June 19., 2001
Mr. D. Stephen Jones, President
Lake Creek Corporation, Bay Tree Lakes
PO Box 650
Clinton, NC 28329
SUBJECT: Compliance Evaluation Inspection
Bay Tree Lakes Wastewater Treatment Plant
NPDES Permit No. NC0036404
Bladen County
Dear Mr. Jones:
Enclosed is a report concerning the Compliance Evaluation Inspection conducted at the Bay
Tree Lakes Wastewater treatment facility on June 12, 2001. •
The observations, conclusions, and recommendations from the inspection • are in Part D,
"Summary of Findings/Comments" of this report. Hopefully, this discharge will be eliminated in
the near future with construction.of a land application system. At thi time, however, I do not have
an estimate of when that permit will be issued. •
Please review the attached report. Ofparticular importance is Item D(7), which asks for a
response no later than July 2, 2001. If you or your staff have any questions, do not hesitate to
contact me at 910-486-1541, ext. 722.
KAJka
• Enclosures
Sincerely,
(..
Environmental Specialis
Ken Averitte
225 GREEN STREET - SUITE 7141 SYSTEL BUILDING / FAYETTEVILLE, NC 28301-5043
• PHONE (910) 486-1541 FAX (910) 486-0707 WWW.ENR.STATE.NC.US/ENR/
AN N EQUAL OPPORTUNITY / AFFIRMATIVE ACTION EMPLOYER - 50% RECYCLED/10% POST CONSUMER PAPER
DENR TOLL FREE HOTLINE: 1-877-623-6748 '
NPDES COMPLIANCE INSPECTION REPORT
North Carolina Division of Water Quality
Fayetteville Regional Office
Section A. National Data System Coding
Transaction Code: N NPDES NO. NC0036404 Date: 010612 Inspection Type: C
Inspector: S Facility Type: 2 . Reserved.
Facility Evaluation Rating: 2 BI: N QA: N Reserved.
Section B: Facility Data
• Name and Location of Facility Inspected:
Lake Creek Corporation, (Bay Tree Lakes) WWTP
c/o P.O. Box 650.
Clinton, NC 28329
Entry Time: 10:30 am
Exit Time/Date: 12:40 pm 010612 •
Name(s), Title(s) of On -Site Representative(s):
William M. Steedly (Certified Grade IV) - "ORC"
Phone Number(s): (910) 588-4432
Name, Title and Address of Responsible Official:
Mr. D. Stephen Jones, President
Lake Creek Corporation
P.O. Box 650, Clinton, NC 28329
Nection C: Areas Evaluated During Inspection
Permit Effective Date: 960801
Permit Expiration Date: 020131
Contacted: yes
(S = Satisfactory, M = Marginal, U = Unsatisfactory, N = Not Evaluated, N/A = Not Applicable)
Permit: S.
• Records/Reports:. M
Facility Site Review: S
Flow Measurement: `M
Laboratory: N
Pretreatment: N/A
.:Effiuenf/Receiving.Waters:. S
Compliance Schedule: N/A
Self -Monitoring Program: M
Operation &:Maintenance: S
Sludge Disposal:.M
•-Other:.
Section D: Summary of Findings/Comments:
1. The waste at this facility is 100% domestic from a water oriented residential development.
2. This WWTP is a 20,000 gpd extended aeration plant with an aerated sludge digester, a sludge
holding basin, tablet chlorinator, flow measurement, and a "polishing" pond.with approximately 90
days holding capacity.
3. At the time of the inspection, one of the plant's sludge return lines was clogged and inoperable. The
ORC completed repairs to this line during the course of the inspection.
I
4. There is some doubt as to the accuracy of the facility's flow meter. IA sticker inside the meter panel
indicates that the last calibration of this equipment took place in i cto1ber of 1997. As discussed at
the time of the inspection, this warrants immediate attention.
5. Sludge levels in both clarifiers appeared to be excessively high, within 12"-14" of the surface.
Wasting of sludge is obviously required. However, at this time, tHereiis no known sludge disposal
program identified, aside from the storage basin between the plant and the long term detention pond.
