Dear Mr. Elliot:
NORTH CAROLINA
.E.rmiropirnentert Qualify
April 21, 2022
Subject: Compliance Evaluation Inspection
Cleveland County WTP
NPDES Permit No. NCG590004
Cleveland County
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted
at the subject facility on April 21, 2022, by Ori Tuvia. Your cooperation during the site visit were
much appreciated. Please advise the staff involved with this NPDES Permit by forwarding a copy
of the enclosed report.
As was discussed during the inspection, the bigger lagoon that was converted from being
the freshwater intake lagoon has a bypass pipe. The lagoon must have a free board of at least 2
feet and having the bypass pipe will decrease the size of the lagoon. If you wish to keep the
bypass pipe you will also need to investigate the discharge location of the pipe. It is highly advised
that the facility investigate the lowest point of the lagoon and have clear marking that is 2 feet
below that point (either a gauge or a mark)
The report should be self-explanatory; however, should you have any questions, please
do not hesitate to contact Ori Tuvia at (704) 235-2190, or at ori.tuvia@ncdenr.gov.
Cc: Laserfiche
Sincerely,
DocuSigned by:
for
F161FB69A2D84A3...
W. Corey Basinger
Regional Supervisor
Mooresville Regional Office
Division of Water Resources
North Carolina Department of ErnironmcniaJ Quality I Division of Water Resources
MooresvillektgionaL0ffke I fi;D East Center Avenue. Suite 3a1 I Mooresville. North Carolina 2/NIS
70.4.b63.r69,4
United States Environmental Protection Agency
E PA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction
1 IN I
21IIIIII
Code NPDES yr/mo/day Inspection
2 L 3 I NCG590004 111 121 22/04/19 117
Type
1810I
IIIIIIIIIII
Inspector Fac Type
19I S I 2011
IIIIIIIIIIIIIIIIII I IIIIII
P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
67I1.0 I 70I4 I 71IN I 72 I N I 731 1 74 751
I I 1
I I I I I I 180
l
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Cleveland County WTP
435 Casar-Lawndale Rd
Lawndale NC 28090
Entry Time/Date
11:45AM 22/04/19
Permit Effective Date
19/09/01
Exit Time/Date
12:30PM 22/04/19
Permit Expiration Date
24/07/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Chris Lee Elliott/ORC//
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Christopher Elliott,PO Box 788 Lawndale NC 280900788/ORC/704-538-9033/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and
Ori ATuvia
Signilure(slof Insoector(s) Agency/Office/Phone and Fax Numbers
Date
4/21/2022
oc igne y:
-_ 1- DWR/MRO WQ/704-663-1699/
"
--BB057A2DE017498...
Signature of Ma geR1611tie nWeviewer Agency/Office/Phone and Fax Numbers Date
Andrew Pitn I's u`' H P4411WR/MRO WQ/704-663-1699 Ext.2180/ 4.21.22
F161 FB69A2D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
NPDES yr/mo/day
31 NCG590004 111 121 22/04/19
I17
Inspection Type
18 [j
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page# 2
Permit: NCG590004
Inspection Date: 04/19/2022
Owner - Facility: Cleveland County WTP
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ ❑
application?
Is the facility as described in the permit? • ❑ El El
# Are there any special conditions for the permit? El • El El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment: The permit expires on July 31, 2024.
The facillity has been changed to a general permit. The old permit number was
NC0051918.
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? • ❑ ❑ ❑
Is all required information readily available, complete and current? • ❑ ❑ ❑
Are all records maintained for 3 years (lab. reg. required 5 years)? El El ❑ •
Are analytical results consistent with data reported on DMRs? • El El El
Is the chain -of -custody complete? • El ❑ ❑
Dates, times and location of sampling ■
Name of individual performing the sampling •
Results of analysis and calibration •
Dates of analysis ■
Name of person performing analyses •
Transported COCs ■
Are DMRs complete: do they include all permit parameters? • El El El
Has the facility submitted its annual compliance report to users and DWQ? ❑ El • ❑
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified El El • El
operator on each shift?
