HomeMy WebLinkAboutWQ0016165_Compliance Inspection_20220222R.OY COOPER.
Governor
ELIZABETH S. BISER
Secretary
S. DANIEL SMITH
Director
NORTH CAROLINA
Environmental Quality
February 22, 2022
Tom Johnson, Water Resources Superintendent
City of Lexington
28 West Center Street
Lexington, North Carolina 27292
SUBJECT: Compliance Evaluation Inspection
City of Lexington WWI
Wastewater Irrigation System
Davidson County
Dear Mr. Jones:
On February 17, 2022, Division of Water Resources staff Caitlin Caudle conducted a
scheduled compliance inspection and permitting visit. Steve Craver and Jeff Walser were
present during the entire inspection. A review of records, irrigation fields, and pumping
equipment was completed. This review reflected compliance with the subject permit.
Please reference the attached inspection report for additional comments and
observations. If you have any questions please contact me or Caitlin Caudle at the
letterhead address or phone number, or by email at lon.sniderncdenr.gov or
caitlin.caudle(a�ncdenr.gov.
Sincerely,
DocuSigned by:<
C1. Jn,lhts-
145B49E225C94EA...
Lon T. Snider, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ — WSRO
Enc: Inspection Report
Cc: Steve Craver, Plant Superintendent (Electronic Copy)
Davidson County Environmental Health (Electronic Copy)
WSRO Electronic Files
Laserfiche File WQ0016165
NORTH
D E
Department of Envimnmomni au.i`
North Carolina Department of Environmental Quality Division of Water Resources
Winston-Salem Regional Office 1450 West Hanes Mill Road, Suite 300 I Winston-Salem, North Carolina 27105
336.776.9800
Compliance Inspection Report
Permit: WQ0016165 Effective: 07/02/18 Expiration: 07/31/22 Owner : City of Lexington
SOC: Effective: Expiration: Facility: City of Lexington WWIS
County: Davidson 500 Glendale Rd
Region: Winston-Salem
Contact Person: Tom Johnson
Lexington NC 27292
Title: Phone: 336-248-3926
Directions to Facility:
from 1-85 N go 3.1 mi, take exit #91 go 0.2 mi, turn left on Cotton Grove Rd. go 0.4 mi, turn left on Glendale Rd. go 0.8 mi, arrive at
the site on the left.
System Classifications: SI,
Primary ORC: Certification: Phone:
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
NC0055786 City of Lexington - Lexington Regional WWTP
Inspection Date: 02/17/2022
Entry Time 10:04AM Exit Time: 11:40AM
Primary Inspector: Caitlin Caudle Phone: 336-776-9699
Secondary Inspector(s):
Reason for Inspection: Routine Inspection Type: Compliance Evaluation
Permit Inspection Type: Wastewater Irrigation
Facility Status: Compliant ❑ Not Compliant
Question Areas:
Miscellaneous Questions Record Keeping End Use -Irrigation
(See attachment summary)
Page 1 of 4
Permit: WQ0016165 Owner - Facility: City of Lexington
Inspection Date: 02/17/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Inspection Summary:
On February 17, 2022, DWR staff person Caitlin Caudle conducted a scheduled compliance inspection and permitting visit
Steve Craver and Jeff Walser were present during the entire inspection. A review of records, irrigation fields, and pumping
equipment was completed. This review reflected compliance with the subject permit.
The treatment plant was not inspected.
The following observations were made:
• Irrigation equipment has not been calibrated this permit cycle. A new meter was installed in 2013 and it appeared a
calibration check was completed on June 14, 2017. A new permit was issued on July 2, 2018, after a permit modification
request. Mr. Craver stated that a new effluent flow meter will be purchased.
• Influent is measured at the head of the treatment plant, and effluent is measured using a flow meter on the irrigation
pump.
• There is no effluent storage at this facility. The treatment plant also has a discharge permit and a compost facility.
