HomeMy WebLinkAboutWQCSD0238_Compliance Evaluation Inspection_20220215ROY COOPER.
Governor
ELIZABETH S. BISER
Secretary
S. DANIEL SMITH
Director
Tweetsie Railroad Collection System
Attn: Chris Robbins, Vice President
300 Tweetsie Railroad Ln
Blowing Rock, NC 28605
NORTH CAROLINA
Environmental Quality
March 2, 2022
SUBJECT: Compliance Evaluation Inspection
Tweetsie Railroad Collection System, WQCSD0238
Watauga County
Dear Chris Robbins:
Tricia Lowery, of the NC Division of Water Resources (DWR), Winston-Salem Regional Office (WSRO), visited
the Tweetsie Railroad Collection System on February 15, 2022, to perform a Compliance Evaluation Inspection (CEI).
The assistance and cooperation of Bobby Rowe and Travis Spencer was greatly appreciated. Details of the inspection
are recorded on the attached EPA Water Compliance Inspection Report.
Overall, the collection system is very well maintained and operated. The only areas of concern were:
1. Maps need to be updated with proper information (ie: pipe size, material, and flow). By implementing the
use of GIS, this will resolve the issue.
2. No grease control program. With areas on site preparing food, the education of proper grease control
procedures is critical in the overall health of the collection system. This could be in the form of posters in
food prep areas detailing proper disposal of grease material.
You are reminded that, in accordance with NC General Statute 143-215.6A, failure to comply with all
conditions of the permit subjects the City to civil penalties not to exceed $25,000.00 per violation, per day.
If you have any questions or require further assistance, please contact Tricia Lowery by phone at 336-776-
9691, or by email at tricia.lowery@ncdenr.gov . You may also contact me by phone at 336-776-9700, or by email at
lon.snider@ncdenr.gov.
Sincerely,
DocuSiiggned by:<
t— l . ciA,ac -
"- 145B49E225C94EA...
Lon T. Snider, Regional Supervisor
Water Quality Regional Operations Section
Winston-Salem Regional Office
Division of Water Resources, NCDEQ
Attachments:
1. EPA Water Compliance Inspection Report
cc: LaserFiche
NORTH
D E
D.o.rtm.m .f Dnim.mo.t.i au.i`
North Carolina Department of Environmental Quality Division of Water Resources
Winston-Salem Regional Office 1450 West Hanes Mill Road, Suite 300 I Winston-Salem, North Carolina 27105
336.776.9800
LD_E
NORTH CAROLINA
gapartmeM of Environmental quaky
North Carolina Department of Environmental Quality j Division of Water Resources
Winston-Salem Regional Office 1450 West Hanes Mill Road, Suite 300 I Winston-Salem, North Carolina 27105
336.776.9800
Compliance Inspection Report
Permit: WQCSD0238 Effective: 03/01/00 Expiration:
SOC: Effective: Expiration:
County: Watauga
Region: Winston-Salem
Contact Person: Chris B Robbins
Directions to Facility:
Owner : Tweetsie Railroad
Facility: Tweetsie Railroad Collection System
Title: Vp Phone: 828-264-9061
System Classifications:
Primary ORC: Certification: Phone:
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Inspection Date: 02/15/2022
Entry Time 11:OOAM Exit Time: 01:OOPM
Primary Inspector: Patricia Lowery Phone: 336-776-9691
Secondary Inspector(s):
Reason for Inspection: Routine Inspection Type: Collection System Inspect Non Sampling
Permit Inspection Type: Deemed permitted collection system management and operation
Facility Status: ❑ Compliant Not Compliant
Question Areas:
▪ Miscellaneous Questions
II Spills/Response Plan
▪ Pump Stations
(See attachment summary)
▪ General
▪ Inspections
▪ Grease Control
▪ Lines
Page 1 of 6
Permit: WQCSD0238 Owner - Facility:Tweetsie Railroad
Inspection Date: 02/15/2022
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Inspection Summary:
Tricia Lowery of the NC Division of Water Resources, Winston-Salem Regional Office conducted a compliance evaluation
inspection of WQCSD0238 — Tweetsie Railroad Collection Systems on February 15, 2022. Bobby Rowe and Travis Spencer
were present for the inspection. Results of the inspection are summarized in the following paragraphs:
15A NCAC 02T .0403 Permitting By Regulation
(a)(1) The collection system shall be effectively maintained and operated at all times to prevent discharge to land or surface
waters and to prevent any contravention of groundwater standards or surface water standards.
Observations: Overall the collection system is maintained well.
Compliant: Compliant
(a)(2) A map of the collection system shall have been developed and shall be maintained.
