HomeMy WebLinkAboutNC0034703_Compliance Evaluation Inspection_20220328ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR. NORTH CAROLINA
Director Environmental Quality
March 28, 2022
Anthony Vann, Assistant Superintendent
Rowan -Salisbury Schools
PO Box 2349
Salisbury, NC 28145
SUBJECT: Compliance Evaluation Inspection
Permit No. NC0034703
Knollwood Elementary School
Rowan County
Mr. Vann:
On March 23, 2022, Roberto Scheller of this Office conducted a compliance inspection at the
subject facility. This inspection was conducted as a Compliance Evaluation Inspection (CEI) to
ensure compliance with permit requirements and conditions. The subject facility appeared to be
well operated, maintained, and discharging a clear effluent. We wish to thank the operating staff
for their assistance regarding this inspection.
The enclosed report should be self-explanatory; however, should you have any questions, please
contact myself or Roberto Scheller at (704) 235-2204 or roberto.schellerncdenr.gov.
Sincerely,
DocuSigned by:
Al 4CC681AF27425...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
Enclosure: Compliance Evaluation Inspection Report
cc: Todd F Robinson, ORC, email: trobinson@envirolink.com
Laserfiche
NORTH CAROLINA DE
mo.m.dorEnvironmental w.i�
North Carolina Department of Environmental Quality I Division of Water Resources
512 North Salisbury Street 11611 Mail Service Center I Raleigh, North Carolina 27699-1611
919.707.9000
671
EPA
United States Environmental Protection Agency
Washington, D.C. 20460
Water Compliance Inspection Report
Section A: National Data System Coding (i.e., PCS)
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Transaction Code NPDES yr/mo/day Inspection Type Inspector Fac Type
1 ILI I 2[ I 3 1 NC0034703 111 121 22/03/23 117 181 sI 191 G I 201 1
21111111 1111111111111111111111111 1 1 1 1 1 1 1 I I 1 1
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
711 1
7013 1
Section B: Facility Data
72N1
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Knollwood Elementary School
3075 Shue Rd
Salisbury NC 28144
r6
731 1 174 751 1 1 1 1 1 1 180
Entry Time/Date
09:50AM 22/03/23
Exit Time/Date
10:15AM 22/03/23
Permit Effective Date
19/07/01
Permit Expiration Date
24/06/30
Name(s) of Onsite Represent ative(s)/Titles(s)/Phone and Fax Number(s)
///
Daniel Gatewood/ORC/704-848-4849/
Name, Address of Responsible Official/Title/Phone and Fax Number
J. H. Bivens,515 N Clay St Salisbury NC 28144/Maintenance Director/704-639-3016/
Contacted
No
Other Facility Data
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Facility Site Review Compliance Schedules Effluent/Receiving Wate M Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
r—DocuSigned by:
Roberto Scheller (%-e, DWR/MRO WQ/707-235-2204/ 3/24/2022
�— 91C2A007838943E...
Signature of Management Q A Reviewer
Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger DWR/Division of Water Quality/704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
"—A14CC681AF27425...
3/28/2022
Page# 1
NPDES yr/mo/day Inspection Type
31 NC0034703 111 121 22/03/23 117 18 19 I
(Cont.)
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
1
The subject permitted wastewater treatment facility is a 0.011 MGD WWTP consisting of EQ Basin,
Package Plant, Dosing Tank and Sand Filters, Tablet C12, Tablet De-Chlor, and Flow Meter.
Treatment facility discharges into Little Creek which is Classified as Class C waters in the Yadkin
Pee -Dee River Basin. The current NPDES Permit was issued on April 1, 2019 and expires on June
30,2024.
Review of 12 month compliance history, from February 2021 through January 2022, found three
reported limit violations: 8-2021 Fecal Coliform,Daily Maximum limit violation (NOV issued) and
1-2022 TSS, Daily Maximum and Monthly Average limit violations (NOV issued).
Sticker on flow meter indicates that last calibration was July 16, 2020, with a due date for calibration
July 2021. If this in incorrect, please send a copy of updated calibration sheet to this Office.
Page# 2
Permit: NC0034703
Inspection Date: 03/23/2022
Owner - Facility: Knollwood Elementary School
Inspection Type: Compliance Evaluation
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment: Permit NC0034703 expires on June 30, 2024.
