HomeMy WebLinkAboutNC0060755_Compliance Evaluation Inspection_20220407ROY COOPER
Governor
ELIZABETH 5. B1SER.
Secretary
RICHARD E. ROGERS, JR.
Director
Mr. Kenny Knopf, Area Manager
Carolina Water Services, Inc of NC
8107 S. Arrowridge Blvd
Charlotte, NC 28273
Dear Mr. Knopf:
NORTH CAROLINA
awironmentaf Quality
April 7, 2022
Subject: Compliance Evaluation Inspection
Saddlewood Subdivision WWTP
NPDES Permit No. NC0060755
Gaston County
Enclosed is a copy of the Compliance Evaluation Inspection for the inspection conducted
at the subject facility on April 5, 2022, by Ori Tuvia. Your cooperation during the site visit were
much appreciated. Please advise the staff involved with this NPDES Permit by forwarding a copy
of the enclosed report.
Although the bar screen was in compliance at the time of inspection, the bar screen
appeared undersized. It is recommended that you consider the installation of a larger capacity
bar screen.
The report should be self-explanatory; however, should you have any questions, please
do not hesitate to contact Ori Tuvia at (704) 235-2190, or at ori.tuvia@ncdenr.gov.
Cc: Laserfiche
Sincerely,
DocuSigned by:
44..11414w H P:z>ket.
F161FB69A2D84A3...
for
W. Corey Basinger
Regional Supervisor
Mooresville Regional Office
Division of Water Resources
North Carolina Drpartrncnt of Environmental Quallty I Division of Water Resources
MooresvilleRtgionakOffice 1610East Center Avenue. Smote 301 I Mooresville. North.Caratlna 28115
7c 4.6b3.16]9
United States Environmental Protection Agency
E PA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction
1 IN I
21IIIIII
Code NPDES yr/mo/day Inspection
2 L 3 I NC0060755 111 121 22/04/05 117
Type
1810I
IIIIIIIIIII
Inspector Fac Type
191S I 2011
IIIIIIIIIIIIIIIIII I IIIIII
P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
67I1.0 I 70I4 I 71IN I 72 I N I 731 1 74 751
I I 1
I I I I I I 180
l
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Saddlewood WWTP
335 Fair Meadows Ct
Gastonia NC 28052
Entry Time/Date
09:30AM 22/04/05
Permit Effective Date
20/12/01
Exit Time/Date
10:35AM 22/04/05
Permit Expiration Date
25/08/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Kenneth Wayne Knopf/ORC/704-525-7990/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Martin Lashua,PO Box 240908 Charlotte NC 282240908/Regional
Director/704-319-0517/7045258174 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and
Ori A Tuvia
Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers
Date
4/7/2022
DocuSigned by:
DWR/MRO WQ/704-663-1699/
-<�
BB057A2DE017498...
Signature of M ag&?fATfAeviewer Agency/Office/Phone and Fax Numbers Date
Andrew Pit e "4 H P WR/MRO WQ/704-663-1699 Ext.2180/ 4.7.22
F161 FB69A2D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
NPDES yr/mo/day
31 NC0060755 111 121 22/04/05
I17
Inspection Type
18 [j
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page# 2
Permit: NC0060755
Inspection Date: 04/05/2022
Owner - Facility: Saddlewood WWTP
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ ❑
application?
Is the facility as described in the permit? • ❑ El El
# Are there any special conditions for the permit? El • El El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment: The subject permit expires on August 31, 2025.
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? • ❑ ❑ ❑
Is all required information readily available, complete and current? • ❑ ❑ ❑
Are all records maintained for 3 years (lab. reg. required 5 years)? ❑ ❑ ❑ •
Are analytical results consistent with data reported on DMRs? • ❑ El El
Is the chain -of -custody complete? • El El El
Dates, times and location of sampling •
Name of individual performing the sampling •
Results of analysis and calibration ■
Dates of analysis •
Name of person performing analyses •
Transported COCs ■
Are DMRs complete: do they include all permit parameters? • El El ❑
Has the facility submitted its annual compliance report to users and DWQ? El El • El
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified ❑ El • ❑
operator on each shift?
Is the ORC visitation log available and current? • El El El
Is the ORC certified at grade equal to or higher than the facility classification? • El ❑ ❑
Is the backup operator certified at one grade less or greater than the facility • El El El
classification?
Is a copy of the current NPDES permit available on site? • ❑ El El
Facility has copy of previous year's Annual Report on file for review? El El • El
Comment: The records reviewed during the inspection were well organized and maintained.
DMR's, COC's, ORC logs and calibration logs were reviewed for the period of October
2021 through December 2021.
Page# 3
Permit: NC0060755
Inspection Date: 04/05/2022
Owner - Facility: Saddlewood WWTP
Inspection Type: Compliance Evaluation
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ ❑ • ❑
Is sample collected below all treatment units? • ❑ ❑ ❑
Is proper volume collected? ■ ❑ ❑ ❑
Is the tubing clean? ❑ ❑ • ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 ❑ ❑ • ❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • El El El
representative)?
Comment: The subject permit requires grab effluent sampling.
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, MODE
and sampling location)?
Comment:
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ • ❑
❑ ❑ • ❑
Comment: Field analyses are performed under the facility laboratory (certification 5228). K&W
Labs (NH3, TSS, Fecal, and BOD) also been contracted to provide analytical support.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable • ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The wastewater treatment plant appeared to be properly operated and well maintained.
Bar Screens Yes No NA NE
Type of bar screen
a.Manual •
b.Mechanical El
Page# 4
Permit: NC0060755
Inspection Date: 04/05/2022
Owner - Facility: Saddlewood WWTP
Inspection Type: Compliance Evaluation
Bar Screens
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment: The bar screen appeared to be undersized.
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots? ■ ❑ ❑ ❑
Are surface aerators and mixers operational? El El • ❑
Are the diffusers operational? • El El El
Is the foam the proper color for the treatment process? • El ❑ ❑
Does the foam cover less than 25% of the basin's surface? • El El El
Is the DO level acceptable? • El ❑ ❑
Is the DO level acceptable?(1.0 to 3.0 mg/I) El El El •
Comment:
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment:
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 5
Permit: NC0060755
Inspection Date: 04/05/2022
Owner - Facility: Saddlewood WWTP
Inspection Type: Compliance Evaluation
Disinfection -Liquid
Is there adequate reserve supply of disinfectant?
(Sodium Hypochlorite) Is pump feed system operational?
Is bulk storage tank containment area adequate? (free of leaks/open drains)
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
De -chlorination Yes No NA NE
Type of system ? Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ ❑ •
Is storage appropriate for cylinders? • ❑ ❑ ❑
# Is de -chlorination substance stored away from chlorine containers? ❑ ❑ • ❑
Comment:
Are the tablets the proper size and type? ❑ ❑ ■ ❑
Are tablet de -chlorinators operational? ❑ ❑ • ❑
Number of tubes in use?
Comment:
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: Flow meter was last aclibrated on 12/14/2021 by B.W. Allen Company.
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment: The effluent appeared clear with no floatable foam.
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
Page# 6
Permit: NC0060755
Inspection Date: 04/05/2022
Owner - Facility: Saddlewood WWTP
Inspection Type: Compliance Evaluation
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 7