SUBJECT: Compliance Inspection Report
Sea Isle Plantation North WWTP
Non -discharge Permit No. WQ0013027
Carteret County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Sea Isle Plantation North
WWTP on 4/12/2022. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in Non -discharge Permit No. WQ0013027. The
findings and comments noted during this inspection are provided in the enclosed copy of the inspection
report entitled "Compliance Inspection Report".
The current permit expired on March 31, 2022 and a renewal application was uploaded on April 13, 2022.
Please note for the future that the permit requires the submittal of a renewal application no later than six
months prior to expiration.
If you should have any questions, please do not hesitate to contact Helen Perez with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
helen.perez@ncdenr.gov.
ATTACHMENTS
Cc: Dan Fortin — electronic copy
Upload to Laserfiche
ODE
mw�.mwemw�mMm n�.��
Sincerely,
DocuSigned by:
Hogit4. $i.s•c &
'-E3ABA14AC7DC434...
Morella Sanchez -King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
North Carolina Department of Environmental Quality I Division of Water Resources
Wilmington Regional Office 1127 Cardinal Drive Extension Wilmington. North Carolina 28405
910.796.7215
DocuSign Envelope ID: 6CD2AE98-7D05-4596-8935-2CA06031 C6D2
I� DE
North Carolina Department of Environmental Quality I Division of Water Resources
Wilmington Regional Office 1127 Cardinal Drive Extension I Wilmington, North Carolina 28405
910.796.7215
Department w umwam,mmi aav�
DocuSign Envelope ID: 6CD2AE98-7D05-4596-8935-2CA06031 C6D2
Compliance Inspection Report
Secondary Inspector(s):
Permit: WQ0013027 Effective: 04/10/17 Expiration:
SOC: Effective: Expiration:
County: Carteret
Region: Wilmington
Contact Person: Robert C Howard Title: ORC
03/31/22 Owner : The Sea Isle Plantation North Homeowners
Association
Facility: Sea Isle Plantation North WWTP
Sea Isle N Dr
Indian Beach NC 28512
Phone: 252-241-5460
Directions to Facility:
Take NC 58 East/North about one mile past Indian Beach. Facility is on the left, prior to Pine Knoll Shores.
System Classifications: WW3.,
Primary ORC: Robert C Howard Certification: 996013
Secondary ORC(s):
On -Site Representative(s):
On -site representative Daniel Edward Fortin
Related Permits:
Inspection Date: 04/12/2022 Entry Time 11:OOAM
Primary Inspector: Helen I Perez—DocuSigned by:
412,m, \''en,e,25
�1D645B4A39694BE...
Tyler G Benson( DocuSigned by:
fii1ttx 15u&sbla,
—06DCAE2DD754468...
Permit Inspection Type: High Rate Infiltration
Facility Status: Compliant El Not Compliant
Reason for Inspection: Routine
Question Areas:
▪ Treatment Flow Measurement -Effluent
▪ Treatment Flow Measurement -Water
Use Records
▪ Record Keeping
▪ End Use -Infiltration
▪ Standby Power
(See attachment summary)
Exit Time: 12:OOPM
Phone: 252-241-5460
252-393-8720
Phone: 910-796-7387
Inspection Type: Compliance Evaluation
▪ Treatment Flow Measurement -Influent
▪ Treatment
II Treatment Activated Sludge
▪ Treatment Flow Measurement
▪ Miscellaneous Questions
▪ Treatment Filters
▪ Treatment Disinfection
▪ Treatment Return pumps
Page 1 of 6
DocuSign Envelope ID: 6CD2AE98-7D05-4596-8935-2CA06031 C6D2
Permit: WQ0013027 Owner - Facility: The Sea Isle Plantation North Homeowners Association
Inspection Date: 04/12/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Inspection Summary:
A routine compliance inspection of the Sea Isle Plantation North WWTF was conducted on April 12, 2022. The purpose of
the evaluation was to verify that the facility is operating in compliance with the conditions and limitations specified in
Non -Discharge Permit WQ0013027. Dan Fortin and Robert Howard of Fortin Contract Service were present during the
inspection.