Irrigation is not the primary disposal manner. Irrigation is only completed after the "reuse pump" has been turned off.
• Irrigation is completed when weather allows and when the 12 month floating total allows it. The system is winterized
from approximately November to April. Irrigation was initiated in April of last year and stopped at the end of October.
• Irrigation is 100% manual. A separate pump must be turned off and the irrigation pump turned on. There is not a wet
well. The irrigation pump is located after the chlorine contact chamber.
• Some of the irrigation field perimeter has public access restricted, but Mr. Craver stated they will be adding additional
signage.
• Some I&I is present in the collection system.
• 9,000 GPD was determined based on the 30 in/yr irrigation limit.
• The Operation and Maintenance Plan and Spill Plan are tied into the NPDES permit. Ms. Caudle requested that some
language be added to the Spill Plan concerning emergencies in the irrigation field. Mr. Craver stated that something will be
posted in the building with the irrigation control panel.
• All residuals from the treatment plant are composted.
• The influent flow meter is calibrated quarterly.
• There are no high water alarms related to the irrigation pump as there is not a wet well or any storage.
• Domestic wastewater accounts for 42% of the permitted flow and industrial wastewater accounts for 3% of the permitted
flow.
• The chlorine contact chamber will be reviewed during the next inspection.
Page 2 of 4
Permit: WQ0016165 Owner - Facility: City of Lexington
Inspection Date: 02/17/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
Type
Reuse (Quality)
Infiltration System
Lagoon Spray, LR
Single Family Spray, LR
Activated Sludge Spray, LR
Activated Sludge Spray, HR
Activated Sludge Drip, LR
Recycle/Reuse
Single Family Drip
Record Keeping
Is a copy of current permit available?
Are monitoring reports present: NDMR?
NDAR?
Are flow rates less than of permitted flow?
Are flow rates less than of permitted flow?
Are application rates adhered to?
Is GW monitoring being conducted, if required (GW-59s submitted)?
Are all samples analyzed for all required parameters?
Are there any 2L GW quality violations?
Is GW-59A certification form completed for facility?
Is effluent sampled for same parameters as GW?
Do effluent concentrations exceed GW standards?
Are annual soil reports available?
# Are PAN records required?
# Did last soil report indicate a need for lime?
If so, has it been applied?
Are operational logs present?
Are lab sheets available for review?
Do lab sheets support data reported on NDMR?
Do lab sheets support data reported on GW-59s?
Are Operational and Maintenance records present?
Were Operational and Maintenance records complete?
Has permittee been free of public complaints in last 12 months?
Is a copy of the SOC readily available?
Yes No NA NE
El
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ • ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page 3 of 4
Permit: WQ0016165 Owner - Facility: City of Lexington
Inspection Date: 02/17/2022 Inspection Type : Compliance Evaluation
Reason for Visit: Routine
No treatment units bypassed since last inspection?
Comment: No lime was needed.
End Use -Irrigation
Are buffers adequate?
Is the cover crop type specified in permit?
Is the crop cover acceptable?
Is the site condition adequate?
Is the site free of runoff / ponding?
Is the acreage specified in the permit being utilized?
Is the application equipment present?
Is the application equipment operational?
Is the disposal field free of limiting slopes?
Is access restricted and/or signs posted during active site use?
Are any supply wells within the CB?
Are any supply wells within 250' of the CB?
How close is the closest water supply well?
Is municipal water available in the area?
# Info only: Does the permit call for monitoring wells?
Are GW monitoring wells located properly w/ respect to RB and CB?
Are GW monitoring wells properly constructed, including screened interval?
Are monitoring wells damaged?
Comment: Monitoring wells are not requried by the permit.
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ • ❑ ❑
❑ • ❑ ❑
❑ ❑ ❑ •
❑ • ❑ ❑
❑ ❑ • ❑
❑ ❑ • ❑
❑ ❑ • ❑
Page 4 of 4