HomeMy WebLinkAboutNC0068918_Permit (Issuance)_20121102NPDES DOCUMENT SCANNING COVER SHEET
NC0068918
Cedar Hill WWTP
NPDES Permit:
Document Type:
Permit Issuance
Wasteload Allocation
Authorization to Construct (AtC)
Permit Modification
Complete File - Historical
Engineering Alternatives (EAA)
Plan of Action
Instream Assessment (67b)
Speculative Limits
Environmental Assessment (EA)
Permit
History
Document Date:
November 2, 2012
This documerit is printed on reuse paper - ignore any
content on the reN ersce side
Air"A
NCDENR
North Carolina Department of Environment and Natural Resources
Division of Water Quality
Beverly Eaves Perdue Charles Wakild, P.E. Dee Freeman
Governor Director Secretary
November 2, 2012
Mr. Cody S. Jones
P.O. Box 20670
Charleston, South Carolina 29413
Subject: NPDES PERMIT ISSUANCE
Permit Number NC0068918
Cedar Hill WWTP — Class II
Jackson County
Dear Mr. Jones:
Division personnel have reviewed and approved your application for renewal of the subject
permit. Accordingly, we are forwarding the attached final NPDES discharge permit. This permit is
issued pursuant to the requirements of North Carolina General Statute 143-215.1 and the
Memorandum of Agreement between North Carolina and the U.S. Environmental Protection
Agency dated October 15, 2007 (or as subsequently amended).
If any parts, measurement frequencies or sampling requirements contained in this permit are
unacceptable to you, you have the right to an adjudicatory hearing upon written request within
thirty (30) days following receipt of this letter. This request must be in the form of a written
petition, conforming to Chapter 150B of the North Carolina General Statutes, and filed with the
Office of Administrative Hearings (6714 Mail Service Center, Raleigh, North Carolina 27699-
6714). Unless such demand is made, this permit shall be final and binding.
Please take notice that this permit is not transferable. This permit does not affect the legal
requirements to obtain other permits which may be required by the Division of Water Quality or
permits required by the Division of Land Resources, Coastal Area Management Act, or any other
Federal or Local governmental permits which may be required.
If you have any questions or need additional information, please do not hesitate to contact
Maureen Kinney of my staff at (919) 807-6388.
Charles Wakild, P.E.
cc: Central Files
NPDES Unit Files r
Asheville Regional Office
1617 Mall Service Center, Raleigh, North Carolina 27699-1617
Location: 512 N. Salisbury St. Raleigh, North Carolina 27604
Phone: 919-807.63001 FAX: 919-807-6492
Internet: httpJ/portal.ncdenr.orglweblwglhome
One
NorthCarolina
,%I �aaturaaiilj
An Equal Opportunity \ Affirmative Action Employer
Permit NC0068918
STATE OF NORTH CAROLINA
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
DIVISION OF WATER QUALITY
PERMIT
TO DISCHARGE WASTEWATER UNDER THE
NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM
In compliance with the provisions of North Carolina General Statute 143-215.1, other lawful standards
and regulations promulgated and adopted by the North Carolina Environmental Management
Commission, and the Federal Water Pollution Control Act, as amended, the
Cedar Beach Investment Group, LLC
is hereby authorized to discharge wastewater from a facility located at the
Cedar Hill WWTP
US 64 East at Cedar Hill
Jackson County
to receiving waters designated as Horsepasture River in the Savannah River Basin in accordance with
effluent limitations, monitoring requirements, and other conditions set forth in Parts I, II, III and IV
hereof.
This permit shall become effective December 1, 2012.
This permit and authorization to discharge shall expire at midnight on August 31, 2017.
Signed this day November 2, 2012.
Ch. : Wakild, P.E., Director
Di sion of Water Quality
By Authority of the Environmental Management Commission
Permit NC0068918
SUPPLEMENT TO PERMIT COVER SHEET
All previous NPDES Permits issued to this facility, whether for operation or discharge are hereby
revoked. As of this permit issuance, any previously issued permit bearing this number is no longer
effective. Therefore, the exclusive authority to operate and discharge from this facility arises under the
permit conditions, requirements, terms, and provisions included herein.
