HomeMy WebLinkAboutNC0036269_Sampling Inspection_20220217United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
1
21IIIIII
671
Transaction Code
IN I 2 I5
NPDES yr/mo/day Inspection
I 3 I NC0036269 111 121 22/02/01 117
Type
18 [ e
IIIIIIIIIII
Inspector Fac Type
191 S I 201
IIIIIIIIIIIIIIIIII I IIIIII
P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
I 70I3 I 711 1 72 I N I 731 I 74 71
I I
I I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES Dermit Number)
Rocky River WWTP
6400 Breezy Ln
Concord NC 280256972
Entry Time/Date
07:30AM 22/02/01
Permit Effective Date
21/11/01
Exit Time/Date
11:43AM 22/02/01
Permit Expiration Date
26/10/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
James Christian Sims/ORC/704-788-4164/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Travis M Fowler,232 Davidson Hwy Concord NC 280270428/Facilities
Director/704-788-4164/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signa
Roberto Scheller
ure btpfjlwycytor(s) Agency/Office/Phone and Fax Numbers
CSCIAILA., DWR/MRO WQ/707-235-2204/
Date
2/16/2022
"-91C2A007838943E...
Signature
of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
�Docusig� w 2/17/2022
�A14CC681AF27425...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
31
NPDES yr/mo/day
N C 0036269 111 121 22/02/01
I17
Inspection Type
18i i
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The subject treatment facility is a 26.5 MGD Two stage, pure oxygen WWTP. The Permit became
effective on November 1, 2021 and expires on October 31, 2026. Permit is for discharge to Rocky
River which is listed as Class C waters in the Yadkin -Pee Dee River Basin. Flow is tiered for 26.6
MGD, 30 MGD and 34 MGD with current instream waste concentrations (IWC), pecent effluent, of
66.5% @ 26.5 MGD, 69% @ 30 MGD, 71.8% @ 34 MGD.
Split samples for Chronic Toxicity were collected at time of inspection and results will be forwarded
under separate cover. Toxicity samples were collected on February 1st and 3rd.
Yearly average flow for calendar year 2021 was caculated @ 79.35% of permitted flow.
At time of inspection effluent was clear with no visible suspended soilds. At point of discharge a small
amount of foam was being generated but dissipated 50-60 feet downstream from discharge point.
Page# 2
Permit: NC0036269
Inspection Date: 02/01/2022
Owner - Facility: Rocky River WWTP
Inspection Type: Compliance Sampling
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ ❑
application?
Is the facility as described in the permit? • ❑ El El
# Are there any special conditions for the permit? • ❑ ❑ ❑
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment:
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Comment: Records reviewed were readily available and orderly.
Laboratory
Are field parameters performed by certified personnel or laboratory?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
•
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
Page# 3
Permit: NC0036269
Inspection Date: 02/01/2022
Owner - Facility: Rocky River WWTP
Inspection Type: Compliance Sampling
Laboratory
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Comment:
Yes No NA NE
II El El El
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable MODE
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Bar Screens Yes No NA NE
Type of bar screen
a.Manual ❑
b.Mechanical •
Are the bars adequately screening debris? • ❑ ❑ ❑
Is the screen free of excessive debris? • ❑ ❑ ❑
Is disposal of screening in compliance? • ❑ ❑ ❑
Is the unit in good condition? • ❑ ❑ ❑
Comment:
Grit Removal Yes No NA NE
Type of grit removal
a.Manual El
b.Mechanical •
Is the grit free of excessive organic matter? • ❑ ❑ ❑
Is the grit free of excessive odor? • ❑ ❑ ❑
# Is disposal of grit in compliance? • ❑ ❑ ❑
Comment:
Page# 4
Permit: NC0036269
Inspection Date: 02/01/2022
Owner - Facility: Rocky River WWTP
Inspection Type: Compliance Sampling
Influent Sampling
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is sampling performed according to the permit?
Comment: At time of inspection Influent sampler was recorded at 0 degrees Celsius.
Primary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the sludge blanket level acceptable?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment:
Pure Oxygen
Type of pure oxygen system
Is there a back-up source for the system?
Are mixers operational?
Are samples port/points easily accessible?
Comment:
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
Yes No NA NE
Generated on -site
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 5
Permit: NC0036269
Inspection Date: 02/01/2022
Owner - Facility: Rocky River WWTP
Inspection Type: Compliance Sampling
Secondary Clarifier
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Chemical Feed Yes No NA NE
Is containment adequate? • ❑ ❑ ❑
Is storage adequate? • ❑ ❑ ❑
Are backup pumps available? • ❑ El El
Is the site free of excessive leaking? ■ ❑ ❑ ❑
Comment:
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Comment: RAS, WAS pumps consist of 5 screw lift pumps.
Yes No NA NE
• ❑ ❑ ❑
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? • ❑ ❑ ❑
Is sample collected below all treatment units? • ❑ ❑ ❑
Is proper volume collected? • ❑ ❑ ❑
Is the tubing clean? ■ ❑ El ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 • El El El
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • ❑ El El
representative)?
Comment: At time of inspection effluent sampler was recorded at 3 degrees Celsius.
Page# 6
Permit: NC0036269
Inspection Date: 02/01/2022
Owner - Facility: Rocky River WWTP
Inspection Type: Compliance Sampling
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment:
Disinfection -Liquid
Is there adequate reserve supply of disinfectant?
(Sodium Hypochlorite) Is pump feed system operational?
Is bulk storage tank containment area adequate? (free of leaks/open drains)
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
De -chlorination Yes No NA NE
Type of system ? Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ ❑ •
Is storage appropriate for cylinders? ❑ ❑ • ❑
# Is de -chlorination substance stored away from chlorine containers? ❑ ❑ • ❑
Are the tablets the proper size and type? ❑ ❑ • ❑
Comment: Sodium Bisulfite is used for dechlorination.
Are tablet de -chlorinators operational? ❑ ❑ ■ ❑
Number of tubes in use?
Comment:
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 7
Permit: NC0036269
Inspection Date: 02/01/2022
Owner - Facility: Rocky River WWTP
Inspection Type: Compliance Sampling
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: Solids handling equipment consist of two gravity -flow sludge thickners, sludge
conditioning (plolymer addition), two centrifuges, sludge incinerator, sludge -ash settling
basin.
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 8