This facility is a 40,000 GPD extended aeration plant with two rotary distributor, high -rate infiltration disposal fields. During
2021, flows peaked to a little over 4,000 GPD in the summer and had very low flows during the winter months. Due to mostly
seasonal residential occupancy and the flow from a Septic Tank Effluent Pumping (STEP) collection system, the plant treats
an influent high in TKN. This issue has caused many effluent exceedances in Total Nitrogen during this permit cycle. After a
review of GW-59 monitoring reports, there appears to be no evidence of groundwater quality standard violations for Nitrogen
in the three monitoring wells on site. Since requesting technical assistance from Tom Tharrington of the Wilmington Regional
Office (WIRO) in 2019, operators have raised the level and increased aeration and mixing time in the EQ tank as
recommended, which improved treatment. In 2021, Mag meters in the EQ tank and common tank disabled flow control and
Total Nitrogen was exceeded for many months. Covid related issues with suppplies delayed repairs. Since Jauary 2022, all
repairs have been made and TKN has been trending down.
The current permit expired on March 31, 2022. The new property management company, Chalk and Gibbs, has been in
contact with the WIRO for guidance on the renewal process. The renewal application was uploaded on April 13, 2022.
Please note for future reference that the permit requires the submittal of a renewal application no later than six months prior
to expiration.
The facility is compliant with Non -Discharge Permit WQ0013027. Please review the comment sections of the inspection
report for more details.
Page 2 of 6
DocuSign Envelope ID: 6CD2AE98-7D05-4596-8935-2CA06031 C6D2
Permit: WQ0013027 Owner - Facility: The Sea Isle Plantation North Homeowners Association
Inspection Date: 04/12/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Type
Reuse (Quality)
Lagoon Spray, LR
Single Family Spray, LR
Activated Sludge Spray, LR
Activated Sludge Spray, HR
Recycle/Reuse
Activated Sludge Drip, LR
Single Family Drip
Infiltration System
Treatment
Are Treatment facilities consistent with those outlined in the current permit?
Do all treatment units appear to be operational? (if no, note below.)
Comment: No comment.
Treatment Flow Measurement -Influent
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
Comment:
Treatment Flow Measurement -Water Use Records
Is water use metered?
Are the daily average values properly calculated?
Comment:
Treatment Flow Measurement -Effluent
Is flowmeter calibrated annually?
Is flowmeter operating properly?
Does flowmeter monitor continuously?
Does flowmeter record flow?
Does flowmeter appear to monitor accurately?
Comment: The effluent flowmeter was calibrated on 3/23/2022 by Delta Systems Inc.
Standby Power
Is automatically activated standby power available?
Yes No NA NE
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
Yes No NA NE
❑ ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
Page 3 of 6
DocuSign Envelope ID: 6CD2AE98-7D05-4596-8935-2CA06031 C6D2
Permit: WQ0013027 Owner - Facility: The Sea Isle Plantation North Homeowners Association
Inspection Date: 04/12/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Is generator tested weekly by interrupting primary power source?
Is generator operable?
Does generator have adequate fuel?
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: A portable generator was on site and was operational and transferred power to plant when
main power source was shut off. A permanent generator has been ordered to replace the
portable unit.
Treatment Activated Sludge
Is the aeration mechanism operable?
Is the aeration basin thoroughly mixed?
Is the aeration equipment easily accessed?
Is Dissolved Oxygen adequate?
Are Settleometer results acceptable?
Is activated sludge an acceptable color?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
❑ ❑ ❑ •
• ❑ ❑ ❑
Comment: The 2 anoxic tanks both have ORP sensors and the 2 aeration tanks have DO sensors for
process control monitoring. In addition, ammonia and nitrate strips are used along with
settleometer testing for monitoring plant treatment.
Treatment Return pumps
Are they in place?
Are they operational?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: There are 4 telescoping valves located in a mixed -liquor recycle tank to adjust the flow of RAS.
Treatment Filters
Is the filter media present?