Cedar Beach Investment Group, LLC is hereby authorized to:
1. Continue to operate an existing 0.10 MGD wastewater treatment facility with the following
components:
• 26,709 gallon aeration
• 8,325 flow equalization
• 5,327 gallon clarifiers
• 4,435 gallon sludge holding
• 800 gallon chlorine contact chamber
• 300 gallon de -chlorine post aeration chamber
• Dual 7.5 hp main plant blowers
• 1.0 hp flow equalization blower
• Flow meter
This facility is located and West of Cedar Hill Road, on Hwy 64 East, Cashiers, in Jackson County.
2. Discharge from said treatment works, through Outfall 001 at the location specified on the attached
map, into the Horsepasture River, currently classified C-Trout waters in sub -basin 03-13-02 of the
Savannah Broad River Basin.
Cedar Beach Investment Group, LLC
Cedar Hill WWTP
Cot___: Jackson Stream Class: C-Trout
Receiving Stream: Horsepasture River Sub -Basin: 03-13-02
Latitude: 35° 08' 03" Grid/Quad: Big Ridge
Longitude: 83° 04' 14" HUG #: 03060101
Facility
Location
(not to scale)
NPDES Permit: NC0068918
Permit NC0068918
A. (1.) EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS
During the period beginning on the effective date of this permit and lasting until expiration, the
Permittee is authorized to discharge from outfall 001. Such discharges shall be limited and monitored
by the Permittee as specified below:
EFFLUENT
CHARACTERISTICS
Parameter Code
LIMITS
REQUIREMENTS
MONITORING
Monthly
Average
Daily
Maximum
Measurement
Frequency
Sample
Type
Sample
Location
Flow
50050
0.10 MGD
Continuous
Recording
Influent or Effluent
BOD, 5-day (20°C)
C0310
30.0 mg/L
45.0 mg/L
Weekly
Composite
Effluent
Total Suspended Solids
C0530
30.0 mg/L
45.0 mg/L
Weekly
Composite
Effluent
NH3 as N —Summer*
C0610
11.0 mg/L
35.0 mg/L
Weekly
Composite
Effluent
NH3 as N —Winter*
C0610
14.0 mg/L
35.0 ug/L
Weekly
Composite
Effluent
Fecal Coliform (geometric mean)
31616
200/100 mL
400/100 mL
Weekly
Grab
Effluent
1
Total Residual Chlorine
50060
28 µg/L
2/Week
Grab
Effluent
Temperature °C
00010
Monitor & Report
Daily
Grab
Effluent
Total Nitrogen (NO2+NO3+TKN)
00600
Monitor & Report
Semi-
Annually
Composite
Effluent
Total Phosphorus
00665
Monitor & Report
Semi-
Annually
Composite
Effluent
pH
00300
Not < 6.0 nor > 9.0
Standard Units
Weekly
Grab
Effluent
*Summer: April 1— October 31
*Winter: November 1— March 31
Footnote:
1. The limit for total residual chlorine is only if chlorine is used for disinfection. The Division shall
consider all effluent TRC values reported below 50 1..tg/1 to be in compliance with the permit.
However, the Permittee shall continue to record and submit all values reported by a North Carolina
certified laboratory (including field certified), even if these values fall below 50 µg/1.
THERE SHALL BE NO DISCHARGE OF FLOATING SOLIDS OR VISIBLE FOAM IN OTHER THAN TRACE AMOUNTS.
1C.)/1c//7_,
ASHEVILLE
ILLS
The Town of Franklin requested renewal of per-
mit N00021547 for Franklin WWTP In Macon
County; this facility discSharge Is treated mu-
nicipai wastewater tb Little Tennessee River,
Little Tennessee River Basin.
Cedar Beach Investment Group LLC, permit
number NC0068918, has applied for renewal of
its permit discharging to the Horsepasture Riv-
er In the Savannah River Basin.
Cullasala Homeowners' Association Inc, has re-
questetld renewal of permit NC0064416 for Culla-
saja Homeowners' Association WWTP Jackson
County. This permitted facility discharges
treated wastewater to Norton Mill Creek. Sa-
vannah River Basin.