Is the ORC visitation log available and current? • El ❑ ❑
Is the ORC certified at grade equal to or higher than the facility classification? • El El El
Is the backup operator certified at one grade less or greater than the facility • ❑ ❑ ❑
classification?
Is a copy of the current NPDES permit available on site? • El El El
Facility has copy of previous year's Annual Report on file for review? El El • El
Comment: DMRs, chain -of -custody's (COCs), and calibration logs from Janaury 2022 through
April 2022 (EDMR's were not reviewed for April of March) were reviewed for the
inspection.
Page# 3
Permit: NCG590004
Inspection Date: 04/19/2022
Owner - Facility: Cleveland County WTP
Inspection Type: Compliance Evaluation
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ • ❑
Comment: The permittee performs on -site analysis of pH and total residual chlorine (TRC) under
field laboratory certification #5381. Meritech has been contracted for any other
sampling data.
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ El • El
Is sample collected below all treatment units? • ❑ El El
Is proper volume collected? • El El El
Is the tubing clean? ❑ El • ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 ■ El El El
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • El El El
representative)?
Comment: New permut, issued on September 1, 2019, the permit changed the requirement for
composite toxcity sample into a gran sample.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable MODE
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: At the time of the inspection the facility appeared to be well maintained. during the visit
the facility was in the process of removing sludge from it's smaller lagoon, in the
process of filling the lagoon and only use the bigger lagoon.
The bigger lagoon was converted from being freshwater intake lagoon and has a
bypass pipe. The lagoon must have a free board of at least 2 feet, and having the
bypass pipe will decrease the size of the lagoon.
Lagoons
Type of lagoons?
# Number of lagoons in operation at time of visit?
Are lagoons operated in?
Yes No NA NE
2
Parallel
Page# 4
Permit: NCG590004
Inspection Date: 04/19/2022
Owner - Facility: Cleveland County WTP
Inspection Type: Compliance Evaluation
Lagoons Yes No NA NE
# Is a re -circulation line present? ❑ ❑ • ❑
Is lagoon free of excessive floating materials? • ❑ ❑ ❑
# Are baffles between ponds or effluent baffles adjustable? • ❑ ❑ ❑
Are dike slopes clear of woody vegetation? • ❑ ❑ ❑
Are weeds controlled around the edge of the lagoon? • ❑ ❑ ❑
Are dikes free of seepage? • ❑ ❑ ❑
Are dikes free of erosion? ■ ❑ ❑ ❑
Are dikes free of burrowing animals? • ❑ ❑ ❑
# Has the sludge blanket in the lagoon (s) been measured periodically in multiple ❑ ❑ • ❑
locations?
# If excessive algae is present, has barley straw been used to help control the growth? El El El
Is the lagoon surface free of weeds? ■ ❑ ❑ ❑
Is the lagoon free of short circuiting? • ❑ ❑ ❑
Comment: Sludge was being pumped for disposal from the small lagoon at the time of the
inspection, in the process of having it closed down. Sludge from the larger lagoon has
not been done since it was converted into a backwash lagoon in the beginning of 2013.
De -chlorination Yes No NA NE
Type of system ? Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ ❑ •
Is storage appropriate for cylinders? • ❑ ❑ ❑
# Is de -chlorination substance stored away from chlorine containers? El El ❑ •
Are the tablets the proper size and type? El El • El
Comment: Permittee was using liquid sodium thiosulfite at the time of the inspection. Process
control sampling is used to adjust dechlorination feed.
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
❑ ❑ • ❑
Yes No NA NE
❑ ❑ • ❑
Page# 5
Permit: NCG590004
Inspection Date: 04/19/2022
Owner - Facility: Cleveland County WTP
Inspection Type: Compliance Evaluation
Flow Measurement - Effluent Yes No NA NE
Comment: Effluent Flow estimates are based on pump run time. A new flow meter was purchased
and installed but was not working since it was installed facility staff should investigate
why it is not working, However the facility is not required to use a flow meter.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment: At the time of the inspection the effluent apperead clear.
Yes No NA NE
• ❑ ❑ ❑