April 22, 2022
Yes WI Utilities Exp LLC
Attn: Karen E. Hamilton, Operations Vice President
5050 South Syracuse Street, Ste 1200
Denver, CO 80237
SUBJECT: Compliance Evaluation Inspection & Notice of Deficiency
NOD#: NOD-2022-PC-0052
Woodlake Wastewater Treatment Plant
NPDES Permit Number NC0023299
Guilford County
Dear Ms. Hamilton:
Mr. Ron Boone, of the NC Division of Water Resources (NCDWR), Winston-Salem Regional
Office (WSRO), conducted a compliance evaluation inspection of the Woodlake mobile home
park wastewater treatment plant, on March 23, 2022. Mr. Boone met with Randy Bell, Operator
in Responsible Charge (ORC), and Bradley Flynt, Backup ORC. Their assistance and cooperation
were greatly appreciated. Inspection findings are detailed in the attached Water Compliance
Inspection Report and summarized below.
- The comminutor is not listed in the permit's plant description.
- The aeration header may be too small.
- There is no spare pump on hand for the influent pump station.
- The pump station's telemetry system should be evaluated as it did not call the ORC's cell
phone, as it was purportedly programmed to do, the first several times the telemetry system
was triggered/tested.
- The pump station's audible/visual alarms did not operate properly during the inspection.
This must be repaired within 30 days of reception of this inspection report.
- The flow meter is due for calibration in March, 2022.
- The backup ORC is performing more visitation than he is allowed to do by regulation. This
needs to be adjusted or the backup ORC designated as the ORC.
Please be aware that the Division may take enforcement action against any permittee who fails to
comply with any requirement of their permit. Pursuant to NC General Statute (NCGS) 143-215.6A,
a civil penalty of not more than twenty-five thousand dollars ($25,000.00) may be assessed against
any person who violates or fails to act in accordance with the terms, conditions, or requirements
of any permit issued pursuant to G.S. 143-215.1.
GDE
NORTH C CLI JA '
D. mmmr� .orennt o�.i
North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1450 W. Hanes Mill Rd, Suite 300 I Winston-Salem, North Carolina 27105
336.776.9800
If you have any questions or concerns, please do not hesitate to contact Mr. Boone by phone at
336-776-9690, or by email at ron.boone@ncdenr.gov. Thank you in advance for your time and
attention to this matter.
Sincerely,
[Docufby:<
Signed
-0A, l c�A.aCc"
145B49E225C94EA...
Lon T. Snider, Regional Supervisor
Water Quality Regional Operations Section
Winston-Salem Regional Office
Division of Water Resources, NCDEQ
Attachments:
1. Water Compliance Inspection Report
cc: Laserfiche
Randy Bell, ORC (via email randall.bell@greensboro-nc.gov)
D_E
NORTH CAROLINA
gaparMeM of Environment,/quay
North Carolina Department of Environmental Quality I Division of Water Resources
Winston-Salem Regional Office 1450 W. Hanes Mill Rd, Suite 300 I Raleigh, North Carolina 27105
336.776.9800
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction
1 IN
Code
I 2
IL
NPDES yr/mo/day Inspection Type Inspector Fac
I 3 I NC0023299 111 121 22/03/23 117 1810I 19I S I 2011
Type
21IIIIII
IIIIIIIIIII
IIIIIII
I
IIIIII
IIIIIIIIIII
P6
Inspection
671
Work Days
Facility Self -Monitoring
I 70I
Evaluation Rating
I 711
B1
1
72
QA
I N I
73I
1
I I
Reserved
74 71
I
I I
I
I
I
180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES Dermit Number)
Woodlake WWTP
215 E Sheraton Park Rd
Greensboro NC 27406
Entry Time/Date
09:30AM 22/03/23
Permit Effective Date
17/01/01
Exit Time/Date
10:30AM 22/03/23
Permit Expiration Date
21/09/30
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Randall Keith Bell/ORC/336-373-7514/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Karen E Hamilton,5050 S Syracuse St Denver CO 80237//303-483-7300/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ron Boone DWR/WSRO WQ/336-776-9690/
1- DocuSigned by:
osiaecl Boo.ue, 4/21/2022
‘.._R)nPRnn,F9A ARn
SfgnlJbusalwagement Q A Reviewer Agency/Office/Phone and Fax Numbers Date
l—oti 'T. Sti'd� 4/22/2022
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
31
NPDES yr/mo/day
N C0023299 I11 121 22/03/23
117
Inspection Type
18 [j
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Ron Boone, of the NC Division of Water Resources (DWR), Winston-Salem Regional Office, met with
Randy Bell, Operator in Responsible Charge, and Bradley Flynt, Backup Operator in Responsible
Charge, on 3/23/2022, to perform a compliance evaluation inspection of the Woodlake wastewater
treatment plant. Below is a summary of the inspection findings.
- The comminutor is not listed in the plant description area of the permit.
- The operators stated the aeration header was recently replaced with too small a pipe, which can
make it difficult to maintain sufficient dissolve oxygen levels in the aeration basins. Yes should
evaluate upsizing the aeration header to better maintain dissolved oxygen levels.