Observations: Map is effective for overall view of collection system. It consists of line locations and locations of pump
stations, but it does not reference pipe size, pipe material, pipe age or flow direction. They are currently looking into
developing a GIS mapping for facility. Inspector stated GIS will be a tremendous asset to correct map deficiencies and
recommended to expedite the use of GIS.
Complaint: Non -compliant
(a)(3) An operation and maintenance plan, including pump station inspection frequency, preventative maintenance schedule,
spare parts inventory, and overflow response shall have been developed and implemented.
Observations: Inspector is satisfied with O&M plan as it is detailed and comprehensive. Detailed logbooks are kept and
reviewed concerning pump stations and maintenance schedules. Spill response plan was recently updated and satisfactory.
Compliant: Compliant
(a)(4) Pump stations that are not connected to telemetry system shall be inspected by the permittee or its representative
every day, 365 days per year, unless the permittee demonstrates that the daily inspections are not necessary because the
pump station has sufficient storage capacity, above the elevation at which the pump activates, to justify a longer inspection
interval. In no case shall the inspection interval exceed seven days. Pump stations that are connected to a telemetry
system shall be inspected once per week.
Observations: There are 2 simple pump stations in the system. `Main' PS is duplex system and is currently undergoing
rehabilitation which will include installing a telemetry system. Mr. Rowe continually emails inspector updates on progress.
The rehabilitation started after inspection date. The second pump station 'High County' is a simplex system with no
telemetry. As both currently are not connected to a telemetry system, they are inspected daily, multiple times a day.
Compliant: Compliant
(a)(5) High -priority sewers shall be inspected by the permittee or its representative once every six months, and inspections
shall be documented.
Observations: No high priority lines exists in this collection system
Compliant: NA
(a)(6) A general observation by the permittee or its representative of the entire collection system shall be conducted once
per year.
Observations: The overall collection system is inspected by Mr. Rowe and Mr. Spencer on a regular basis throughout the
year with proper documentation of inspections.
Compliant: Compliant
(a)(7) Overflows and bypasses shall be reported to the appropriate Division regional office in accordance with 15A NCAC
02B .0506(a), and public notice shall be provided as required by G.S. 143-215.1 C.
Observations: There have been no SSO's or bypasses reported over the past 3 years with this collection system.
Compliant: Compliant
(a)(8)(B) Grease Control Program shall be in place for private owned collection systems that will include bi-annual
Page 2 of 6
Permit: WQCSD0238 Owner - Facility:Tweetsie Railroad
Inspection Date: 02/15/2022
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
distribution of grease education materials to users of the collection system by the permittee or representative.
Observations: There was no grease control program observed at the time of inspection. Inspector explained this need to be
implemented to comply with regulations of the deemed system. The facility contains 5 restaurants/dining areas.
Compliant: Non -compliant
(a)(9) Right-of-ways and easements shall be maintained in the full easement width for personnel and equipment
accessibility.
Observations: There are no ROW's within the collection system.
Compliant: NA
(a)(10) Documentation of compliance with Subparagraphs (a)(1) through (a)(9) of this Rule shall be maintained by the
collection system owner for three years with the exception of the map, which shall be maintained for the life of the system.
Observations: All documentation, with the exception of (a)(8)(B) `grease control program', are maintained in appropriate time
frame.
Compliant: Compliant
Special note concerning Main pump station rehabilitation. Mr. Rowe emailed inspector details (from the estimate given by
contractor) of the work being conducted to this pump station. Excerpt from estimate:
"Install control panel rack and excavate force main. Remove existing pumps, meet pump truck onsite to clean wet well and
plug invert. Set up for OSHA permitted Confined Space Entry (CSE). Remove all existing piping and guide rails. Install new
force main piping, check valves and isolation valves. Set new pump bases and install new guide rails. Reconnect existing
pumps and install new float brackets. Wire in new floats and test for leaks. Mount existing control panel to new panel rack.
Reuse existing junction box for incoming power only. Install conduit from control panel to well. Install new concrete lid with
hatch. Install new telemetry -based Mission Unit. Test for proper operation."
Overall, the collection system is very well maintained and operated. The only areas of concern were:
1. Maps need to be updated with proper information (ie: pipe size, material, and flow). By implementing the use of GIS,
this will resolve the issue.
2. No grease control program. With areas on site preparing food, the education of proper grease control procedures is
critical in the overall health of the collection system. This could be in the form of posters in food prep areas detailing proper
disposal of grease material.
Page 3 of 6
Permit: WQCSD0238 Owner - Facility:Tweetsie Railroad
Inspection Date: 02/15/2022
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
General
# Is this system a satellite system?
# If Yes, what is system name or permit number?
Is there a overall sewer system map?
