HomeMy WebLinkAboutWQ0002127_CEIARR_20220413
SENT VIA ELECTRONIC COPY ONLY: NO HARD COPY WILL BE MAILED
April 13, 2022
Eli Self
Email: eself@morgantonnc.gov
City of Morganton
SUBJECT: Compliance Inspection Report
Annual Report Review 2021
City of Morganton DCAR
Non-discharge Permit No. WQ0002127
Burke County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the City of Morganton’s DCAR
Annual Report on 4/13/2022. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in Non-discharge Permit No. WQ0002127. The
findings and comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact me at 828-296-4686 or via email at
mikal.willmer@ncdenr.gov.
Sincerely,
Mikal Willmer, Environmental Specialist II
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS: Inspection
Ec: LF
DocuSign Envelope ID: BB256E1E-0B96-42CA-ACA7-9078E4892855
Compliance Inspection Report
Permit:WQ0002127 Effective:05/18/21 Expiration:02/28/23 Owner :City of Morganton
SOC:
Contact Person:
Region:
County:
Directions to Facility:
Burke
Asheville
Eli Self
Effective:Expiration:Facility:City of Morganton DCAR
1000 Vine Arden Rd
Morganton NC 28655
Title:Phone:828-438-5378ORC
I-40 to Exit 105 to Hwy. 18N. Turn rt. on Hwy. 70 By-Pass, turn left @ light to Hwy. 70 W. Turn right on Kirksey Dr. Go approx. 1.25
miles to Vine Arden Road on right.
Secondary ORC(s):
Phone:Certification:Primary ORC:
System Classifications:
On-Site Representative(s):
Related Permits:
NC0026573 City of Morganton - Catawba River Pollution Control Facility
Secondary Inspector(s):
Primary Inspector:
Inspection Date:Exit Time:Entry Time:
Phone:
04/13/2022 09:00AM 09:56AM
Mikal Willmer 828-296-4686
Facility Status:
Permit Inspection Type:
Reason for Inspection:Inspection Type:
Not CompliantCompliant
Routine
Distribution of Residual Solids (503)
Annual Report Review
Question Areas:
Miscellaneous Questions Record Keeping Treatment
Pathogen and Vector Attraction
(See attachment summary)
Page 1 of 4
DocuSign Envelope ID: BB256E1E-0B96-42CA-ACA7-9078E4892855
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0002127
04/13/2022 Annual Report Review
City of Morganton
Routine
Inspection Summary:
Mikal Willmer, with the Asheville Regional Office, conducted a review of the City of Morganton’s 2021 DCAR Annual Report
on April 13, 2022. This review was conducted to determine whether the facility processed and monitored all residuals in
compliance with Permit No. WQ0002127.
The City distributed approximately 717 metric dry tons of Class A Compost to local businesses and individuals in 2021. All
customers were provided with a utilization agreement listing the requirements for proper use of the residuals. Noncompliant
piles from 2018 and 2019 were disposed of in the Foothills Landfill.
Pathogen Reduction (PR): PR is met via fecal coliform density reduction below 1,000 MPN/g and through PFRP (Option E)
composting. The statically aerated piles appeared to exceed 55°C for at least three consecutive days. The City is currently
collecting five fecal samples over a two-week period as the final product pile is being constructed. It was noted during the
review that a couple of the reported fecal coliform results are reported as a greater than values. It is advisable the permittee
avoid relying on these values for permit compliance if multiple greater than values are reported during a single sampling event
as the actual coliform density cannot be determined.
Vector Attraction Reduction (VAR): VAR is met via the 14-day aerobic process (Option 5). All constructed piles appeared to
exceed 40°C for at least 14 consecutive days and had an average temperature that exceeded 45°C.
Non-Hazardous Waste Characterization: Required once per permit cycle. Completed in June of 2018.
Metals, Nutrients & Pollutants of Concern: Values were below the monthly and ceiling concentration limits for Class A
products. Continue to monitor Zinc levels as it was approximately half the monthly limit in 2021. Nutrients and metals were
sampled quarterly.
PAN & SAR: PAN balances are being calculated and maintained quarterly. SAR values for 2021 are below 10.
Permit Renewal Reminder: As a reminder, the permit expires February 28, 2023, and the permit renewal application is due
no later than September 1, 2022.
Page 2 of 4
DocuSign Envelope ID: BB256E1E-0B96-42CA-ACA7-9078E4892855
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0002127
04/13/2022 Annual Report Review
City of Morganton
Routine
Type Yes No NA NE
Land Application
Distribution and Marketing
Record Keeping Yes No NA NE
Is GW monitoring being conducted, if required?
Are GW samples from all MWs sampled for all required parameters?
Are there any GW quality violations?
Is GW-59A certification form completed for facility?
Is a copy of current permit on-site?
Are current metals and nutrient analysis available?
Are nutrient and metal loading calculating most limiting parameters?
a. TCLP analysis?
b. SSFA (Standard Soil Fertility Analysis)?
Are PAN balances being maintained?
Are PAN balances within permit limits?
Has land application equipment been calibrated?
Are there pH records for alkaline stabilization?
Are there pH records for the land application site?
Are nutrient/crop removal practices in place?
Do lab sheets support data reported on Residual Analysis Summary?
Are hauling records available?
Are hauling records maintained and up-to-date?
# Has permittee been free of public complaints in last 12 months?
Has application occurred during Seasonal Restriction window?
Class A product supplied to varying customer base and used on various crops.Comment:
Pathogen and Vector Attraction Yes No NA NE
a. Fecal coliform SM 9221 E (Class A or B)
Class A, all test must be <1000 MPN/dry gram
Geometric mean of 7 samples per monitoring period for class B<2.0*10E6 CFU/dry gram
Fecal coliform SM 9222 D (Class B only)
Geometric mean of 7 samples per monitoring period for class B<2.0*10E6 CFU/dry gram
b. pH records for alkaline stabilization (Class A)
c. pH records for alkaline stabilization (Class B)
Temperature corrected
d. Salmonella (Class A, all test must be < 3MPN/4 gram day)
Page 3 of 4
DocuSign Envelope ID: BB256E1E-0B96-42CA-ACA7-9078E4892855
Inspection Date:
Permit:
Inspection Type :
Owner - Facility:
Reason for Visit:
WQ0002127
04/13/2022 Annual Report Review
City of Morganton
Routine
e. Time/Temp on:
Digester (MCRT)
Compost
Class A lime stabilization
f. Volatile Solids Calculations
g. Bench-top Aerobic/Anaerobic digestion results
Comment:
Treatment Yes No NA NE
Check all that apply
Aerobic Digestion
Anaerobic Digestion
Alkaline Pasteurization (Class A)
Alkaline Stabilization (Class B)
Compost
Drying Beds
Other
See summary for details.Comment:
Page 4 of 4
DocuSign Envelope ID: BB256E1E-0B96-42CA-ACA7-9078E4892855