate?
Are buffers maintained?
Are any supply wells within the CB?
Are any supply wells within 250' of the CB?
Is municipal water available in the area?
Are GW monitoring wells required?
Are GW monitoring wells located properly w/ respect to RB and CB?
Are GW monitoring wells properly constructed, including screened interval?
Is a usable green area maintained?
Is the disposal site acceptable?
Is the distribution equipment acceptable?
Is the disposal site free of ponding?
Is the disposal site free of breakout?
Are the disposal sites free of solids, algae, etc.?
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Yes No NA NE
High Rate
• ❑ ❑ ❑
❑ ❑ ❑ •
❑ ❑ ❑ •
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page6of7
Permit: WQ0005173 Owner - Facility: Cape Royall Dolphin Association Incorporated
Inspection Date: 05/10/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Do the records show that the fields are properly maintained?
Are the disposal sites free of vegetation?
Do any surface water features appear to be adversely impacted by GW discharge?
No chemicals or rototiller used to eliminate vegetation, solids, algae, etc.?
Comment:
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Page 7 of 7