HomeMy WebLinkAboutNC0065889_Compliance Evaluation Inspection_20220411DocuSign Envelope ID: C8015DC3-02B0-4254-B9BD-B5315B8EB1 BE
ROY COOPER
Governor
ELIZABETH S. RISER
Secretary
RICHARD E. ROGERS, JR.
Director
NORTH CAROLINA
Environmental Quality
SENT VIA ELECTRONIC MAIL ONLY: NO HARD COPY WILL BE MAILED.
April 11, 2022
Harrison Merrill Jr.
Indian Creek Resort, LLC
E-mail: Whmerrilltrust.com
SUBJECT: Compliance Inspection Report
Catatoga at Lake Toxaway WWTP
NPDES WW Permit No. NC0065889
Transylvania County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Catatoga at Lake
Toxaway WWTP on 4/07/2022. This inspection was conducted to verify that the facility is operating in
compliance with the conditions and limitations specified in NPDES WW Permit No. NC0065889. The
findings and comments noted during this inspection are provided in the enclosed copy of the inspection
report entitled "Compliance Inspection Report".
If you should have any questions, please do not hesitate to contact Timothy Heim with the Water
Quality Regional Operations Section in the Asheville Regional Office at 828-296-4500 or via email at
tim.heim@ncdenr.gov.
ATTACHMENTS
Ec: Drew Hooper — ORC, LF
Sincerely,
�DocuSigned by:
'-E397192DABFB4FF...
Daniel Boss, Asst. Regional Supervisor
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
North Carolina Department of Environmental Quelfy I olvtslon of Water Resources
Asheville Regional Office 12090 O.S. Highway 70 I Swannanoa, Noah Carolina 28778
828.290 4500
DocuSign Envelope ID: C8015DC3-02B0-4254-B9BD-B5315B8EB1 BE
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection
1 IN I 2 LI 3 I NC0065889 111 121 22/04/07 117
Type
18110
IIIIIIIIIII
Inspector Fac Type
19 I S I 201
21IIIIII IIIIIIIIIIIIIIIIII I IIIIII
P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
671 I 70I I 711 172 I N I 731 I 74 71
I I
I I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Catatoga at Lake Toxaway WWTP
Indian Creek Trl Off US Hwy 64
Lake Toxaway NC 28747
Entry Time/Date
10:OOAM 22/04/07
Permit Effective Date
17/11/01
Exit Time/Date
12:OOPM 22/04/07
Permit Expiration Date
22/08/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Andrew Duane Hooper/ORC/864-903-4637/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Harrison Merri11,8000 Capps Ferry Rd Douglasville GA 301356525//404-467-6918/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Facility Site Review Effluent/Receiving Wate
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Timothy H Heim DWR/ARO WQ/828-296-4665/ 4/11/2022
(—DocuSigned by:
"-082B1105A3CA418...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
�DocuSigned by:
,6,,,, 4—, 4/11/2022
,..—„, 4,n,,,.. p
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
DocuSign Envelope ID: C8015DC3-02B0-4254-B9BD-B5315B8EB1 BE
31
NPDES yr/mo/day
NC0065889 111 121 22/04/07
I17
Inspection Type
18LI
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Tim Heim of the Asheville Regional Office performed a Compliance Inspection of the Facility on April
7, 2022. Drew Hooper (ORC — Goldie Associates) was present and assisted with the inspection. The
facility appeared in compliance with Permit NC0065889.
The following items were noted during the inspection:
The facility fence, overhanging trees, broken UV bulb, and UV battery backup system have all been
repaired or replaced since being noted in the last inspection.
Complete planned installation of the new influent pump station and control panel.
Repair the UV transmittance indicator panel.
Clean the scum baffle in the secondary clarifier.
Page# 2
DocuSign Envelope ID: C8015DC3-02B0-4254-B9BD-B5315B8EB1 BE
Permit: NC0065889
Inspection Date: 04/07/2022
Owner - Facility: Catatoga at Lake Toxaway WWTP
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable II El El El
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new El ❑ ❑
application?
Is the facility as described in the permit? • El El El
# Are there any special conditions for the permit? El • El El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment:
Bar Screens Yes No NA NE
Type of bar screen
a.Manual •
b.Mechanical ❑
Are the bars adequately screening debris? • ❑ ❑ ❑
Is the screen free of excessive debris? • ❑ ❑ ❑
Is disposal of screening in compliance? • ❑ ❑ ❑
Is the unit in good condition? ❑ El • ❑
Comment:
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots? • El ❑ ❑
Are surface aerators and mixers operational? ❑ El • ❑
Are the diffusers operational? ■ ❑ ❑ ❑
Is the foam the proper color for the treatment process? • ❑ ❑ ❑
Does the foam cover less than 25% of the basin's surface? • ❑ ❑ ❑
Is the DO level acceptable? ❑ ❑ ❑ •
Page# 3
DocuSign Envelope ID: C8015DC3-02B0-4254-B9BD-B5315B8EB1 BE
Permit: NC0065889
Inspection Date: 04/07/2022
Owner - Facility: Catatoga at Lake Toxaway WWTP
Inspection Type: Compliance Evaluation
Aeration Basins
Is the DO level acceptable?(1.0 to 3.0 mg/I)
Comment:
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment:
Disinfection - UV
Are extra UV bulbs available on site?
Are UV bulbs clean?
Is UV intensity adequate?
Is transmittance at or above designed level?
Is there a backup system on site?
Is effluent clear and free of solids?
Comment:
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Yes No NA NE
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
• ❑ ❑ ❑
II El El El
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ ❑ •
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ • ❑
Page# 4