HomeMy WebLinkAboutNC0024911_Compliance Evaluation Inspection_20220420DocuSign Envelope ID: 7B3936E7-81 E3-46AF-BBD7-01 D874F3C9AA
ROY COOPER
Governor
ELIZABETH S. RISER
Secretary
RICHARD E. ROGERS, JR.
Director
NORTH CAROLINA
Environmental Quality
SENT VIA ELECTRONIC MAIL ONLY: NO HARD COPY WILL BE MAILED.
April 20, 2022
Thomas Hartye P.E.
Metropolitan Sewerage District (MSD)
E-mail: THartye@msdbc.org
SUBJECT: Compliance Inspection Report
French Broad River WRF
NPDES WW Permit No. NC0024911
Buncombe County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the French Broad River WRF
on 4/14/2022. This inspection was conducted to verify that the facility is operating in compliance with
the conditions and limitations specified in NPDES WW Permit No. NC0024911. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled ''Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact me with the Water
Quality Regional Operations Section in the Asheville Regional Office at 828-296-4500 or via email at
tim.heim@ncdenr.gov.
ATTACHMENTS
Ec: LF, Roger Edwards, ORC- MSD
Sincerely,
DocuSigned by:
fki4AO&Al tkt,iI44
08281105A3CA418..
Tim Heim, P.E., Environmental Engineer
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
North Carolina Department of Environmental Queley I olvtslon of Water Resources
Asheville Regional Office 120900S. Highway 70 I Swannanoa, Noah Carolina 28778
828.290 4500
DocuSign Envelope ID: 7B3936E7-81 E3-46AF-BBD7-01 D874F3C9AA
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection
1 IN I 2 LI 3 I NC0024911 111 121 22/04/14 117
Type
1810I
IIIIIIIIIII
Inspector Fac Type
19I S I 2011
21IIIIII IIIIIIIIIIIIIIIIII I IIIIII
P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
671 I 70I I 711 172 I N I 731 1 74 71
I I
I I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
French Broad River WRF
NC Hwy 251
Asheville NC 28814
Entry Time/Date
02:OOPM 22/04/14
Permit Effective Date
18/10/01
Exit Time/Date
04:30PM 22/04/14
Permit Expiration Date
22/12/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Roger C Edwards/ORC/828-225-8224/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Roger C Edwards,244 Baird Cove Rd Asheville NC 28804//828-225-8224/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Operations & Maintenar Records/Reports Self -Monitoring Progran
Facility Site Review
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Timothy H Heim DWR/ARO WQ/828-296-4665/
4/20/2022
rDocuSignea by:
� ttMbTUA N m
`Signature
of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
oar
D SB edby 4/20/2022
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
DocuSign Envelope ID: 7B3936E7-81 E3-46AF-BBD7-01 D874F3C9AA
31
NPDES yr/mo/day
N C 0024911 111 121 22/04/14
I17
Inspection Type
18LI
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Tim Heim of the Asheville Regional Office performed a Compliance Inspection of the Facility on April
14, 2022. Roger Edwards (ORC) was present and assisted with the inspection. The facility appeared
well operated at the time of the inspection, and in compliance with Permit NC0029411.
The following additional items were noted at the time of the inspection:
The new high rate primary clarifier is operational and undergoing startup commissioning
The facility is evaluating future upgrades to biological treatment and other components. Consider
discussions with ARO regarding maintaining compliance during construction of these upgrades.
Page# 2
DocuSign Envelope ID: 7B3936E7-81 E3-46AF-BBD7-01 D874F3C9AA
Permit: NC0024911
Inspection Date: 04/14/2022
Owner - Facility: French Broad River WRF
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable II El El El
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new El El ❑
application?
Is the facility as described in the permit? • El El El
# Are there any special conditions for the permit? El • El El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment:
Pump Station - Influent
Is the pump wet well free of bypass lines or structures?
Is the wet well free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Bar Screens Yes No NA NE
Type of bar screen
a.Manual ❑
b.Mechanical •
Are the bars adequately screening debris? • ❑ ❑ ❑
Is the screen free of excessive debris? • ❑ ❑ ❑
Is disposal of screening in compliance? • ❑ ❑ ❑
Is the unit in good condition? • ❑ ❑ ❑
Comment:
Page# 3
DocuSign Envelope ID: 7B3936E7-81 E3-46AF-BBD7-01 D874F3C9AA
Permit: NC0024911
Inspection Date: 04/14/2022
Owner - Facility: French Broad River WRF
Inspection Type: Compliance Evaluation
Grit Removal Yes No NA NE
Type of grit removal
a.Manual El
b.Mechanical •
Is the grit free of excessive organic matter? • El El El
Is the grit free of excessive odor? • El El El
# Is disposal of grit in compliance? • ❑ ❑ ❑
Comment:
Primary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • ❑ El El
Is the site free of excessive buildup of solids in center well of circular clarifier? El El • El
Are weirs level? • El El El
Is the site free of weir blockage? • El El El
Is the site free of evidence of short-circuiting? • ❑ ❑ ❑
Is scum removal adequate? • El El El
Is the site free of excessive floating sludge? • El El El
Is the drive unit operational? El El • El
Is the sludge blanket level acceptable? El ❑ • El
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) El El • El
Comment: Rapid ActiFlow settling type primary clarifier.
Rotating Biological Contactor
Is the unit free of excessive sloughing of growth?
Is the unit operational?
Are media panels in good condition?
Comment:
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
❑ ❑ • ❑
▪ ❑ ❑ ❑
Page# 4
DocuSign Envelope ID: 7B3936E7-81 E3-46AF-BBD7-01 D874F3C9AA
Permit: NC0024911
Inspection Date: 04/14/2022
Owner - Facility: French Broad River WRF
Inspection Type: Compliance Evaluation
Secondary Clarifier Yes No NA NE
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment: Rectangular clarifiers.
• ❑ ❑ ❑
• ❑ ❑ ❑
Filtration (High Rate Tertiary) Yes No NA NE
Type of operation: Cross flow
Is the filter media present? • ❑ ❑ El
Is the filter surface free of clogging? • El El El
Is the filter free of growth? • El ❑ ❑
Is the air scour operational? El El • El
Is the scouring acceptable? El El • ❑
Is the clear well free of excessive solids and filter media? • El El El
Comment: Textile base disk filters.
Disinfection -Liquid
Is there adequate reserve supply of disinfectant?
(Sodium Hypochlorite) Is pump feed system operational?
Is bulk storage tank containment area adequate? (free of leaks/open drains)
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
• ❑ ❑ ❑
❑ ❑ ❑ •
De -chlorination Yes No NA NE
Type of system ? Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)? • El El El
Is storage appropriate for cylinders? • El El El
# Is de -chlorination substance stored away from chlorine containers? • El El El
Page# 5
DocuSign Envelope ID: 7B3936E7-81 E3-46AF-BBD7-01 D874F3C9AA
Permit: NC0024911
Inspection Date: 04/14/2022
Owner - Facility: French Broad River WRF
Inspection Type: Compliance Evaluation
De -chlorination Yes No NA NE
Comment:
Are the tablets the proper size and type?
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment:
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
Comment:
• ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 6