HomeMy WebLinkAboutNCG551149_Inspection_20220428DocuSign Envelope ID: A98D518F-1171-4C8B-BC82-0E5F86A8EAAA
ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR.
Director
Lindsey Dunn
2522 Ferrell Road
Durham, NC 27704
Dear Ms. Dunn:
NORTH CAROLINA
Environmental Quality
April 28, 2022
Subject: Compliance Evaluation Inspection
Single Family Wastewater Treatment System
General NPDES Permit NCG550000
Certificate of Coverage NCG551149
Facility: 2522 Ferrell Road
Durham County
On April 22, 2022, Alys Hannum from the Raleigh Regional Office visited your single-family
residence wastewater treatment system to evaluate compliance with the subject General National
Pollution Discharge Elimination System (NPDES) Permit. Your assistance during the inspection
was greatly appreciated.
Our records indicate the treatment system consists of a septic tank, sub -surface sand filter, tablet
chlorinator with chlorine contact chamber, and discharge pipe.
General NPDES Permit NCG550000 and Certificate of Coverage (COC) NCG551149 authorize
the discharge of domestic wastewater from your treatment system to receiving waters designated
as an unnamed tributary to Panther Creek in the Neuse River Basin, in accordance with the
effluent limits and monitoring requirements established within the General Permit. The following
conditions were noted at your facility:
• Pumping the septic tank: You are required to inspect the septic tank at least yearly to
determine if solids must be removed or if other maintenance is necessary. Septic tanks
should be pumped out every five years or when the solids level is found to be more than
1/3 of the liquid depth in the septic tank compartment, whichever is greater. A pumping
company can check the status periodically and determine when pumping is required.
During the inspection, you provided documentation showing Central Carolina Services
pumped out the septic tank on June 11, 2019.
• Chlorine tablets in the chlorinator: You are reminded that it is required that chlorine
tablets be maintained in the chlorinator to ensure proper disinfection of the discharged
wastewater. Chlorine tablets provide effective disinfection and prevent/limit harmful
NORTH CAROLINA
Department of Environmental Quality
North Carolina Department of Environmental Quality I Division of Water Resources
Raleigh Regional Office 13800 Barrett Drive I Raleigh, North Carolina 27609
919.791.4200
DocuSign Envelope ID: A98D518F-1171-4C8B-BC82-0E5F86A8EAAA
Lindsey Dunn, 2522 Ferrell Road
Certificate of Coverage NCG551149
April 28, 2022
Page 2 of 3
bacteria from discharging to the environment. The product label for these tablets must
indicate the tablets are approved for wastewater use and not for swimming pools. Part 1,
Section D (1) of General NPDES Permit NCG550000 requires the permittee to inspect
the tablet chlorinator weekly to ensure there is an adequate supply of tablets for
continuous and proper operation. The inspector did not observe any chlorine tablets in the
chlorinator. Please ensure the correct type of tablets are used and maintained in the
chlorinator as required by the General NPDES Permit.
• Analyzing the effluent: Part 1. C., Effluent Limitations and Monitoring Requirements,
within General Permit NCG550000 requires a permittee to sample and analyze the
effluent leaving his/her treatment system prior to discharge annually. Parameters to be
sampled and analyzed include Flow, BOD (Biochemical Oxygen Demand), Total
Suspended Solids, Fecal Coliform and Total Residual Chlorine. During the inspection,
you informed the inspector that the effluent has not been monitored within the last 12
months because there has been no flow through the system. If the system does begin to
flow, please collect a representative sample of the effluent, have it analyzed by a
certified commercial laboratory and submit the results to this office. Failure to monitor
the effluent discharge as required is a violation of NPDES General Permit
NCGSS0000.
• Discharge outlet location. The permittee is required to conduct a visual review of the
outfall location at least twice each year (one at the time of sampling) to ensure that no
visible solids or other obvious evidence of system malfunctioning is observed. Any
visible signs of a malfunctioning system shall be documented and steps taken to correct
the problem. The discharge pipe was visible and accessible the day of the inspection.
Please continue to ensure the outlet is always visible/maintained and cleared of
vegetation, soil and leaves.
Division records indicate the required annual fee ($60 per year) due September 2, 2021, for the
period ending August 31, 2022, has been paid. There are no overdue fees for the subject COC.
