HomeMy WebLinkAboutNC0021857_Wasteload Allocation_19910318NPDES DOCUMENT SCANNING COVER SHEET
NC0021857
Newland WWTP
NPDES Permit:
Document Type:
Permit Issuance
(Wasteload
Allocation `'
Authorization to Construct (AtC)
Permit Modification
Complete File - Historical
Engineering Alternatives (EAA)
Correspondence
Owner Name Change
201 Facilities Plan
Instream Assessment (67b)
Speculative Limits
Environmental Assessment (EA)
Document Date:
March 18, 1991
Mato; document printed on remise paper - ignore any
content on the rewertse side
NPDES WASTE LOAD ALLOCATION
PERMIT NO.: NC0021857
PERM]. lEE NAME:
Town of Newland / Newland WWTP
Facility Status: Existing
Permit Status: Renewal
Major Minor
Pipe No.: 001
Design Capacity: 0.160 MGD
Domestic (% of Flow): 100 %
Industrial (% of Flow):
Comments:
RECEIVING STREAM: North Toe River
Class: WS-III-Trout
Sub -Basin: 04-03-06
Reference USGS Quad: C1 1SW, Newland (please attach)
County: Avery
Regional Office: A5t-1g\1 l c_.c. RAG & or.1►OL oFF0.E
Previous Exp. Date: 8/31/91 Treatment Plant Class: II
Classification changes within three miles:
No change within 3 miles.
Requested by: Jeffrey A. Curka Date: 12/27/90
Prepared by: . '-2, lavute Date: 3//r(7/
Reviewed by. I, Date: '5 1 t/ 9 1
13ot.. 94.ri _1z-w 3 /g i
(1)
Modeler
Date Rec.
#
SMN
IZ1Z$(50
yG�9
Drainage Area (mil ) /0 Avg. Streamflow (cfs): 2z
7Q10 (cfs) .3.3 Winter 7Q 10 (cfs) `f. 30Q2 (cfs)
Toxicity Limits: IWC % Acute/Chronic
Instream Monitoring:
Parameters
Upstream Location
Downstream N Location
Effluent
Characteristics
Summer
Winter
BOD5 (mg/1)
30
3 c
NH3-N (mg/1)
! 1(A-7-)
z ` (,47--1
D.O. (mg/1)
4, ✓
ri•:
TSS (mg/1)
3 0
; 0
F. Col. (/100 ml)
Z D o
Z o v
pH (SU)
6 — 7
G _ q
‹f,per.
Z8 vi/.e
zi Lf: L
' LOTTED
Comments:
-1-
Facility Name
NPDES No.
Type of Waste
Facility Status
Permit Status
Receiving Stream
Stream Classification:
Subbasin
County
Regional Office
Requestor
Date of Request
Topo Quad
FACT SHEET FOR WASTELOAD ALLOCATIONS
NEWLAND WWTP
NC0021857
100% DOMESTIC
EXISTING
RENEWAL
NORTH TOE RIVER
WSIII TROUT
040306
AVERY
ARO
CURKA
12/28/90
C11SW
Request
Stream Characteristics:
USGS # 03.4619.1050
Drainage Area: 10 sq. mi
Summer 7Q10:
Winter 7Q10:
Average Flow:
30Q2:
Wasteload Allocation Summary
(approach taken, correspondence with region, EPA, etc.)
3.3 cfs
4.8 cfs
22 cfs
cfs
# 5979
RECEIVED
Water Quality Section
FEB -5 1991
Asheville Regional Of**
Asheville, North Carolina
9/85
Special Scheduled Requirements and additional comments from Reviewers:
T!{� TPwN OF NEwL.'NP 0/..5 &e uE-5-r-r7 4MMONi.4 L!frh75
IN L.1Eu Tbxicv Ty. Atakirrakul'- Drf /A/P( IerE.s
n4 7" HE M ei Ltr c4A/ /is/Lv "16ET MOPS& .44ii M'/»
1-/t4/7 DP I/ d //
Recommended by
Reviewed by
Instream Assessment:
Regional S
Permits & En
RETURN TO TECHNICAL SERVICES BY:
MAR 01 1991
Date• 1/30/91
Date: I/31 k /
Date: -3/6/ 9 /
Date: .3r/ L(i(
-2-
CONVENTIONAL PARAMETERS
Existing Limits
Monthly Average
Summer/Winter
Wasteflow (MGD): 0.160
BOD5 (mg/1): 30
NH3N (mg/1): NR
DO (mg/1): NR
TSS (mg/1): 30
Fecal Coliform (/100 ml): 1000
pH (SU): 6-9
Res. chlorine (ug/1): 29
TP (mg/1):
TN (mg/1):
Toxicity:
Recommended Limits
Daily Maximum
Monthly Average Daily Maximum
Summer Winter
Wasteflow (MGD): 0.160 0.160
BOD5 (mg/1): 30 30
NH3N (mg/1): 11(AT) 26(AT)*
DO (mg/1): NR NR
TSS (mg/1): 30 30
Fecal Coliform (/100 ml): 200 200
pH (SU): 6-9 6-9
Res. chlorine (ug/1): 28 28
TP (mg/1) :
TN (mg/1) :
Toxicity: CHRONIC/CERIODAPHNIA/QRTRLY @ 7%*
INSTREAM MONITORING REQUIRMENTS:
Upstream: N
Donwstream: N
Location:
Location:
Limits Changes Due To: Parameter(s) Affected
Instream Data
Ammonia Toxicity
Chlorine
Nutrient Sensitive Waters
HQW
New 7Q10 flow data
Special Modeling Studies
New facility information
NH3 Choice Option
Existing 29 ug/1 changed to 28 ug/1
Other **Facility should be given option of ammonia limits or chronic
toxicity requirement at 7%**
(explanation of any modifications to past modeling analysis
including new flows, rates, field data, interacting discharges, etc.)