PUBLIC NOTICE STATE OF NORTH CAROLINA
ENVIRONMENTAL NU6UINTOPMANAGEMENT
1617 MAIL SERVICE CENTER,
RALEIGH NC 27699-1617
NOTIFICATION OF INTENT TO ISSUE A NPDES
WASTEWATER PERMIT
The North Carolina Environmental Management
Commission proposes to issue a
NPDEwastewatersted discharge permit to the per-
son(s)below.
Written comments regarding the proposed per-
niit wil be accepted until 30 days
after t e publish date of this notice. The Direc-
tor oft a NC Division ofb Water Quality
(DWQ) may hold a public hearing should there
be a slnificant degreof public
interest. Please mail comments and/or infor-
mation requests to DWQ at the above
address. Interested persons may visit the DWQ
at 512 N. Salisbury Street, Raleigh
NC to review information on file. Additional in-
formation on NPDES permits and this
notice may be found an our website: http://-
portal.ncdenr.org/web/wo/swp/ps/npdes/cale
ndaor by calling (919) 807-6304.
August 31, 2012 (9615
CI r 11IZE 1. 11 T • 1 1S
VOICE OF THE MOUNTAINS • CPTIZEN-TIMFS.com
AFFIDAVIT OF PUBLICATION
BUNCOMBE COUNTY
SS.
NORTH CAROLINA
Before the undersigned, a Notary Public of said County and
State, duly commissioned, qualified and authorized by law
to administer oaths, personally appeared Velene Fagan,
who, being first duly sworn, deposes and says: that she is
the Legal Billing Clerk of The Asheville Citizen -Times,
engaged in publication of a newspaper known as The
Asheville Citizen -Times, published, issued, and entered as
first class mail in the City of Asheville, in said County and
State; that she is authorized to make this affidavit and
sworn statement; that the notice or other legal
advertisement, a true copy of which is attached hereto, was
published in The Asheville Citizen -Times on the
following date: August 31st, 2012. And that the said
newspaper in which said notice, paper, document or legal
advertisement was published was, at the time of each. and
every publication, a newspaper meeting all of the
requirements and qualifications of Section 1-597 of the
General Statues of North Carolina and was a qualified
newspaper within the meaning of Section 1-597 of the
General Statues of North Carolina.
Signed this 3151, day of August, 2012
(Signature of person making affiday.
Sworn to and subscrib efore me the 315t, day of August,
2012.
_ r 0e44d4330 lAPC-/OBI
y Co sion expires the 5th day of October, 201za° 1°Y#: ,p'4'°osa
ai
F.
PU B L.IC
'9114BE
Public
(828) 232-5830 I (828) 253-5092 FAX
14 O. HENRY AVE. I P.O. BOX 2090 I ASHEVILLE, NC 28802 I (800) 800-4204
a) GAPNEIT
Kinney, Maureen
From: Cantwell, Janet
Sent: Monday, September 10, 2012 2:35 PM
To: Kinney, Maureen
Cc: Cranford, Chuck; Menzel, Jeff
Subject: Cedar Hill, NC0068918, Jackson Co.
Hi Maureen ---The "standby generator" was not mentioned in the new draft permit; it was on the last permit issued
11/1/07. Limits and frequency remain unchanged.
It looks OK to me.
Thanks ---Janet
Janet Cantwell - Janet.CantwellPncdenr.eov
North Carolina Dept. of Environment and Natural Resources
Asheville Regional Office
Division of Water Quality - Water Quality Section
2090 US Highway 70
Swannanoa, NC 28778-8211
Tel: 828-296-4500
Fax: 828-299-7043
http://portal.ncdenr.org/web/csc/permits
E-mail correspondence to and from this address may be subject to the North Carolina Public Records Law and may be disclosed to
third parties.
1
FACT SHEET FOR EXPEDITED PERMIT RENEWALS
This form must be completed by Permit Writers for all expedited permits which do not require
full Fact Sheets. Expedited permits are generally simple 100% domestics (e.g., schools, mobile
home parks, etc) that can be administratively renewed with minor changes, but can include
facilities with more complex issues (Special Conditions, 303(d) listed water, toxicity testing,
instream monitoring, compliance concerns).