Is the filter media the correct size and type?
Is the air scour operational?
Is the scouring acceptable?
Is the clear well free of excessive solids?
Is the mud well free of excessive solids and filter media?
Does backwashing frequency appear adequate?
Comment: The dual tertiary filters are backwashed manually once a day.
Treatment Disinfection
Is the system working?
Do the fecal coliform results indicate proper disinfection?
Is there adequate detention time (>=30 minutes)?
Is the system properly maintained?
If gas, does the cylinder storage appear safe?
Is the fan in the chlorine feed room and storage area operable?
Is the chlorinator accessible?
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ ❑ •
❑ ❑ ❑ •
❑ ❑ ❑ •
• ❑ ❑ ❑
• ❑❑❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page 4 of 6
DocuSign Envelope ID: 6CD2AE98-7D05-4596-8935-2CA06031 C6D2
Permit: WQ0013027 Owner - Facility: The Sea Isle Plantation North Homeowners Association
Inspection Date: 04/12/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
If tablets, are tablets present?
Are the tablets the proper size and type?
Is contact chamber free of sludge, solids, and growth?
If UV, are extra UV bulbs available?
If UV, is the UV intensity adequate?
# Is it a dual feed system?
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000- - )
If yes, then when was the RMP last updated?
Comment: No comment.
Record Keeping
Is a copy of current permit available?
Are monitoring reports present: NDMR?
NDAR?
Are flow rates less than of permitted flow?
Are flow rates less than of permitted flow?
Are application rates adhered to?
Is GW monitoring being conducted, if required (GW-59s submitted)?
Are all samples analyzed for all required parameters?
Are there any 2L GW quality violations?
Is GW-59A certification form completed for facility?
Is effluent sampled for same parameters as GW?
Do effluent concentrations exceed GW standards?
Are annual soil reports available?
# Are PAN records required?
# Did last soil report indicate a need for lime?
If so, has it been applied?
Are operational logs present?
Are lab sheets available for review?
Do lab sheets support data reported on NDMR?
Do lab sheets support data reported on GW-59s?
Are Operational and Maintenance records present?
Were Operational and Maintenance records complete?
Has permittee been free of public complaints in last 12 months?
Is a copy of the SOC readily available?
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
❑ ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑•
❑ ❑ ❑ •
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
• ❑ ❑ ❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ ❑ •
❑ ❑ ❑ •
❑ ❑ ❑ •
• ❑ ❑ ❑
Page 5 of 6
DocuSign Envelope ID: 6CD2AE98-7D05-4596-8935-2CA06031 C6D2
Permit: WQ0013027 Owner - Facility: The Sea Isle Plantation North Homeowners Association
Inspection Date: 04/12/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
No treatment units bypassed since last inspection?
• ❑ ❑ ❑
Comment: A review of groundwater monitoring shows periodic TDS exceedances in MW #1 and #3, which
is not uncommon in a barrier island.
End Use -Infiltration
# Is the application High Rate or Low Rate?
Are buffers maintained?
Are any supply wells within the CB?
Are any supply wells within 250' of the CB?
Is municipal water available in the area?
Are GW monitoring wells required?
Are GW monitoring wells located properly w/ respect to RB and CB?
Are GW monitoring wells properly constructed, including screened interval?
Is a usable green area maintained?
Is the disposal site acceptable?
Is the distribution equipment acceptable?
Is the disposal site free of ponding?
Is the disposal site free of breakout?
Are the disposal sites free of solids, algae, etc.?
Do the records show that the fields are properly maintained?
Are the disposal sites free of vegetation?
Do any surface water features appear to be adversely impacted by GW discharge?
No chemicals or rototiller used to eliminate vegetation, solids, algae, etc.?
Yes No NA NE
High Rate
• ❑ ❑ ❑
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: Work was recently done to clear vegetation around the outside of the fenced area of the site to
improve access to the monitoring wells and to eliminate any hanging branches over the
infiltration fields. Fields were in good condition, with no ponding, vegetation or breakout
observed. Monitoring wells appeared to be in good condition.