HomeMy WebLinkAboutNon-Discharge Effluent Monitoring Policy 160209State of North Carolina Department of Environment and Natural Resources Division of Water Resources WATER QUALITY PERMITTING SECTION NON-DISCHARGE EFFLUENT MONITORING FOR DOMESTIC WASTEWATER February 9, 2016 PCS Code Parameter – PCS Code Units Frequency 1 Sample Type 2 00310 BOD, 5-Day (20 ºC) mg/L See Table 2 Composite 3 00940 Chloride (as Cl) 4 mg/L Same as GW monitoring Composite 3 50060 Chlorine, Total Residual 5 mg/L Major 6 5 x Week 8 Grab 10 Minor 7 Weekly 9 31616 Coliform, Fecal MF, M-FC Broth, 44.5 ºC #/100 mL See Table 2 Grab 10 50050 Flow, in Conduit or thru Treatment Plant 11 GPD Major 6 Continuous Major 6 Recorder Minor 7 Monthly Minor 7 Estimate 00610 Nitrogen, Ammonia Total (as N) mg/L See Table 2 Composite 3 00620 Nitrogen, Nitrate Total (as N) mg/L See Table 2 Composite 3 00625 Nitrogen, Kjeldahl, Total (as N) mg/L See Table 2 Composite 3 00600 Nitrogen, Total (as N) mg/L See Table 2 Composite 3 00400 pH s.u. Major 6 5 x Week 8 Grab 10 Minor 7 Weekly 9 00665 Phosphorus, Total (as P) mg/L See Table 2 Composite 3 70300 Solids, Total Dissolved – 180 ºC 4 mg/L Same as GW monitoring Composite 3 00530 Solids, Total Suspended mg/L See Table 2 Composite 3 00076 Turbidity, HCH Turbidimeter 12 NTU Continuous Recorder 1. Permits not matching recommended sampling frequencies shall include documentation in the Cover Letter and Attachment A footnotes supporting this variation. 2. For Active Treatment Systems (e.g., extended aeration, anoxic, MBR, etc.), if Q < 30,000 GPD, sample type can be grab (15A NCAC 02B .0505). For Passive Treatment Systems (e.g., facultative lagoons, septic tanks, etc.), sample type shall be grab. 3. See 15A NCAC 02B .0503(4). 4. Applicable only for facilities with groundwater monitoring wells. 5. Applicable only if chlorine is used as a disinfectant. 6. Q ≥ 10,000 GPD. 7. Q < 10,000 GPD. 8. Lagoon type systems with weekly ORC visits can have a weekly sampling frequency for pH and/or Total Residual Chlorine. 9. Total Residual Chlorine / pH can be “Per Event” if Permittee documents that the facility infiltrates/irrigates at a rate less than once per week. 10. See 15A NCAC 02B .0503(14). 11. Flow thru treatment plant should be monitored at a representative location (i.e., flow monitoring is not acceptable following treatment systems with substantial equalization such as lagoons). 12. Applicable only for Reclaimed Water facilities, and facilities complying with the High-Rate Infiltration Policy. Table 2 – Recommended Sampling Frequencies Flow (GPD) Active Treatment Systems (e.g., extended aeration, anoxic, MBR, etc.) Passive Treatment Systems (e.g., facultative lagoons, septic tanks, etc.) Mainland Systems Year-round Coastal Barrier Island Systems September 1st to April 30th Coastal Barrier Island Systems May 1st to August 31st With BNR 1 Without BNR With BNR 1 Without BNR With BNR 1 Without BNR ≤ 1000 3 x Year 3 x Year 3 x Year 3 x Year 3 x Year 3 x Year Annual > 1,000 to 10,000 Monthly 4 x Year Monthly 4 x Year Weekly Monthly 3 x Year > 10,000 to 100,000 2 x Month Monthly 2 x Month Monthly Weekly Weekly 4 x Year > 100,000 to 500,000 2 x Week 2 x Month 2 x Week 2 x Month 2 x Week Weekly Monthly > 500,000 3 x Week 2 x Week 3 x Week 2 x Week 3 x Week 2 x Week 2 x Month 1. Applies when Total Nitrogen (TN) and/or Total Phosphorus (TP) limits are met by a Biological Nutrient Removal (BNR) process. Table 3: Minimum Operator of Responsible Charge (ORC) Visitation Requirements for Classified Facilities (15A NCAC 08G .0204) Treatment Type Flow Criteria Classification Minimum ORC Visitation Schedule Surface Irrigation Systems with the exception of (a) and (b) N/A Surface Irrigation System Weekly 1 Domestic systems with septic tank/sand filters; biological lagoons; or constructed wetlands ≤ 1,500 GPD Surface Irrigation System 2 x Year 2 Domestic systems with ATUs (aerobic treatment units) ≤ 1,500 GPD Surface Irrigation System 2 x Year 2 Activated sludge or fixed growth 1,500 GPD to 0.5 MGD Grade II Biological 5 x Week Activated sludge or fixed growth + BNR required by permit 3 1,500 GPD to 0.5 MGD Grade III Biological 5 x Week Activated sludge or fixed growth 0.5 to 2.5 MGD Grade III Biological 5 x Week Activated sludge or fixed growth + BNR required by permit 3 0.5 to 2.5 MGD Grade IV Biological 5 x Week Activated sludge or fixed growth > 2.5 MGD Grade IV Biological 5 x Week Physical process (DAF, screening, filtration) N/A Grade I Phys/Chem Weekly Chemical process, RO, electrodialysis, and ultrafiltration N/A Grade II Phys/Chem 5 x Week 1. In the event of dual classification as a Surface Irrigation System and a Biological Treatment System, the visitation schedule for the surface irrigation system applies only to the irrigation portion of the system. The biological wastewater treatment facility visitation is set by a separate classification. 2. There must be a six month interval between visits. 3. Applies when Total Nitrogen (TN) and/or Total Phosphorus (TP) limits are met by a Biological Nutrient Removal (BNR) process.