HomeMy WebLinkAboutNC0074772_Compliance Evaluation Inspection_20220127ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
S. DANIEL SMITH
Director
Shannon Becker, President
Aqua North Carolina, Inc.
202 MacKenan Court
Cary, North Carolina 27511
Dear Mr. Becker:
NORTH CAROLINA
Environmental Quality
January 27, 2022
Subject: Compliance Evaluation Inspection
Diamond Head WWTP
NPDES Permit No. NC0074772
Iredell County
Enclosed is a copy of the Compliance Evaluation Inspection (CEI) Report for the inspection conducted at the subject
facility on January 13, 2022, by Mr. Wes Bell of this Office. Please advise the facility's Operator -in -Responsible Charge
(ORC) of our findings by forwarding a copy of the enclosed report.
Should you have any questions concerning this report, please do not hesitate to contact Mr. Bell at (704) 235-2192,
or via email at wes.bell@ncdenr.gov.
Enclosure: Inspection Report
NORTH
Deparlmant of Environmental Ouallt
Sincerely,
DocuSigned by:
A w H 1%.1444.
F161 FB69A2D84A3...
fo r
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
North Carolina Department of Environmental Quality 1 Division of Water Resources
Mooresville Regional Office 1610 East Center Avenue, Suite 301 I Mooresville, North Carolina 28115
704.663.1699
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code
1 IN I 2 I5
21IIIIII
NPDES yr/mo/day Inspection
I 3 I NC0074772 111 121 22/01/13 117
Type
18110
IIIIIIIIIII
Inspector Fac Type
19 I S I 201
IIIIIIIIIIIIIIIIII I IIIIII
P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
67I2.0 I 70I4 I 71IN I 72 I N I 731 I 74 751
I I 1
I I I I I I 180
l
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Diamond Head WWTP
NCSR 1109
Mooresville NC 28115
Entry Time/Date
09:56AM 22/01/13
Permit Effective Date
21/07/01
Exit Time/Date
11:03AM 22/01/13
Permit Expiration Date
25/03/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Dustin Joseph Dillard/ORC/828-261-6459/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Shannon V Becker,202 Mackenan Dr Cary NC 275116447/President/919-653-5570/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s)
Wes Bell
of Inspector(s) Agency/Office/Phone and Fax Numbers Date
—Docusigned by: DWR/MRO WQ/704-663-1699 Ext.2192/ 1/26/2022
144- Bat
"-A61696D90CC3437...
Signature of Manag QtfuAiReWknwer Agency/Office/Phone and Fax Numbers Date
Andrew Pitner 4444 H P1 WN/MRO WQ/704-663-1699 Ext.2180/ 1. 27.22
F161FB69A2D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
NPDES yr/mo/day
31 NC0074772 111 121 22/01/13
I17
Inspection Type
18 [j
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Page# 2
Permit: NC0074772
Inspection Date: 01/13/2022
Owner - Facility: Diamond Head WWTP
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ ❑
application?
Is the facility as described in the permit? • ❑ El El
# Are there any special conditions for the permit? • ❑ ❑ ❑
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment: The last compliance evaluation inspection at this facility was performed by DWR staff
on 8/1/19.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
•
• ❑ ❑ ❑
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Page# 3
Permit: NC0074772
Inspection Date: 01/13/2022
Owner - Facility: Diamond Head WWTP
Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Comment: The records reviewed during the inspection were organized and well maintained.
Discharge monitoring reports (eDMRs) were reviewed for the period December 2020
through November 2021. No effluent limit and/or monitoring violations were reported.
If the introduction of off -site wastewater does not occur within a given quarter, then the
ORC must ensure to note this in the eDMR's Comments Section when the effluent
quarterly samples are collected [Permit Condition Reference: Part 1, Section A(1)
footnote #5]. All applicable eDMRs for 2021 should be revised and resubmitted to
include this statement (if applicable).
The ORC must ensure all process control measurements (settleability tests, MLSS
measurements, etc.) are documented as required by 15A NCAC 2B .0506 (c)(3) and
subject NPDES Permit.
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Comment: On -site effluent field analyses (dissolved oxygen, pH, temperature and total residual
chlorine) are performed under the Aqua N.C.'s field laboratory certification #5035.
Water Tech Labs and Meritech, Inc. (subcontracted — chronic toxicity) have been
contracted to provide analytical support.
The ORC must ensure to report all effluent total residual chlorine (TRC) values down
to the lowest standard verified (15 ug/L) on the TRC meter (annual five -point curve
verification).
