HomeMy WebLinkAboutNC0035041_Compliance Evaluation Inspection_20220328ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
RICHARD E. ROGERS, JR. NORTH CAROLINA
Director Environmental Quality
March 28, 2022
Mr. Tony Konsul
Carolina Water Service, Inc. of NC, LLC
Post Office Box 240908
Charlotte, NC 28224
SUBJECT: Compliance Evaluation Inspection
Hemby Acres WWTP
NPDES Permit #NC0035041
Union County, NC
Mr. Konsul:
On March 24, 2022, Roberto Scheller of this Office conducted an inspection at the subject facility.
This inspection was conducted as a Compliance Evaluation Inspection (CEI) to ensure compliance
with permit requirements and conditions. At time of inspection, the subject facility appeared to
be well maintained and operated. We wish to thank your operating staff for their assistance
regarding this inspection.
The enclosed report should be self-explanatory; however, should you have any questions, please
do not hesitate to contact Roberto Scheller, of the Mooresville Regional Office, at 704-663-1699
or roberto.scheller@ncdenr.gov.
Enclosure: Inspection Report
Cc: LaserFiche
NORTH CAROLINA DE
mo.m.m or Environmental w.i�
Sincerely,
,—DocuSigned by:
`—A14CC681 AF27425...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
North Carolina Department of Environmental Quality I Division of Water Resources
512 North Salisbury Street 11611 Mail Service Center I Raleigh, North Carolina 27699-1611
919.707.9000
United States Environmental Protection Agency
E PA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code
1 IN I 2 IL I
21IIIIII
NPDES yr/mo/day Inspection
3 I NC0035041 111 121 22/03/24 117
Type
1810I
IIIIIIIIIII
Inspector Fac Type
19I S I 2011
IIIIIIIIIII IIIIIII I IIIIII
P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
671 I 70I3 I 711 1 72 I N I 73I 1 74 71
I I 1
I I I I I I I80
l
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES Dermit Number)
Hemby Acres WWTP
7803 Idlewild Rd
Indian Trail NC 28079
Entry Time/Date
10:26AM 22/03/24
Permit Effective Date
19/02/01
Exit Time/Date
11:58AM 22/03/24
Permit Expiration Date
23/10/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Thomas C Capps/ORC/704-361-5067/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Mark Richard Haver,PO Box 240908 Charlotte NC 282240908/Area
Manager/704-525-7990/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signatur
Roberto Scheller
s 4911r§t31f(s) Agency/Office/Phone and Fax Numbers
V
Date
3/28/2022
DWR/MRO WQ/707-235-2204/
91C2A007838943E...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger DWR/Division of Water Quality/704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
3/28/2022
Page# 1
"-A14CC681AF27425...
31
NPDES yr/mo/day
N C0035041 111 121 22/03/24
I17
Inspection Type
18 [j
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
On March 24, 2022 a Compliance Evaluation Inspection (CEI) was conducted at HembyAcers WWTP.
Permit for this facility (NC0035041) became active February 1, 2019 and expires October 31, 2023.
Discharge from treatment facility is via permitted Outfall #001 into the North Fork of Crooked Creek,
which is classified as Class C waters in the Yadkin Pee -Dee River Basin.
12-Month review of compliance history for the period February 2021 through January 2022, found no
reported permit limit violations.
The permitted facility is a 0.3 MGD WWTP consisting of Influent Pump Station, Micro Screen (Bar
Screen),
2-Aeration Basins, 2-Secondary Clarifiers, 2-Tertiary Filters, Liquid Chlorine (Sodium Hypochlorite),
Liquid De -chlorination (Sodium Bi-Sulfite), Post Aeration, Continuous Flow Measurement, and
Back-up Generator.
At time of inspection effluent was clear with no visible suspended solids.
Page# 2
Permit: NC0035041
Inspection Date: 03/24/2022
Owner- Facility: Hemby Acres WWTP
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new El El ❑
application?
Is the facility as described in the permit? • El El El
# Are there any special conditions for the permit? El El • El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • El El El
Comment: Permit effective February 1, 2019 and expires on October 31, 2023.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Comment: Records were current and readily available for review.
Laboratory
Are field parameters performed by certified personnel or laboratory?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
•
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
Page# 3
Permit: NC0035041
Inspection Date: 03/24/2022
Owner- Facility: Hemby Acres WWTP
Inspection Type: Compliance Evaluation
Laboratory
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ ❑
Comment: Facility use contract lab K&W Laboratory, Certification # 559, and on -site Field Lab
Certification #5228.
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment: Bar screen had been replaced with Micro Screen.
Yes No NA NE
•
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Surface
Is the basin free of dead spots? • ❑ ❑ ❑
Are surface aerators and mixers operational? • ❑ ❑ ❑
Are the diffusers operational? ❑ ❑ • ❑
Is the foam the proper color for the treatment process? • ❑ ❑ ❑
Does the foam cover less than 25% of the basin's surface? • ❑ ❑ ❑
Is the DO level acceptable? ❑ ❑ ❑ •
Is the DO level acceptable?(1.0 to 3.0 mg/I) ❑ ❑ ❑ •
Comment:
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 4
Permit: NC0035041
Inspection Date: 03/24/2022
Owner- Facility: Hemby Acres WWTP
Inspection Type: Compliance Evaluation
Secondary Clarifier
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Comment: At time of inspection effluent from secondary clarifers was clear with few visible
suspended solids. Sludge blanket was at 16 to 18 inches.
Filtration (High Rate Tertiary)
Type of operation:
Is the filter media present?
Is the filter surface free of clogging?
Is the filter free of growth?
Is the air scour operational?
Is the scouring acceptable?
Is the clear well free of excessive solids and filter media?
Comment:
Disinfection -Liquid
Is there adequate reserve supply of disinfectant?
(Sodium Hypochlorite) Is pump feed system operational?
Is bulk storage tank containment area adequate? (free of leaks/open drains)
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Comment:
De -chlorination
Type of system ?
Yes No NA NE
Down flow
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
Liquid
Page# 5
Permit: NC0035041
Inspection Date: 03/24/2022
Owner- Facility: Hemby Acres WWTP
Inspection Type: Compliance Evaluation
De -chlorination
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Are the tablets the proper size and type?
Comment: Sodium Bi-Sulfite is used for de -chlorination.
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment:
Yes No NA NE
❑ ❑ ❑ •
• ❑ ❑ ❑
❑ ❑ • ❑
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? • ❑ El El
Is sample collected below all treatment units? • El El El
Is proper volume collected? • El ❑ ❑
Is the tubing clean? ■ El El El
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 • El El El
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • El El El
representative)?
Comment: At time of inspection effluent sampler was recorded at 4 degrees Celsius.
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: Flow meter was calibrated last on December 13, 2021 by B.W. Allen Co. At time of
inspection Flow meter was recording 284.7 GPM.
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Yes No NA NE
Page# 6
Permit: NC0035041
Inspection Date: 03/24/2022
Owner- Facility: Hemby Acres WWTP
Inspection Type: Compliance Evaluation
Standby Power
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
Comment: Generator maintained by Kraft Power, Inc.
Yes No NA NE
• ❑ ❑ ❑
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable MODE
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Process control include 30-minute Settleable Solids Test and Percent Solids Test.
Aerobic Digester Yes No NA NE
Is the capacity adequate? • ❑ El El
Is the mixing adequate? • ❑ ❑ ❑
Is the site free of excessive foaming in the tank? • El El El
# Is the odor acceptable? • ❑ El El
# Is tankage available for properly waste sludge? • El El El
Comment:
Page# 7