HomeMy WebLinkAboutNC0055255_Compliance Evaluation Inspection_20220425ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
Jones Estates Bay Country, LLC
Attn: Jason Freed, Owner
2310 South Miami Blvd, Ste 238
Durham, NC 27703
NORTH CAROLINA
Environmental Quality
April 25, 2022
SUBJECT: Compliance Evaluation Inspection & Notice of Deficiency
NOD #: NOD-2022-PC-0053
Crown Mobile Home Park Wastewater Treatment Plant
NPDES Permit Number NC0055255
Guilford County
Dear Mr. Freed:
Mr. Ron Boone, of the NC Division of Water Resources (NCDWR), Winston-Salem Regional
Office (WSRO), conducted a compliance evaluation inspection of the Crown mobile home park
wastewater treatment plant, on March 23, 2022. Mr. Boone met with Hal Young, Operator in
Responsible Charge (ORC), and Bradley Flynt, Backup ORC. Their assistance and cooperation
was greatly appreciated. Inspection findings are detailed in the attached Water Compliance
Inspection Report and summarized below.
- The plant appears to be in good condition with minimal corrosion or other structural issues.
- The mixed liquor appears healthy with no foul odors.
- The effluent from the clarifiers appears clear with no pin floc and the weirs appear level.
- The flow meter is due for calibration in June, 2022.
- The effluent flow sampler is set up to pull constant time/constant volume samples. It must be
set up to pull flow proportional samples.
- The effluent appears clear with no detectable solids or foam, and no foul odor. The receiving
stream looks good.
- All reviewed documentation was compliant and all required documentation was readily
available, complete, and current.
Mr. Boone noted no other concerns, deficiencies, or violations.
Please be aware that the Division may take enforcement action against any permittee who fails to
comply with any requirement of their permit. Pursuant to NC General Statute (NCGS) 143-215.6A,
a civil penalty of not more than twenty-five thousand dollars ($25,000.00) may be assessed against
any person who violates or fails to act in accordance with the terms, conditions, or requirements
of any permit issued pursuant to G.S. 143-215.1.
GDE
NORTH C OLI JA '
omm mr� ep..of o�.i
North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1450 W. Hanes Mill Rd, Suite 300 I Winston-Salem, North Carolina 27105
336.776.9800
If you have any questions or concerns, please do not hesitate to contact Mr. Boone by phone at
336-776-9690, or by email at ron.boone@ncdenr.gov. Thank you in advance for your time and
attention to this matter.
Sincerely,
DocuSigned by:by�
. 3 -rMJCr
145B49E225C94EA...
Lon T. Snider, Regional Supervisor
Water Quality Regional Operations Section
Winston-Salem Regional Office
Division of Water Resources, NCDEQ
Attachments:
1. Water Compliance Inspection Report
cc: Laserfiche
Hal Young, ORC (via email william.young@greensboro-nc.gov)
D_E
NORTH CAROLINA
gaparMeM of Environment,/quay
North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1450 W. Hanes Mill Rd, Suite 300 I Raleigh, North Carolina 27105
336.776.9800
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction
1 IN
Code
I 2
IL
NPDES yr/mo/day Inspection Type Inspector Fac
I 3 I NC0055255 111 121 22/03/23 117 1810I 19I S I 2011
Type
21IIIIII
IIIIIIIIIII
IIIIIII
I
IIIIII
IIIIIIIIIII
P6
Inspection
671
Work Days
Facility Self -Monitoring
I 70I
Evaluation Rating
I 711
B1
1
72
QA
I N I
73I
1
I I
Reserved
74 71
I
I I
I
I
I
180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES Dermit Number)
Crown Mobile Home Park
6201 Jonquil Dr
Greensboro NC 27407
Entry Time/Date
12:30PM 22/03/23
Permit Effective Date
17/01/01
Exit Time/Date
01:30PM 22/03/23
Permit Expiration Date
21/08/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
William H Young/ORC/336-627-1009/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Jason Freed,2310 S Miami Blvd Ste 238 Durham NC 27703//917-225-9614/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ron DBo0genedby: DWR/WSRO WQ/336-776-9690/
osiaecl Boo,ve 4/25/2022
"—B20F8DD5F2A3460...
Signature
of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
FDocuSigned by:
L—o, T. StiAc>_ 4/25/2022
EPA Form �35 (�f
'-145 49 2 �-S3 C EA ..
ev 9-94) Previous editions are obsolete.
Page# 1
3I
NPDES yr/mo/day
N C0055255 111 121 22/03/23
I17
Inspection Type
18 [j
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Ron Boone, of the NC Division of Water Resources (DWR), Winston-Salem Regional Office, met with
Hal Young, Operator in Responsible Charge (ORC), and Bradley Flynt, Backup ORC, on 3/23/2022,
to perform a compliance evaluation inspection of the Crown mobile home park wastewater treatment
plant. Below is a summary of the inspection findings.
- The plant appears to be in good condition with minimal corrosion or other structural issues.