/off 3 el/D/C-E 0/776/1
10/89 �(� �/ ',
Facilit Name `--�c1`-"Yt ' �w"l� v� , Permit # 4����857
y / �%
CHRONIC TOXICITY TESTING REQUIREMENT (QRTRLY)
The effluent discharge shall at no time exhibit chronic toxicity in any two consecutive toxicity tests,
using test procedures outlined in:
1.) The North Carolina Ceriodaphnia chronic effluent bioassay procedure (North Carolina Chronic
Bioassay Procedure - Revised *September 1989) or subsequent versions.
The effluent concentration at which there may be no observable inhibition of reproduction or
significant mortality is 7 % (defined as treatment two in the North Carolina procedure
document). The permit holder shall perform quarterly monitoring using this procedure to establish
compliance with the permit condition. The first test will be performed after thirty days from
issuance of this permit during the months of Ail 6C7 . Effluent
sampling for this testing shall be performed at the NPDES permitted final effluent discharge below
all treatment processes.
All toxicity testing results required as part of this permit condition will be entered on the Effluent
Discharge Monitoring Form (MR-1) for the month in which it was performed, using the parameter
code TGP3B. Additionally, DEM Form AT-1 (original) is to be sent to the following address:
Attention: Environmental Sciences Branch
North Carolina Division of
Environmental Management
P.O. Box 27687
Raleigh, N.C. 27611
Test data shall be complete and accurate and include all supporting chemical/physical measurements
performed in association with the toxicity tests, as well as all dose/response data. Total residual
chlorine of the effluent toxicity sample must be measured and reported if chlorine is employed for
disinfection of the waste stream.
Should any single quarterly monitoring indicate a failure to meet specified limits, then monthly
monitoring will begin immediately until such time that a single test is passed. Upon passing, this
monthly test requirement will revert to quarterly in the months specified above.
Should any test data from this monitoring requirement or tests performed by the North Carolina
Division of Environmental Management indicate potential impacts to the receiving stream, this
permit may be re -opened and modified to include alternate monitoring requirements or limits.
NO1E: Failure to achieve test conditions as specified in the cited document, such as minimum
control organism survival and appropriate environmental controls, shall constitute an invalid test
and will require immediate retesting(within 30 days of initial monitoring event). Failure to submit
suitable test results will constitute noncompliance with monitoring requirements.
7Q10 3.3 cfs
Permited Flow a• /60 MGD
IWC% ?
Basin & Sub -basin Ftlio
Receiving Stream A%a��ro�.✓ /� •�
County 4futeit. tetefi /y
**Chronic Toxicity (Ceriodaphnia) P/F at r% %, 44JdPR ? oer , See Part , Condition .
Recommended by:
) s
'LA,
0, 515
wtAirf'
CP44:-. 6. 166 14(.0
0,4
CP/1-3 Za_t.6
?pea
wive. y,tc.4
4.) 9 f 50C-_
1,jA-,
6
- 90 /
/.)15 -741 e
7' f
3,
7 2,,
newland wwtp
CHLORINE ANALYSIS
7Q10: 3.3000 cfs
CL2 Effl. Conc: 0.2000 mg/1
AL (17/19 ug/1): 17.0000 ug/1
Upstream CL2 Conc.: 0.0000 ug/1
Design Flow: 0.1600 MGD
Predicted CL2 Downstream: 13.98 ug/1
0.013979 mg/1
CL2 Limit: 243.2096 ug/1
0.243209 mg/1
newland wwtp
AMMONIA ANALYSIS
7Q10: 3.3000 cfs
NH3 Effl. Conc: 2.9000 mg/1
AL (1/1.8 mg/1) : 1000.00 ug/1
Upstream NH3 Conc.: 220.0000 ug/1
Design Flow: 0.1600 MGD
Predicted NH3 Downstream: 407.33 ug/1
0.407328 mg/1
NH3 Limit: 11379.03 ug/1
11.37903 mg/1
AMMONIA ANALYSIS (WINTER)
7Q10: 3.8000 cfs
NH3 Effl. Conc: 2.9000 mg/1
AL (1/1.8 mg/1): 1800.00 ug/1
Upstream NH3 Conc.: 220.0000 ug/1
Design Flow: 0.1600 MGD
Predicted NH3 Downstream: 384.19 ug/1
0.384189 mg/1
NH3 Limit: 26009.67 ug/1
26.00967 mg/1
newland wwtp
AMMONIA ANALYSIS
7Q10: 3.3000 cfs
NH3 Effl. Conc: 2.9000 mg/1
AL (1/1.8 mg/1) : 1000.00 ug/1
Upstream NH3 Conc.: 220.0000 ug/1
Design Flow: 0.1600 MGD
Predicted NH3 Downstream: 407.33 ug/1
0.407328 mg/1
NH3 Limit: 11379.03 ug/1
11.37903 mg/1
AMMONIA ANALYSIS (WINTER)
7Q10: 3.8000 cfs
NH3 Effl. Conc: 2.9000 mg/1
AL (1/1.8 mg/1): 1800.00 ug/1
Upstream NH3 Conc.: 220.0000 ug/1
Design Flow: 0.1600 MGD
Predicted NH3 Downstream: 384.19 ug/1
0.384189 mg/1
NH3 Limit: 26009.67 ug/1
26.00967 mg/1