Yes No NA NE
❑ ❑ ❑
❑ ❑ ❑
❑ Cl ❑
❑ ❑ ❑
❑ ❑ ❑
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? M ❑ ❑ ❑
Is all required information readily available, complete and current? M❑ ❑ ❑
Are all records maintained for 3 years (lab. reg. required 5 years)? M❑ ❑ 0
Are analytical results consistent with data reported on DMRs? M ❑ ❑ ❑
Is the chain -of -custody complete? M ❑ ❑ ❑
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters? ❑ ❑ ❑
Has the facility submitted its annual compliance report to users and DWQ? 0 ❑ 0
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified ❑ ❑ ❑
operator on each shift?
Is the ORC visitation log available and current? ❑ ❑ 0
Is the ORC certified at grade equal to or higher than the facility classification? 0 ❑ ❑
Is the backup operator certified at one grade less or greater than the facility M ❑ ❑ ❑
classification?
Is a copy of the current NPDES permit available on site? ❑ ❑ Cl
Facility has copy of previous year's Annual Report on file for review? ❑ ❑ ❑
Comment:
Compliance Schedules
Is there a compliance schedule for this facility?
Yes No NA NE
❑ ❑ ❑
Page# 3
Permit: NC0034703
Inspection Date: 03/23/2022
Owner - Facility: Knollwood Elementary School
Inspection Type: Compliance Evaluation
Compliance Schedules
Is the facility compliant with the permit and conditions for the review period?
Comment: Treatment facility treats wastewater from Knollwood Elementary School.
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Comment: Contract lab Statesville Analytical Certification #440.
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Aeration Basins
Mode of operation
Type of aeration system
Is the basin free of dead spots?
Yes No NA NE
❑ ❑ ❑
Yes No NA NE
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
Yes No NA NE
❑ ❑ ❑
❑❑❑
Yes No NA NE
El
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
Yes No NA NE
Ext. Air
Diffused
❑ ❑ ❑
Page# 4
Permit: NC0034703
Inspection Date: 03/23/2022
Owner - Facility: Knollwood Elementary School
Inspection Type: Compliance Evaluation
Aeration Basins Yes No NA NE
Are surface aerators and mixers operational? 0 0 ❑
Are the diffusers operational? MI 0 0 0
Is the foam the proper color for the treatment process? • 0 0 0
Does the foam cover less than 25% of the basin's surface? • 0 0 0
Is the DO level acceptable? 0 0 0 •
Is the DO level acceptable?(1.0 to 3.0 mg/I) 0 0 0
Comment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • 0 0 0
Is the site free of excessive buildup of solids in center well of circular clarifier? • 0 0 0
Are weirs level? ■ 0 0 0
Is the site free of weir blockage? • 0 0 0
Is the site free of evidence of short-circuiting? • 0 0 0
Is scum removal adequate? • 0 0 0
Is the site free of excessive floating sludge? • 0 0 0
Is the drive unit operational? 0 0 0
Is the return rate acceptable (low turbulence)? • 0 0 0
Is the overflow clear of excessive solids/pin floc? • 0 0 0
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) 0 0 0 •
Comment:
Sand Filters (Low rate)
(If pumps are used) Is an audible and visible alarm Present and operational?
Is the distribution box level and watertight?
Is sand filter free of ponding?
Is the sand filter effluent re -circulated at a valid ratio?
# Is the sand filter surface free of algae or excessive vegetation?
# Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1)
Comment: Once through sand filter.
Flow Measurement - Effluent
# Is flow meter used for reporting?
Yes No NA NE
❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
Yes No NA NE
❑ ❑ ❑
Page# 5
Permit: NC0034703
Inspection Date: 03/23/2022
Owner - Facility: Knollwood Elementary School
Inspection Type: Compliance Evaluation
Flow Measurement - Effluent
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
❑ ❑ ❑
❑ ❑ ❑
❑ ❑ ❑
Comment: Sticker on Flow meter indicated that last calibration date was July 16, 2020, with next
calibration due July 2021. If calibration date on flow meter is not correct please provide
this Office with last calibration date.
Disinfection -Tablet
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Number of tubes in use?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Comment:
Yes No NA NE
❑ ❑ ❑
❑ ❑ ❑
2
❑ ❑ ❑
❑ ❑ ❑
III ❑ ❑ ❑
De -chlorination Yes No NA NE
Type of system ? Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)? 0 ❑ ❑
Is storage appropriate for cylinders? ❑ ❑ 0
# Is de -chlorination substance stored away from chlorine containers? 0 ❑ 0 III
Comment:
Are the tablets the proper size and type?
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment:
1
❑ ❑ ❑
❑ ❑ El
Page# 6