Basic Information for Expedited Permit Renewals
Permit Writer/Date
Maureen Kinney 8/23/12
Permit Number
NC0068918
Facility Name
Cedar Hill WWTP
Basin Name/Sub-basin number
03-13-02
Receiving Stream
Horsepasture River
Stream Classification in Permit
C-Trout
Does permit need Daily Max NH3 limits?
No
Does permit need TRC limits/language?
Yes No Language updated
Does permit have toxicity testing?
Yes No
Does permit have Special Conditions?
Yes No
Does permit have instream monitoring?
Yes No
Is the stream impaired (on 303(d) list)? For
what parameter?
Yes No
Any obvious compliance concerns?
No
Any permit mods since last permit?
No
Current expiration date
8/31/12
New expiration date
8/31/17
Comments received on Draft Permit?
No
Most Commonly Used Expedited Language:
• TRC language for Compliance Level for Cover Letters/Effluent Sheet Footnote:
"The Division shall consider all effluent TRC values reported below 50 µg/L to
be in compliance with the permit. However, the Permittee shall continue to
record and submit all values reported by a North Carolina certified laboratory
(including field certified), even if these values fall below 50 µg/L."
(c)f 1'
C
Cedar Beach Investment Group, LLC
Cody S. Jones
CSJ Realty Advisors, LLC
P.Q. Box 20670
Charleston, S.C. 29413
Phone 843-224-7260
Mrs. Dina Sprinkle
NC DENR / DWQ / Point Source Branch
1617 Mail Service Center
Raleigh, NC 27699-1617
(919) 807-6304
Randolph W. Cooper
Cooper Law Firm, LLC
109 River Landing Dr.
Suite 100-B
Daniel Island, S.C. 29492
Phone 843-881-5413
Fax 843-881-8366
Mrs. Sprinkle, please accept this request to renew NPDES Permit NC0068918 Cedar
Beach Investment Group, LLC, Jackson County.
Since our last approval of renewal October 1, 2007 we have transitioned from a "no
flow" facility to a functioning treatment plant operated by RPB Systems, Inc. of
Asheville, N.C.
Cody S. Jones
843-224-7260
csjchas@gmail.com
PO Box 20670
Charleston, SC 29413
MAY 102012
;'Fr QUALITY
-:CE BRANCH
NPDES APPLICATION - FORM D
For privately owned treatment systems treating 100% domestic wastewaters <1.0 MGD
Mail the complete application to:
N. C. DENR / Division of Water Quality / NPDES Unit
1617 Mail Service Center, Raleigh, NC 27699-1617
NPDES Permit NCOO
/f you ar,; completing this form in computer use the TAB key or the up - down arrows to move from one field '2
the next. To check the boxes, click your mouse on top of the box. Otherwise, please print or type.
1. Contact Information:
Owner Name
Facility Name
Malting Address
City
State / Zip Code
Telephone Number
Fax Number
e-mail Address
CCAo lleAtinINU86TMBKT tovi• L.LC
CQaper wee wivrerThwineferPLA:si
P.O. Box aobno
kftrt.esrost
SouTh coLi'P
14.60
l23610
csicinfls 0
2. Location of facility producing discharge:
Check here if same address as above
Street Address or State Road
City
State / Zip Code
Couri;y
I gao hwy. c3•s. 64 east
C ets
No hit\ t'OLI M v9 k 1! 7
z'AGK5a�
3. Operator Information:
A'an of the firm, public organization or other entity that operates the facility. (Note that this is not referring to the
Operator in Responsible Charge or ORC)
Name
Mailing Address
City
State / Zip Code
Telephone Number
Fax Number
1 of
Form-D 05/08
RP Q sys7ei"5 X'Nc.
P.O. 8aX 30%5'
� shoe u ttte.
/'(�trL't CtcL,,q,4 euoa.
tetoo
4-5
7j(7;b1UME1
0 2012
NPDES APPLICATION - FORM D
For privately owned treatment systems treating 100% domestic wastewaters <1.0 MGD
4. Description of wastewater:
Egcility Generating Wastewater(check a// that apply
I ridustrial
Commercial
Residential
School
Other
Number of Employees
Number of Employees
Number of Homes
Number of Students/Staff
Explain:
l�.