A method of actually disposing of sludge completely out of the system would greatly benefit this
facility. -
6. The tablets used in the disinfection system were. noted to be for swimming pool use. Tablets for this
system should be specifically for use with wastewater applications.'•
7 A compliance evaluation review of the last 12 months of self monitoring data did not reveal any
monthly effluent limits violations (copy attached). However, this review discovered that no
monitoring data has been received for the month of Septe»aber, 2000. Please provide the
monitoring report for that month to the Fayetteville Regional Office no later than July 2, 2001.
8. As discussed during the inspection, laboratory records are to be m dint lined on -site. Historically, the
ORC has kept this data at his home. These reports must be kept available at Bay Tree Lakes.
I •
Name and Signature of Inspector Agency/Office/Telephone
DENR/Fayetteville/(910)48 6-1541
I 'I
Ken Averit
Name and Signature of Reviewer
Belinda Henson
Action Taken
. Agency/Office/Telephone
DENR/Fayetteville/(910)486-1541
Regulatory Office Use Only
Compliance Status
_Noncompliance
Compliance
Date
Date
L-lS-O
D ate
7
GKEX88/MP 06/18/�.;001
COMPLIANCE EVALUATION ANALYSIS REPORT PAGE 1
PERMIT--NC0036404 PIPE--001 REPORT PERIOD: 0005-0104 .LOC---E
FACILITY --LAKE CREEK CORP-BAY TREE LAKES DESIGN FLOW-- .0200 CLASS--0
LOCATION-=CLINTON REGION/COUNTY--06 BLADEN
50050 00310 00530 00610 31616 50060 00300 00010
MONTH Q/MGD BOD RES/TSS NH3+NH4- FEC COLI CHLORINE DO TEMP
LIMIT F .0200 F 5.00 F 30.0 F 2.00 F 200.0 F 6.00
00/05
00/06
00/07
00/08
00/10
LIMIT F .02.00 F 10.00 F 30.0 F 4.00 F 200.0 F 6.00
00/11
LIMIT F .0200 F 10.00 F 30.0 F 4.00 F 200.0 NOL NOL NOL
00/12 .0162 5.50 3.4 3.90 1.0 .000 6.50 7.47
01/01 .0162 6.00 6.5 3.90 1.7 ..000 6.40 8.50
)1/02 .0162 8.00 6.7 3.80 1.0 .000 6.40 12.80
)1/03 .0162 7.50 7.9 2.60 2.0 .000 6.40 14.70
JIMIT F .0200 F. 5.00 F 30.0 F 2.00 F 200.0 NOL F 6.00 NOL
)1/04
WERAGE .0162 6.75 6.1 3.55 1.4 .000 . 6.42 10.86
MAXIMUM .0162 8.00 7.9 3.90 2.0 6.50 14.70
MINIMUM .0162 5.50 3.4 2.60 1.0 .000 6.40 7.47
JNIT MGD MG/L MG/L MG/L #/100ML MG/L MG/L .Q4
.GKEX88/MP
COMPLIANCE EVALUATION ANALYSIS REPORT
1
PERMIT--NC0036404 PIPE--001 REPORT PERIOD: 0005-0104 LOC---E
FACILITY --LAKE CREEK CORP-BAY TREE LAKES DESIGN FLOW-- .0200 CLASS-0
LOCATION--CLINTON REGION/COUNTY -06 BLADEN
00400
MONTH PH
LIMIT 9.0 6.0
00/05
00/06
00/07
00/08
00/10
LIMIT 9.0 6.0
00/11
LIMIT 9.0 6.0
00/12 _7.2-7.1
01/01 7.2-7.0
01/02 7.1-7.0
01/03 7.2-7.0
LIMIT. 9.0 6.0
01/04
AVERAGE
MAXIMUM 7.200
MINIMUM 7.000
UNIT SU
06/18/2001
PAGE 2
• INSPECTION REPORT
UPDATE OPTION: TRX: 5IF KEY: NC0036404INSCEI 010612
SYSMSG: *** DATA MODIFIED SUCCESSFULLY ***
PERMIT--- NC0036404 REG/COUNTY-- 06 BLADEN
FACILITY-- LAKE CREEK CORP-BAY TREE LAKES LOC-- CLINTON
INS TYPE NEXT PLANNED
rIVT
INSPECTION INSPECTED BY:
DATE: 010612 AK
REPORT
DATE
010619
COMMENTS:
INSPECTION DMR RESPONSE RECEIVED
STATUS STATUS DUE DATE DATE
C 010702