Loading...
HomeMy WebLinkAboutWQCSD0004_Compliance Evaluation Inspection_20200225 February 25, 2022 Town of Norlina Attn: Mayor Dwight Pearce PO Box 149 Norlina, NC 27563 Subject: Compliance Evaluation Inspection Norlina Collection System Permit Number WQCSD0004 Warren County Dear Mayor Pearce: On February 22, 2022, Stephanie Goss and Chris Smith of the Division of Water Resources (Division) conducted the subject inspection. The assistance of Blaine Reese, Operator in Responsible Charge (ORC) and Mark Perkinson was appreciated. Below is a list of findings developed from the inspection: 1. The Division’s data system does not list a designated ORC or back-up ORC. Please complete the attached WCPS Operator Designation Form and submit to the Division. 2. The Town of Norlina’s wastewater collection system has approximately 65,800 feet of gravity sewer and 6 duplex pump stations. 3. In 2021, the Town of Norlina cleaned out 8,670 feet of gravity sewer line which is 13% and meets the permit requirements. 4. A Fats, Oil and Grease (FOG) program is implemented and in use. Educational materials are mailed out once a year. Please ensure that educational materials are mailed out twice a year per permit requirements. 5. There have been no SSO’s or bypasses at the Town of Norlina’s collection system since April 9, 2008. 6. All records are kept for over three years as required by the permit. 7. All six of the Town of Norlina’s pump stations were inspected: Hilltop Oaks, Pines, Shaw Road, King Drive, Lagoon and Elm Street. All six pump stations have identification signs, secured access, appeared in good condition and were free of excess debris. All audible and DocuSign Envelope ID: DE48EC0E-8F56-4554-982D-5227A8619F2A Page | 2 visual alarms functioned when the high-water floats were activated except for the Lagoon Pump Station. The visual alarm was not functioning. A logbook for each pump station was available to view during the inspection. Elm Street is the only pump station to have a generator on-site. The generator did not operate successfully as the battery was dead which starts up the generator then it is powered by natural gas. 8. There are no high priority lines in the collection system. 9. Maintenance logs were reviewed and appeared satisfactory. 10. An up-to-date map of the collection system was available in paper copy and in a pdf version which can be edited as needed. If you have any questions concerning this report, please contact Stephanie Goss at 919-791-4256 or by e-mail at stephanie.goss@ncdenr.gov. Sincerely, Vanessa E. Manuel, Assistant Regional Supervisor Water Quality Regional Operations Section Raleigh Regional Office Division of Water Resources, NCDEQ Attachment: ORC Designation Form cc: Laserfiche DocuSign Envelope ID: DE48EC0E-8F56-4554-982D-5227A8619F2A Compliance Inspection Report Permit:WQCSD0004 Effective:03/01/00 Expiration:Owner :Town of Norlina SOC: Contact Person: Region: County: Directions to Facility: Warren Raleigh Dwight Pearce Effective:Expiration:Facility:Norlina Town Collection System Title:Phone:252-456-3325 Secondary ORC(s): Phone:Certification:Primary ORC: CS1,System Classifications: On-Site Representative(s): Related Permits: Secondary Inspector(s): Primary Inspector: Inspection Date:Exit Time:Entry Time: Phone: 02/22/2022 09:30AM 12:30PM Stephanie Goss 919-791-4200 Chris Smith Facility Status: Permit Inspection Type: Reason for Inspection:Inspection Type: Not CompliantCompliant Routine Deemed permitted collection system management and operation Collection System Inspect Non Sampling Question Areas: Miscellaneous Questions General Grease Control Inspections Lines Pump Stations (See attachment summary) Page 1 of 5 2/25/2022 DocuSign Envelope ID: DE48EC0E-8F56-4554-982D-5227A8619F2A Inspection Date: Permit: Inspection Type : Owner - Facility: Reason for Visit: WQCSD0004 02/22/2022 Collection System Inspect Non Sampling Town of Norlina Routine Inspection Summary: Page 2 of 5 DocuSign Envelope ID: DE48EC0E-8F56-4554-982D-5227A8619F2A Inspection Date: Permit: Inspection Type : Owner - Facility: Reason for Visit: WQCSD0004 02/22/2022 Collection System Inspect Non Sampling Town of Norlina Routine General Yes No NA NE # Is this system a satellite system? # If Yes, what is system name or permit number?. Is there a overall sewer system map? Does the map include: Pipe sizes Pipe materials (PVC, DIP, etc) Pipe location # Flow direction # Approximate pipe age # Pump station ID, location and capacity # Force main air release valve location & type # Location of satellite connections Are system maintenance records maintained? .Comment: Grease Control Yes No NA NE Is grease/sewer education program documented with req'd customer distribution? # Are other types of education tools used like websites, booths, special meetings, etc? If Yes, what are they? (This can reduce mailing to annual.) The Town of Norlina is distributing materials once a year. It is required to be distributed 2x a year. For public systems, is there a Grease Control Program via an ordinance/agreement? If Yes, does it require grease control devices at applicable locations? Is the Grease Control Program enforced via periodic inspections/records review? Is action taken against violators? .Comment: Inspections Yes No NA NE Are adequate maintenance records maintained? Are pump stations being inspected at the required frequency? Is at least one complete functionality test conducted weekly per pump station? Is there a system or plan in place to observe the entire system annually? Is the annual inspection documented? # Does the system have any high-priority lines/locations? Are inspections of HPL documented at least every 6 months? Are new lines being added to the HPL list when found or created? .Comment: Page 3 of 5 DocuSign Envelope ID: DE48EC0E-8F56-4554-982D-5227A8619F2A Inspection Date: Permit: Inspection Type : Owner - Facility: Reason for Visit: WQCSD0004 02/22/2022 Collection System Inspect Non Sampling Town of Norlina Routine Lines/Right-of-Ways/Aerial Lines Yes No NA NE Please list the Lines/Right of Ways/Aerial Lines Inspected: . Are right-of-ways and easements maintained for the full width for access? If No, give details on temporary access: . Is maintenance documented? Were all areas/lines inspected free of issues? .Comment: Pump Stations Yes No NA NE Please list the Pump Stations Inspected: All six of the Town of Norlina’s pump stations were inspected: Hilltop Oaks, Pines, Shaw Road, King Drive, Lagoon and Elm Street. All six pump stations have identification signs, secured access, appeared in good condition and were free of excess debris. All audible and visual alarms functioned when the high-water floats were activated except for the Lagoon Pump Station. The light was not functioning. A logbook for each pump station was available to view during the inspection. Elm Street is the only pump station to have a generator on-site. The generator did not operate successfully as the battery was dead which starts the generator. # Number of duplex or larger pump stations in system 6 # Number of vacuum stations in system 0 # Number of simplex pump stations in system 0 # Number of simplex pump stations in system serving more than one building 0 How many pump/vacuum stations have: # A two-way "auto polling" communication system (SCADA) installed?0 # A simple one-way telemetry/communication system (auto-dialer) installed?0 For pump stations inspected: Are they secure with restricted access? Were they free of by-pass structures/pipes? Were wet wells free of excessive grease/debris? # Do they all have telemetry installed? Is the telemetry system functional? Is a 24-hour notification sign posted ? Does the sign include: Owner Name? Pump station identifier? # Address? Instructions for notification? 24-hour emergency contact numbers? Are audio and visual alarms present? Are audio and visual alarms operable? Page 4 of 5 DocuSign Envelope ID: DE48EC0E-8F56-4554-982D-5227A8619F2A Inspection Date: Permit: Inspection Type : Owner - Facility: Reason for Visit: WQCSD0004 02/22/2022 Collection System Inspect Non Sampling Town of Norlina Routine # Is there a backup generator or bypass pump connected? If tested during inspection, did it function properly? Is the back-up system tested at least bi-annually under normal operating conditions? # Does it have a dedicated connection for a portable generator? # Is the owner relying on portable units in the event of a power outage? # If Yes, is there a distribution plan? If Yes, what resources (Units/Staff/Vehicles/etc) are included in Plan? . # Does Permittee have the approved percentage of replacement simplex pumps? Is recordkeeping of pump station inspection and maintenance program adequate? Do pump station logs include at a minimum: Inside and outside cleaning and debris removal? Inspecting and exercising all valves? Inspecting and lubricating pumps and other equipment? Inspecting alarms, telemetry and auxiliary equipment? .Comment: Page 5 of 5 DocuSign Envelope ID: DE48EC0E-8F56-4554-982D-5227A8619F2A