- The mixed liquor appears healthy with no foul odors.
- The effluent from the clarifiers appears clear with no pin floc and the weirs appear level.
- The flow meter is due for calibration in June, 2022.
- The effluent flow sampler is set up to pull constant time/constant volume samples. It must be set up
to pull flow proportional samples.
- The effluent appears clear with no detectable solids or foam, and no foul odor. The receiving
stream looks good.
- All reviewed documentation was compliant and all required documentation was readily available,
complete, and current.
Mr. Boone noted no other concerns, deficiencies, or violations.
Page# 2
Permit: NC0055255
Inspection Date: 03/23/2022
Owner - Facility: Crown Mobile Home Park
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new MODE
application?
Is the facility as described in the permit? ❑ • ❑ ❑
# Are there any special conditions for the permit? ❑ • ❑ ❑
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment: The facility now employs UV disinfection but still maintains the
chlorination/dechlorination systems for backup purposes.
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Comment: None
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ • ❑ ❑
Is sample collected below all treatment units? • ❑ ❑ ❑
Is proper volume collected? • ❑ ❑ ❑
Is the tubing clean? • ❑ ❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 ❑ ❑ ❑ •
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type ❑ ❑ ❑ •
representative)?
Comment: Sampler is set to sample on a constant volume/constant time basis. It must be set up to
pull flow proportional composite samples.
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, El El El
and sampling location)?
Comment: None
Page# 3
Permit: NC0055255
Inspection Date: 03/23/2022
Owner - Facility: Crown Mobile Home Park
Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? • ❑ ❑ ❑
Is all required information readily available, complete and current? • ❑ ❑ ❑
Are all records maintained for 3 years (lab. reg. required 5 years)? ■ ❑ ❑ ❑
Are analytical results consistent with data reported on DMRs? • ❑ ❑ ❑
Is the chain -of -custody complete? • ❑ ❑ ❑
Dates, times and location of sampling •
Name of individual performing the sampling •
Results of analysis and calibration •
Dates of analysis •
Name of person performing analyses •
Transported COCs ■
Are DMRs complete: do they include all permit parameters? • ❑ ❑ ❑
Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ • ❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified ❑ El • El
operator on each shift?
Is the ORC visitation log available and current? • ❑ ❑ ❑
Is the ORC certified at grade equal to or higher than the facility classification? • ❑ ❑ ❑
Is the backup operator certified at one grade less or greater than the facility • ❑ ❑ ❑
classification?
Is a copy of the current NPDES permit available on site? • ❑ ❑ ❑
Facility has copy of previous year's Annual Report on file for review? ❑ ❑ • ❑
Comment: None
Pump Station - Influent Yes No NA NE
Is the pump wet well free of bypass lines or structures? • ❑ ❑ ❑
Is the wet well free of excessive grease? • El El El
Are all pumps present? • El El El
Are all pumps operable? • ❑ ❑ ❑
Are float controls operable? • El El El
Is SCADA telemetry available and operational? • El El El
Is audible and visual alarm available and operational? • El El El
Comment: None
Page# 4
Permit: NC0055255
Inspection Date: 03/23/2022
Owner - Facility: Crown Mobile Home Park
Inspection Type: Compliance Evaluation
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment: None
Equalization Basins
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
Comment: None
Aeration Basins
Mode of operation
Type of aeration system
Is the basin free of dead spots?
Are surface aerators and mixers operational?
Are the diffusers operational?
Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/I)
Yes No NA NE
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
Ext. Air
• ❑ ❑ ❑
• ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: None
Secondary Clarifier Yes No NA NE
Page# 5
Permit: NC0055255
Inspection Date: 03/23/2022
Owner - Facility: Crown Mobile Home Park
Inspection Type: Compliance Evaluation
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment: None
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Comment: None
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: Meter due for calibration 6/30/2022.
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Disinfection - UV Yes No NA NE
Are extra UV bulbs available on site? • ❑ ❑ ❑
Are UV bulbs clean? • ❑ ❑ ❑
Is UV intensity adequate? • ❑ ❑ ❑
Is transmittance at or above designed level? ■ ❑ ❑ ❑
Is there a backup system on site? • ❑ ❑ ❑
Is effluent clear and free of solids? • ❑ ❑ ❑
Page# 6
Permit: NC0055255
Inspection Date: 03/23/2022
Owner - Facility: Crown Mobile Home Park
Inspection Type: Compliance Evaluation
Disinfection - UV Yes No NA NE
Comment: Chlorination/dechlorination backup system.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment: None
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Aerobic Digester Yes No NA NE
Is the capacity adequate? ■ ❑ ❑ ❑
Is the mixing adequate? ■ ❑ ❑ ❑
Is the site free of excessive foaming in the tank? • ❑ El ❑
# Is the odor acceptable? • El El El
# Is tankage available for properly waste sludge? • El ❑ ❑
Comment: None
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ▪ El El El
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: None
Page# 7