April 11, 2022
SUBJECT: Compliance Inspection Report
Carolina Pines Estates WWTP
NPDES WW Permit No. NC0056618
Craven County
Dear Mr. Hough:
The North Carolina Division of Water Resources conducted an inspection of the Carolina Pines Estates
WWTP on 3/11/2022. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in NPDES WW Permit No. NC0056618. The
findings and comments noted during this inspection are provided in the enclosed copy of the inspection
report entitled "Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
(ford Css.b. D.p rt..nt d fu.4m.o tal Qadly I DkNm.r MW.< Ie.amco
%Winton PrOaral Mar 94310.41io9tm Square WM I Wanks en. 14.6 Cuo4u Rl9
79.4WbW
If you should have any questions, please do not hesitate to contact Sarah Toppen with the Water
Quality Regional Operations Section in the Washington Regional Office at 252-946-6481 or via email at
Sarah.Toppen@ncdenr.gov.
ATTACHMENTS
Cc: Laserfiche
Sincerely,
Sarah Toppen, Environmental Specialist II
Water Quality Regional Operations Section
Washington Regional Office
Division of Water Resources, NCDEQ
ua.r. V.su otc.w+ommet.+O+ny I DrNn u(Wo1a hwm
tutintanleraNIONce I tiay. o<,3eic..uIu I wa►ryiw.wuoernarem
x7iwee4a1
United States Environmental Protection Agency
E PA Washington, D.C. 20480
Water Compliance Inspection Report
Fonn Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection
1 IN I 2 IF i 3 I NC0056618 111 121 22/03/11 117
Type
181 I
IIIIIIIIIII
Inspector Fac Type
19I G 1 201 I
21IIIIII IIIIIIIIIII IIIIIII I IIIIII
p6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA
671I 70Li 71 I uI 72 I N I
Reserved
731 I 174 79
I I I
111180
I 111180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Carolina Pines Estates WWTP
141 Blackheath Dr
New Bern NC 28560
Entry Time/Date
11:20AM 22/03/11
Permit Effective Date
18/07/01
Exit lime/Date
12:30PM 22/03/11
Permit Expiration Date
23/06/30
Name(s) of Onslte Representative(s)(ntles(s)/Phone and Fax Number(s)
///
Mathew Golden/ORC/252-659-0517/
Other Facility Data
Name, Address of Responsible OfflclalMtle/Phone and Fax Number
Contacted
Arthur Hough,PO Box 240908 Charlotte NC 282240908//800-348-2383/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling Dispo$. Facility Site Review
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Sarah AToppen DWR/WARO WQ/252-946-6481/ 4/1'1,� 0202-1
%SONO ,k dcp:oki
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
NPDES yr/mo/day
31 NC0056618 I11 121 22_/03/11
Inspection Type
I17 18L j
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On Friday, March 11, 2022, Sarah Toppen with NCDWR met on -site with Matthew Golden, Operator
with Carolina Water.
The visual alarm was working but the audible alarm was not functioning at the equalization basin.
Both audible and visual alarms should be working.
The facility was in compliance the day of the inspection. Refer to the inspection report for more
details.
Page# 2
Permit: NC0056818 Owner - Facility: Carolina Pines Estates WWTP
Inspection Date: 03/11/2022 Inspection Typo: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • 0 0 ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable • 0 0 0
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The outside of the metal tanks were winded and painted the end of 2021.
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Equalization Basins
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
Yes No NA NE
•
0
• ❑ ❑ ❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
III ❑ ❑ ❑
▪ ❑ ❑ ❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ■ ❑ ❑
• ❑ ❑ ❑
Comment: The visual alarm was working the day of Inspection but the audible alarm was not
operable.
Aerobic Digester Yes No NA NE
Is the capacity adequate? • 0 ❑ 0
Is the mixing adequate? • 0 0 ❑
Is the site free of excessive foaming in the tank? • 0 0 0
# Is the odor acceptable? • 0 0 0
# Is tankage available for properly waste sludge? • 0 0 0
Page# 3
Permit: NC0056618
Owner - Facility: Carolina Pines Estates WWTP
Inspection Date: 03/11/2022 Inspection Type: Compliance Evaluation
Aerobic Digester
Comment:
Yes No NA NE
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • ❑ 0 ❑
Is the site free of excessive buildup of solids in center well of circular clarifier? • ❑ ❑ 0
Are weirs level? ■ ❑ ❑ ❑
Is the site free of weir blockage? • 0 0 ❑
Is the site free of evidence of short-circuiting? • 0 ❑ ❑
Is scum removal adequate? ❑ ❑ • ❑
Is the site free of excessive floating sludge? 0 0 ❑
Is the drive unit operational? • 0 0 ❑
Is the return rate acceptable (low turbulence)? • 0 0 ❑
Is the overflow clear of excessive solids/pin floc? • 0 0 0
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) ❑• ❑ ❑
Comment: The sludge blanket in clarifier 1 was 14 feet and clarifier 2 had a sludge blanket of 14
feet.
