April 21, 2022
GRADY FULCHER – PROPERTY MANAGER
GENESIS CONDOMINIUM OWNERS ASSOCIATION, INC.
POST OFFICE BOX 1154
ATLANTIC BEACH, NORTH CAROLINA 28512
Subject: Application No. WQ0006863
Additional Information Request
Genesis Condominiums WWTP
High-Rate Infiltration System
Carteret County
Dear Mr. Fulcher:
Division of Water Resources’ Central and Regional staff has reviewed the application package
received September 17, 2021 and subsequent response package received February 28, 2022. However,
additional information is required before the review may be completed. Please address the item on the
attached page no later than the close of business on May 23, 2022.
Please be aware that you are responsible for meeting all requirements set forth in North Carolina
rules and regulations. Any oversights that occurred in the review of the subject application package are
still the Applicant’s responsibility. In addition, any omissions made in responding to the outstanding item
in Section A, or failure to provide the additional information on or before the above requested date may
result in your application being returned as incomplete pursuant to 15A NCAC 02T .0107(e)(2).
Please reference the subject application number when providing the requested information. All
revised and/or additional documentation shall be signed, sealed and dated (where needed), with an
electronic response submitted to my attention at: https://edocs.deq.nc.gov/Forms/NonDischarge-Branch-
Submittal-Form-Ver2.
If you have any questions regarding this request, please contact me at (919) 707-3660 or
Lauren.Plummer@ncdenr.gov. Thank you for your cooperation.
Sincerely,
Lauren Raup-Plummer, Engineer III
Division of Water Resources
cc: Wilmington Regional Office, Water Quality Regional Operations Section (Electronic Copy)
John F. Phillips, PE – Diehl & Phillips, P.A. (Electronic Copy)
Laserfiche File (Electronic Copy)
Mr. Grady Fulcher
April 21, 2022
Page 2 of 2
A. Existing Permit:
1. During communications with Mr. Don O’Mara regarding the now-resolved air mixing question, it
was determined that the ultraviolet (UV) disinfection system was modified from the permitted two
62 gallon per minute (GPM) disinfection units to three 40 GPM UV disinfection units. This change
is a minor modification, and the Non-Discharge Branch does not have any records of this
modification being submitted for review. Please provide information regarding the UV disinfection
system including equipment type, treatment configuration, calculations, operation and maintenance
requirements. Please also provide information for any additional or modified piping or
appurtenances that were required for installation of the modified system. Please submit application
form HRIS 06-16, signed and sealed engineering documents pursuant to 15A NCAC 02T .0704.
Our understanding is that this equipment has already been installed, as such please also provide the
date it was installed, an executed engineering certification, and the updated Operation and
Maintenance (O&M) plan.