January 25, 2022
SUBJECT: Compliance Evaluation Inspection
Elkin Feed Mill
NPDES Permit Number NCG500229
Surry County
Dear Mr. Payne:
Mr. Ron Boone, of the NC Division of Water Resources (NCDWR), Winston-Salem Regional
Office (WSRO), conducted a compliance evaluation inspection of the Central Care, Inc.,
wastewater treatment plant, on January 19, 2022. Mr. Boone met with you and the ORC, Cliff
Cain. Your assistance and cooperation was greatly appreciated. Inspection findings are detailed in
the attached Water Compliance Inspection Report and summarized below.
This inspection was prompted in part due to several notices and assessments that DWR recently
issued against Central Care, Inc., for effluent temperature monitoring violations. The permit
currently requires daily effluent temperature monitoring and many violations of this requirement
have recently occurred. Therefore, many monitoring violations have accumulated and appropriate
enforcement documentation issued. During the inspection you and Mr. Cain inquired further about
getting the monitoring frequency reduced.
After consulting with DWR's NPDES Unit post -inspection, it was determined that you may
request a minor permit modification to change the effluent temperature monitoring requirement
from daily to weekly. Whether such a modification would be granted depends primarily on the
enforcement history of the facility. If you wish to request the modification, please do so by sending
correspondence to me, at this office, expressing your desire to do so. We will then begin the
evaluation process.
During the inspection the plant appeared to be well maintained and in good condition. The effluent
appeared clear and free of solids with no odor or any other signs of being poor quality. The
receiving stream looked excellent and unaffected by the effluent. All required documentation was
readily available, complete, and current. No other deficiencies, concerns, or violations were noted
during the inspection.
NORTH
D E
D.o.rtm.m of ln.im.mo.t.i Ou.i`
North Carolina Department of Environmental Quality Division of Water Resources
Winston-Salem Regional Office 1450 West Hanes Mill Road, Suite 300 I Winston-Salem, North Carolina 27105
336.776.9800
Please be aware that the Division may take enforcement action against any permittee who fails to
comply with any requirement of their permit. Pursuant to NC General Statute (NCGS) 143-215.6A,
a civil penalty of not more than twenty-five thousand dollars ($25,000.00) may be assessed against
any person who violates or fails to act in accordance with the terms, conditions, or requirements
of any permit issued pursuant to G.S. 143-215.1.
If you have any questions or concerns, please do not hesitate to contact Mr. Boone by phone at
336-776-9690, or by email at ron.boone@ncdenr.gov. Thank you in advance for your time and
attention to this matter.
Attachments:
1. Water Compliance Inspection Report
cc: 1. Laserfiche
LD_E
NORTH CAROLINA
Department of Environmental quaky
Sincerely,
. DocuSigned by:
L_ l . Jn.l0.CT
`— 145B49E225C94EA...
Lon T. Snider, Regional Supervisor
Water Quality Regional Operations Section
Winston-Salem Regional Office
Division of Water Resources, NCDEQ
North Carolina Department of Environmental Quality j Division of Water Resources
Winston-Salem Regional Office 1450 West Hanes Mill Road, Suite 300 I Winston-Salem, North Carolina 27105
336.776.9800
United States Environmental Protection Agency
E PA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction
1 IN
Code
I 2
IL
NPDES yr/mo/day Inspection Type Inspector Fac
I 3 I NC0038822 111 121 22/01/19 117 18 1 19 I S I 201
Type
21IIIIII
IIIIIIIIIII
IIIIIII
I
IIIIII
IIIIIIIIIII
P6
Inspection
671
Work Days
Facility Self -Monitoring
I 70I
Evaluation Rating
I 711
B1
1
72
QA
I N I
731
I
I I
Reserved
74 71
I
I I
I
I
I
180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES oermit Number)
Central Care WWTP
139 Apex Ln
Mount Airy NC 27030
Entry Time/Date
02:OOPM 22/01/19
Permit Effective Date
19/04/01
Exit Time/Date
03:OOPM 22/01/19
Permit Expiration Date
24/02/29
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Clifford Curtis Cain/ORC/336-996-2841/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
David Payne,139 Apex Ln Mount Airy NC 27030//336-320-2185/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Ron Boone DWR/WSRO WQ/336-776-9690/
1- DocuSigned by:
or�.aet Boo.u� 1/25/2022
B2UF
Signature
i5UUSF 2A:i4(iU...
of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
rDocuSigned by:
t- T. '5A,ae.r.
145B49E225C94EA...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
sI
NPDES yr/mo/day
NC0038822 111 121 22/01/19
117
Inspection Type
18 [j
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Mr. Ron Boone, of the NC Division of Water Resources (NCDWR), Winston-Salem Regional Office
(WSRO), conducted a compliance evaluation inspection of the Central Care, Inc., wastewater
treatment plant, on January 19, 2022. Mr. Boone met with you and the ORC, Cliff Cain. Your
assistance and cooperation was greatly appreciated. Inspection findings are detailed in the attached
Water Compliance Inspection Report and summarized below.