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ 0 I ❑
application?
Is the facility as described in the permit? ❑ • 0 0
# Are there any special conditions for the permit? • ❑ 0 ❑
Is access to the plant site restricted to the general public? • 0 0 ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment: The permit list tablet de -chlorination is being used but the facility is using liquid
de-chlorination.
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting? • 0 0 0
Is flow meter calibrated annually? • 0 0 0
Is the flow meter operational? I 0 0 0
(If units are separated) Does the chart recorder match the flow meter? 0 ❑ IN ❑
Comment: The flow meter was calibrated by Delta System in July 2022.
Page# 4
Permit: NC0056618 Owner - Facility: Carolina Plnes Estates WWTP
Inspection Date: 03/11/2022 inspection Type: Compliance Evaluation
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots? IM 0 0 0
Are surface aerators and mixers operational? 0 ❑ MI 0
Are the diffusers operational? • 0 ❑ 0
Is the foam the proper color for the treatment process? • ❑ ❑ 0
Does the foam cover Tess than 25% of the basin's surface? I 0 ❑ 0
Is the DO level acceptable? ❑ 1 0 0
Is the DO level acceptable?(1.0 to 3.0 mg/I) • 0 0 0
Comment: The DO in aeration tank 1 was 4.43 mq/L and aeration tank 2 was 1.2 mq/L.
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Comment:
Disinfection -Liquid
Is there adequate reserve supply of disinfectant?
(Sodium Hypochlorite) Is pump feed system operational?
Is bulk storage tank containment area adequate? (free of leaks/open drains)
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de-chlorinatlon?
Comment: Water Guard comes every week to refill the Sodium Hypochlorite.
Yes No NA NE
• ❑ ❑ ❑
II ❑ ❑ ❑
❑ ❑ ❑ •
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
De -chlorination Yes No NA NE
Type of system ? Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)? • ❑ 0 0
Is storage appropriate for cylinders? • 0 0 ❑
# Is de -chlorination substance stored away from chlorine containers? • ❑ ❑ 0
Are the tablets the proper size and type? ❑ 0 • ❑
Page# 5
Permit: NC0056618 Owner - Fadlity: Carolina Pines Estates WWTP
Inspection Date: 03/11/2022 Inspection type: Compliance Evaluation
De -chlorination Yes No NA NE
Comment: The perimit has tablet de -chlorination system listed as being used but the facility is
using liquid Calcium Thiosulfate.
Are tablet de -chlorinators operational? ❑ ❑ ❑
Number of tubes in use?
Comment:
Effluent Sampling Yes No NA Ng
Is composite sampling flow proportional? ❑ ❑
Is sample collected below all treatment units? •❑ ❑ ❑
Is proper volume collected? •❑ ❑ ❑
Is the tubing clean? •❑ ❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 ❑ ❑ ❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type •❑ ❑ ❑
representative)?
Comment: Sample storage unit temperature was 5 degrees C at the time of inspection.
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
11112012
■ ❑ ❑ ❑
� ❑ ❑ ❑
•
❑ ❑ ❑
Comment: There fuel vendor is Mallard qas. There was a full tank of fuel the day of Inspection,
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? MO ❑ ❑
Is all required information readily available, complete and current? ▪ ❑ ❑ ❑
Are all records maintained for 3 years (lab. reg. required 5 years)? ■ ❑ ❑ ❑
Are analytical results consistent with data reported on DMRs? • 0 0 0
Is the chain -of -custody complete? •❑ ❑ ❑
Dates, times and location of sampling
Page# 6
Permit: NC0056618 Owner - Facility: Carolina Pines Estates WWTP
Inspection Date: 03/11/2022 Inspection Type: Compliance Evaluation
Record Keeping
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
■
•
•
•
• ❑ ❑ ❑
❑ ❑ • ❑
❑ ❑ • ❑
• ❑ ❑ ❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Comment: A spot check looking at September 2021 DMRs, lab reports, chain-of-custodv, and
bench sheets was conducted.
Page# 7