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? • ❑ ❑ ❑
Is sample collected below all treatment units? • ❑ ❑ ❑
Is proper volume collected? ■ ❑ ❑ ❑
Is the tubing clean? ■ ❑ ❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 • ❑ ❑ ❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • ❑ ❑ ❑
representative)?
Comment: The subject permit requires effluent composite and grab samples. The ORC must
ensure to perform and document monthly (at a minimum) sampler aliquot verifications.
Operations & Maintenance Yes No NA NE
Page# 4
Permit: NC0074772
Inspection Date: 01/13/2022
Owner - Facility: Diamond Head WWTP
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable MODE
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: The ORC had pumped out the mud well (prior to the site inspection) and surcharged
the WWTP with wastewater solids. Wastewater solids were observed in the clarifier
effluent, chlorination, filtration and dechlorination treatment processes. The effluent
also appeared turbid with suspended solids. The ORC immediately backwashed the
filters and stopped the discharge. Prior to the end of the inspection, settling in the
clarifier improved with a clear effluent and the WWTP was returning to proper
wastewater treatment. The ORC must ensure that the WWTP is properly operated at
all times.
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Yes No NA NE
Comment: Screenings are transported and disposed into the dumpster located at the Hwy.
150/River Park WWTP. The dumpster contents are disposed at a permitted landfill.
Equalization Basins
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The telemetry type alarm system (high water) was operational during the on -site test.
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Page# 5
Permit: NC0074772
Inspection Date: 01/13/2022
Owner - Facility: Diamond Head WWTP
Inspection Type: Compliance Evaluation
Aeration Basins Yes No NA NE
Is the basin free of dead spots? • ❑ ❑ ❑
Are surface aerators and mixers operational? ❑ El • El
Are the diffusers operational? • ❑ ❑ ❑
Is the foam the proper color for the treatment process? • ❑ ❑ ❑
Does the foam cover less than 25% of the basin's surface? • ❑ ❑ ❑
Is the DO level acceptable? • ❑ ❑ ❑
Is the DO level acceptable?(1.0 to 3.0 mg/I) • ❑ ❑ ❑
Comment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • ❑ El El
Is the site free of excessive buildup of solids in center well of circular clarifier? El El • El
Are weirs level? • El ❑ ❑
Is the site free of weir blockage? ■ El El El
Is the site free of evidence of short-circuiting? ■ ❑ El El
Is scum removal adequate? • El El El
Is the site free of excessive floating sludge? • El ❑ ❑
Is the drive unit operational? El El • El
Is the return rate acceptable (low turbulence)? ■ ❑ El El
Is the overflow clear of excessive solids/pin floc? • El El El
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) • El ❑ ❑
Comment: The ORC should reduce the buildup of wastewater solids in the clarifier scum trough
within the near future.
Disinfection -Tablet
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Number of tubes in use?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Comment: Calcium hvpochlorite tablets were used for disinfection.
Yes No NA NE
5
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 6
Permit: NC0074772
Inspection Date: 01/13/2022
Owner - Facility: Diamond Head WWTP
Inspection Type: Compliance Evaluation
Filtration (High Rate Tertiary)
Type of operation:
Is the filter media present?
Is the filter surface free of clogging?
Is the filter free of growth?
Is the air scour operational?
Is the scouring acceptable?
Is the clear well free of excessive solids and filter media?
Comment:
De -chlorination
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment: Sodium Sulfite tablets were used for dechlorination.
dechlorination.
Yes No NA NE
Down flow
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
Tablet
❑ ❑ • ❑
❑ ❑ • ❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
4
Post aeration is provided following
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The flow meter is calibrated annually and was last calibrated by Aqua NC staff on
7/14/21.
Pump Station - Effluent
Is the pump wet well free of bypass lines or structures?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Yes No NA NE
• ❑ ❑ ❑
▪ El El El
• ❑ ❑ ❑
Page# 7
Permit: NC0074772
Inspection Date: 01/13/2022
Owner - Facility: Diamond Head WWTP
Inspection Type: Compliance Evaluation
Pump Station - Effluent
Is SCADA telemetry available and operational?
Is audible and visual alarm available and operational?
Comment:
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Yes No NA NE
II El El El
Yes No NA NE
❑ ❑ ❑ •
Comment: The effluent appeared turbid with suspended solids prior to stopping the discharge.
The effluent is discharged (via submerged outfall) into the receiving stream.
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: Wastewater solids are removed by a contracted company (Lake Norman Sewer &
Septic Services).
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The backup generator is exercised (automatically) weekly and tested under load
monthly. Managed Generator Services has been contracted to service the generator
quarterly.
Page# 8