Describe the source(s) of wastewater (example subdivision mobile home park, shopping centers, restaurants,
etc.): r ri 1V1 et e1 L%t se t s of r& NeS t,1 eAT/ * L
Population served:
5. Type of collection system
eparate (sanitary sewer only) is Combined (storm sewer and sanitary sewer)
6. Outfall Information:
Number of separate discharge points
Outfall Identification number(s)
1
!s the outfall equipped with a diffuser? Ei Yes �I�o
7. Name of receiving stream(s) (Provide a map showing the exact location of each outfa//j: AoPcat V e r
�
8. Frequency of Discharge: ra Continuous Intermittent
If intermittent:
Days per week discharge occursAePfol Duration: RQ`p kl .(1 T° DA '$
t4.
-1
9. Describe the treatment system
List all installed components, including capacities, provide design removal for BOD, TSS, nitrogen and
phosphorus If the space provided is not sufficient, attach the description of the treatment system in a separar9
sheet of paper.
2 of Farm-D 05108
NPDES APPLICATION - FORM D
For privately owned treatment systems treating 100% domestic wastewaters <1.0 MGD
10. Flow Information:
Treatment Plant Design flow
Annual Average daily fl
MGD • D a.S Ilu STNUhe4
MGD (for the previous 3 years)
Maximum daily flo t MGD (for the previous 3 years)
11. Is this facility located on Indian country?
11 Yes Flo
12. Effluent Data
Prow* de to for the parameters listed. Fecal Coliform, Temperature and pH shall be grab samp/es, for a// other parameter;
24-hour composite sampling shall be used. If more than one analysis is reported, report daily maximum and monthly aver, e
Ifc:.Iyone analysis is reported, report as daily maximum.
Parameter
Daily
Maximum
Monthly
Average
Units of
Measurement
/
Alb
0
ca. /Asp/am
Biochemical Oxygen Demand (BODS)
17. 15
l A ♦ 35
Fecal Coliform
a51 MO
a • 69
Total Suspended Solids
9.5k
1.0
MI. /I
Temperature (Summer)
/ s' 137
/3 I V O
V G
Temperature (Winter)
pH
4•7
6•6
sr;ichitiUN
13. list all permits, construction approvals and/or applications:
Typn Permit Number Type
Hazardous Waste (RCRA) NESHAPS (CAA)
UIC (DWA) Ocean Dumping (MPRSA)
NPDES JL ( Oodp itt19 Dredge or fill (Section 404 or CWA)
PSD (CAA) Other
Non -attainment program (CAA)
14. APPLICANT CERTIFICATION
Permit Number
s
I certify that I am familiar with the information contained in the application and that to the best of my knowledge
and belief such information is true, complete, and accurate.
Printed name of Person Signinge 44.)
Signature of Applicant
Title
Date
No:`n ::arolina General Statute 143-215.6 (b)(2) states: Any person who knowingly makes any false statement representation, or certification in any
a; ;'.on, record, report, plan, or other document files or required to be maintained under Article 21 or regulations of the Environmental Management
3 Form-D 05/08
Cedar Hill WWTP Description
Phase 1- 25,000 gpd of 1 O0,000 gpd permit consists of
26,709 gallon aeration
8,325 flow equalization
5,327 gallon clarifiers
4,435 gallon sludge holding
800 gallon chlorine contact
300 gallon de -chlorine post aeration chamber
Dual 7.5 hp main plant blowers
1.0 hp flow equalization blower
Flow meter
Sludge Management Plan
The owner contracts with RPB Systems, Inc. of Asheville to maintain the system for
daily OW maintenance, testing, lab sampling, reporting, and sludge management. RPB
Systems, Inc. wastes sludge as needed to the sludge digester. Periodically the sludge is
removed from the site by a sludge hauler. B&B Concrete Products, Inc. is the sludge
header for this facility and will provide the sludge removal and hauling to the Tuckasegee
WWTP in Sylva. B&B Concrete Products, Inc. will dispose of the sludge in an approved
discharge location, pay for all tipping/d fees.
-ro LAJA:,.-ettir: -TILL
cat_
2.00 2-
/9Z c
t- ca-ti v14_,
•
0-L-tufy