This inspection was prompted in part due to several notices and assessments that DWR recently
issued against Central Care, Inc., for effluent temperature monitoring violations. The permit currently
requires daily effluent temperature monitoring and many violations of this requirement have recently
occurred. Therefore, many monitoring violations have accumulated and appropriate enforcement
documentation issued. During the inspection you and Mr. Cain inquired further about getting the
monitoring frequency reduced.
After consulting with DWR's NPDES Unit post -inspection, it was determined that you may request a
minor permit modification to change the effluent temperature monitoring requirement from daily to
weekly. Whether such a modification would be granted depends primarily on the enforcement history
of the facility. If you wish to request the modification, please do so by sending correspondence to me,
at this office, expressing your desire to do so. We will then begin the evaluation process.
During the inspection the plant appeared to be well maintained and in good condition. The effluent
appeared clear and free of solids with no odor or any other signs of being poor quality. The receiving
stream looked excellent and unaffected by the effluent. All required documentation was readily
available, complete, and current. No other deficiencies, concerns, or violations were noted during the
inspection.
Page# 2
Permit: NC0038822
Inspection Date: 01/19/2022
Owner - Facility: Central Care WWTP
Inspection Type: Compliance Evaluation
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
•
•
•
•
• ❑ ❑ ❑
• ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Comment: The permittee has recently received several NOV/NOI letters, as well as assessments,
for effluent temperature monitoring violations. The permit currently requires daily
effluent temperature monitoring of the effluent but the owner does NOT pay the
operators to take the daily temperature readings, therefore resulting in the violation
notices and assessments.
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new El ❑ ❑
application?
Is the facility as described in the permit? • ❑ ❑ ❑
# Are there any special conditions for the permit? El • El El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? ■ El El El
Comment: None
Page# 3
Permit: NC0038822
Inspection Date: 01/19/2022
Owner - Facility: Central Care WWTP
Inspection Type: Compliance Evaluation
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Comment: None
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ ❑ •
❑ ❑ ❑ •
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? ❑ ❑ • ❑
Is sample collected below all treatment units? • ❑ ❑ ❑
Is proper volume collected? ■ ❑ ❑ ❑
Is the tubing clean? ❑ ❑ • ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 ❑ ❑ ❑ •
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type ❑ • ❑ ❑
representative)?
Comment: The permittee has recently received several NOV/NOI letters, as well as assessments,
for effluent temperature monitoring violations. The permit currently requires daily
effluent temperature monitoring of the effluent but the owner does NOT pay the
operators to take the daily temperature readings, therefore resulting in the violation
notices and assessments.
Upstream / Downstream Sampling Yes No NA NE
Is the facility sampling performed as required by the permit (frequency, sampling type, ■ ❑ ❑ ❑
and sampling location)?
Comment: None
Flow Measurement - Influent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: The city water meter on the facility is used to report flow volume.
Yes No NA NE
• ❑ ❑ ❑
❑ • ❑ ❑
Page# 4
Permit: NC0038822
Inspection Date: 01/19/2022
Owner - Facility: Central Care WWTP
Inspection Type: Compliance Evaluation
Septic Tank
(If pumps are used) Is an audible and visual alarm operational?
Is septic tank pumped on a schedule?
Are pumps or syphons operating properly?
Are high and low water alarms operating properly?
Comment: Tanks are pumped as needed according to solids levels
Sand Filters (Low rate)
(If pumps are used) Is an audible and visible alarm Present and operational?
Is the distribution box level and watertight?
Is sand filter free of ponding?
Is the sand filter effluent re -circulated at a valid ratio?
# Is the sand filter surface free of algae or excessive vegetation?
# Is the sand filter effluent re -circulated at a valid ratio? (Approximately 3 to 1)
Comment: None
Disinfection -Tablet
Are tablet chlorinators operational?
Are the tablets the proper size and type?
Number of tubes in use?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Yes No NA NE
❑ • ❑ ❑
❑ ❑ • ❑
Yes No NA NE
❑ • ❑ ❑
• ❑ ❑ ❑
❑ • ❑ ❑
Yes No NA NE
❑ ❑ • ❑
• ❑ ❑ ❑
0
❑ ❑ ❑ •
Comment: Chlorine tablets are added to the chlorine contact tank. The operator states this
procedure works better than using the tablet chlorinator.
De -chlorination Yes No NA NE
Type of system ? Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ II El ❑
Is storage appropriate for cylinders? El El • El
# Is de -chlorination substance stored away from chlorine containers? • El ❑ ❑
Are the tablets the proper size and type? • El El El
Comment: None
Are tablet de -chlorinators operational? • ❑ El El
Page# 5
Permit: NC0038822
Inspection Date: 01/19/2022
Owner - Facility: Central Care WWTP
Inspection Type: Compliance Evaluation
De -chlorination Yes No NA NE
Number of tubes in use? 2
Comment: None
Effluent Pipe
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment: None
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: None
Yes No NA NE
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
Page# 6