Does the map include:
Pipe sizes
Pipe materials (PVC, DIP, etc)
Pipe location
# Flow direction
# Approximate pipe age
# Pump station ID, location and capacity
# Force main air release valve location & type
# Location of satellite connections
Are system maintenance records maintained?
Comment: See Summary
Grease Control
Is grease/sewer education program documented with req'd customer distribution?
# Are other types of education tools used like websites, booths, special meetings, etc?
If Yes, what are they? (This can reduce mailing to annual.)
See summary
For public systems, is there a Grease Control Program via an ordinance/agreement?
If Yes, does it require grease control devices at applicable locations?
Is the Grease Control Program enforced via periodic inspections/records review?
Is action taken against violators?
Comment: N/A
Spills and Response Action Plan
# Is system free of known points of bypass?
# Have there been any sewer spills in the past 3 years?
If Yes, were they reported to the Division if meeting the reportable criteria?
If applicable, is there documentation of press releases and public notices issued?
Are all spills or sewer related issues/complaints documented?
# Are there repeated overflows/problems (2 or more in 12 months) at same location?
# If Yes, is there a corrective action plan?
Is a Spill Response Action Plan available?
Is a Spill Response Action Plan available for all personnel?
Yes No NA NE
▪ •
• ❑ ❑ ❑
▪ •
▪ •
▪ •
❑•❑ ❑
❑•❑ ❑
❑•❑ ❑
▪ •
▪ •
• ❑ ❑ ❑
Yes No NA NE
❑ • ❑ ❑
❑•❑ ❑
❑ ❑•❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑•❑
Yes No NA NE
• ❑ ❑ ❑
❑•❑ ❑
❑ ❑•❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ • ❑ ❑
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page 4 of 6
Permit: WQCSD0238 Owner - Facility:Tweetsie Railroad
Inspection Date: 02/15/2022
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
Does the plan include:
# 24-hour contact numbers
# Response time
# Equipment list and spare parts inventory
# Access to cleaning equipment
# Access to construction crews, contractors, and/or engineers
# Source of emergency funds
# Site sanitation and cleanup materials
# Post-overflow/spill assessment
Comment: See summary
Inspections
Are adequate maintenance records maintained?
Are pump stations being inspected at the required frequency?
Is at least one complete functionality test conducted weekly per pump station?
Is there a system or plan in place to observe the entire system annually?
Is the annual inspection documented?
# Does the system have any high -priority lines/locations?
Are inspections of HPL documented at least every 6 months?
Are new lines being added to the HPL list when found or created?
Comment: See summary
Lines/Right-of-Ways/Aerial Lines
Please list the Lines/Right of Ways/Aerial Lines Inspected:
See Summary
Are right-of-ways and easements maintained for the full width for access?
If No, give details on temporary access:
None
Is maintenance documented?
Were all areas/lines inspected free of issues?
Comment: None
Pump Stations
Please list the Pump Stations Inspected:
Main (duplex) and Secondary (simplex)
# Number of duplex or larger pump stations in system
# Number of vacuum stations in system
# Number of simplex pump stations in system
# Number of simplex pump stations in system serving more than one building
How many pump/vacuum stations have:
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Yes No NA NE
❑ ❑ • ❑
❑ ❑ • ❑
Yes No NA NE
0
0
Page 5 of 6
Permit: WQCSD0238 Owner - Facility:Tweetsie Railroad
Inspection Date: 02/15/2022
Inspection Type : Collection System Inspect Non Sampling Reason for Visit: Routine
# A two-way "auto polling" communication system (SCADA) installed?
# A simple one-way telemetry/communication system (auto -dialer) installed?
For pump stations inspected:
Are they secure with restricted access?
Were they free of by-pass structures/pipes?
Were wet wells free of excessive grease/debris?
# Do they all have telemetry installed?
Is the telemetry system functional?
Is a 24-hour notification sign posted ?
Does the sign include:
Owner Name?
Pump station identifier?
# Address?
Instructions for notification?
24-hour emergency contact numbers?
Are audio and visual alarms present?
Are audio and visual alarms operable?
# Is there a backup generator or bypass pump connected?
If tested during inspection, did it function properly?
Is the back-up system tested at least bi-annually under normal operating conditions?
# Does it have a dedicated connection for a portable generator?
# Is the owner relying on portable units in the event of a power outage?
# If Yes, is there a distribution plan?
If Yes, what resources (Units/Staff/Vehicles/etc) are included in Plan?
See summary
# Does Permittee have the approved percentage of replacement simplex pumps?
Is recordkeeping of pump station inspection and maintenance program adequate?
Do pump station logs include at a minimum:
Inside and outside cleaning and debris removal?
Inspecting and exercising all valves?
Inspecting and lubricating pumps and other equipment?
Inspecting alarms, telemetry and auxiliary equipment?
Comment: See summary
0
0
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page 6 of 6