- There is no spare pump on hand for the influent pump station.
- The pump station's telemetry system was not calling the ORC's phone as it was purportedly
programmed to do. It did eventually call his phone, near the end of the inspection, which is unusual.
Yes should have the system evaluated to eliminate bugs that may be causing the system not to be
able to call the ORC's phone for some reason.
- The pump station's audible and visual alarms were not operating properly at the time of the
inspection.
- The flow meter is due for calibration in March, 2022.
- The backup ORC (Bradley Flynt) is performing more often than allowed (40%) by regulation. This
needs to be corrected or Mr. Flynt needs to be reassigned as the ORC.
- All reviewed documentation was compliant and all required documentation was readily available,
complete, and current.
Mr. Boone noted no other concerns, deficiencies, or violations.
Page# 2
Permit: NC0023299
Inspection Date: 03/23/2022
Owner - Facility: Woodlake WWTP
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new El El ❑
application?
Is the facility as described in the permit? El • El El
# Are there any special conditions for the permit? El • El El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • El El El
Comment: Permit plant description does not include the comminutor.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
•
• ❑ ❑ ❑
• ❑ • ❑
❑ ❑ • ❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
Comment: According to eDMRs for January through March 2022, Backup operator, Bradley Flynt,
conducted visitation on 65% of the days the ORC was required to visit in January and
February, and on 70% of the days the ORC was required to visit in March, which
significantly exceeds the 40% of visits the Backup ORC is allowed to conduct. The
ORC, Randy Bell, must complete no less than 60 percent of the required visitations.
Page# 3
Permit: NC0023299
Inspection Date: 03/23/2022
Owner - Facility: Woodlake WWTP
Inspection Type: Compliance Evaluation
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Comment: None
Influent Sampling
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is sampling performed according to the permit?
Comment: None
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
❑ ❑ ❑ •
Yes No NA NE
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? • ❑ El El
Is sample collected below all treatment units? • ❑ ❑ ❑
Is proper volume collected? • ❑ ❑ ❑
Is the tubing clean? • ❑ ❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 El El El •
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type El ❑ El •
representative)?
Comment: None
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, El El El
and sampling location)?
Comment: None
Page# 4
Permit: NC0023299
Inspection Date: 03/23/2022
Owner - Facility: Woodlake WWTP
Inspection Type: Compliance Evaluation
Pump Station - Influent Yes No NA NE
Is the pump wet well free of bypass lines or structures? • ❑ ❑ ❑
Is the wet well free of excessive grease? • ❑ ❑ ❑
Are all pumps present? • ❑ ❑ ❑
Are all pumps operable? • ❑ ❑ ❑
Are float controls operable? • ❑ ❑ ❑
Is SCADA telemetry available and operational? ❑ • ❑ ❑
Is audible and visual alarm available and operational? ❑ • ❑ ❑
Comment: No spare pump on hand. Telemetry did NOT call ORC. Audible and visual alarms were
inoperable.
Bar Screens Yes No NA NE
Type of bar screen
a.Manual •
b.Mechanical ❑
Are the bars adequately screening debris? ■ ❑ ❑ ❑
Is the screen free of excessive debris? • ❑ ❑ ❑
Is disposal of screening in compliance? • ❑ ❑ ❑
Is the unit in good condition? • ❑ ❑ ❑
Comment: None
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots? • ❑ ❑ ❑
Are surface aerators and mixers operational? ❑ ❑ • ❑
Are the diffusers operational? • ❑ ❑ ❑
Is the foam the proper color for the treatment process? ■ ❑ ❑ ❑
Does the foam cover less than 25% of the basin's surface? • ❑ ❑ ❑
Is the DO level acceptable? ❑ ❑ ❑ •
Is the DO level acceptable?(1.0 to 3.0 mg/I) ❑ ❑ ❑ •
Comment: Operators stated that the aeration header is too small and it is difficult to maintain
sufficient dissolved oxygen levels in the aeration basins. Yes should consider upsizinq
the aeration header.
Page# 5
Permit: NC0023299
Inspection Date: 03/23/2022
Owner - Facility: Woodlake WWTP
Inspection Type: Compliance Evaluation
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment: None
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Comment: None
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: There is no flow recorder...only a totalizer. Meter calibration is due in 3/22.
Disinfection -Tablet
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Number of tubes in use?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
Page# 6
Permit: NC0023299
Inspection Date: 03/23/2022
Owner - Facility: Woodlake WWTP
Inspection Type: Compliance Evaluation
Disinfection -Tablet Yes No NA NE
Comment: None
De -chlorination
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Are the tablets the proper size and type?
Comment: None
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment: None
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment: None
Yes No NA NE
Tablet
❑ • ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ • ❑
Aerobic Digester Yes No NA NE
Is the capacity adequate? • ❑ ❑ ❑
Is the mixing adequate? • ❑ ❑ ❑
Is the site free of excessive foaming in the tank? • El El El
# Is the odor acceptable? • El El El
# Is tankage available for properly waste sludge? • ❑ El El
Comment: None
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • El El El
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable II El El El
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: None
Page# 7