Please continue to periodically inspect the wastewater treatment system to ensure the treatment
components are always maintained and in good operating order. You are also reminded to
maintain all monitoring data and associated maintenance records onsite for a minimum of three
years for inspection.
NORTH CAROLINAD_E
Department of Environmental Quality
North Carolina Department of Environmental Quality I Division of Water Resources
Raleigh Regional Office 13800 Barrett Drive I Raleigh, North Carolina 27609
919.791.4200
DocuSign Envelope ID: A98D518F-1171-4C8B-BC82-0E5F86A8EAAA
Lindsey Dunn, 2522 Ferrell Road
Certificate of Coverage NCG551149
April 28, 2022
Page 3 of 3
If you have questions or comments about this, please contact Alys Hannum at
alys.hannum@ncdenr.gov, or by phone at 919-791-4255.
Sincerely,
DocuSigned by:
FhttALSSA, f. Al1.a tAlta
B2916E6AB32144F...
Vanessa E. Manuel, Assistant Regional Supervisor
Water Quality Regional Operations Section
Raleigh Regional Office
Division of Water Resources, NCDEQ
Attachment(s): EPA Water Compliance Inspection Report
cc: RRO/SWP Files
Laserfiche
GD_E
NORTH CofEn NA
Deparbnent iR of Environmental Quality
North Carolina Department of Environmental Quality I Division of Water Resources
Raleigh Regional Office 13800 Barrett Drive I Raleigh, North Carolina 27609
919.791.4200
DocuSign Envelope ID: A98D518F-1171-4C8B-BC82-0E5F86A8EAAA
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction
1
21IIIIII
671
Code
IN I 2 IL I
NPDES yr/mo/day Inspection
3 I NCG551149 111 121 22/04/22 117
Type
1810I
IIIIIIIIIII
Inspector Fac Type
19I S I 2011
IIIIIIIIIII IIIIIII I IIIIII
P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
I 70I4 I 711 1 72 I N I 73I 1 74 71
I I
I I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES oermit Number)
2522 Ferrell Road
2522 Ferrell Rd
Durham NC 27704
Entry Time/Date
10:OOAM 22/04/22
Permit Effective Date
21/12/28
Exit Time/Date
10:30AM 22/04/22
Permit Expiration Date
25/10/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Lindsey C Dunn,2522 Ferrell Rd Durham NC 27704//919-909-6889/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Operations & Maintenar Self -Monitoring Progran
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s)
Alys K Hannum
of Inspector(s) Agency/Office/Phone and Fax Numbers
,-Docusignedby: DWR/RRO WQ/919 791-4255/
a.uwo+-sx.
"-4C22170C5AA04F3...
Date
4/25/2022
Signature
of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
IDocuSigned by:
ou,SSa f. ll.aln t , 4/26/2022
B2916E6AB32144F...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
DocuSign Envelope ID: A98D518F-1171-4C8B-BC82-0E5F86A8EAAA
NPDES yr/mo/day
31 NCG551149 111 121 22/04/22
I17
Inspection Type
18LI
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page# 2
DocuSign Envelope ID: A98D518F-1171-4C8B-BC82-0E5F86A8EAAA
Permit: NCG551149
Inspection Date: 04/22/2022
Owner -Facility: 2522 Ferrell Road
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable El El El
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Septic Tank
(If pumps are used) Is an audible and visual alarm operational?
Is septic tank pumped on a schedule?
Are pumps or syphons operating properly?
Are high and low water alarms operating properly?
Comment:
Sand Filters (Low rate)
(If pumps are used) Is an audible and visible alarm Present and operational?
Is the distribution box level and watertight?
Is sand filter free of ponding?
Is the sand filter effluent re -circulated at a valid ratio?
# Is the sand filter surface free of algae or excessive vegetation?
# Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1)
Comment:
Disinfection -Tablet
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Number of tubes in use?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Comment: Tablet chlorinator did not have any tablets at the time of inspection.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Yes No NA NE
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Yes No NA NE
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
1
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 3
DocuSign Envelope ID: A98D518F-1171-4C8B-BC82-0E5F86A8EAAA
Permit: NCG551149
Inspection Date: 04/22/2022
Owner -Facility: 2522 Ferrell Road
Inspection Type: Compliance Evaluation
Effluent Sampling
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type
representative)?
Comment: System has not been sampled recently due to a lack of flow.
Yes No NA NE
❑ • ❑ ❑
❑ • ❑ ❑
Page# 4