HomeMy WebLinkAboutNC0068918_Permit (Issuance)_19970916NPDES DOCWdENT ! CANNINO COVER SHEET
Permit:
NC0068918
Cedar Hill WWTP
NPDES
Document Type: j'
Permit Issuance
Wasteload Allocation
Authorization to Construct (AtC)
Permit Modification
Complete File - Historical
Engineering Alternatives (EAA)
Plan of Action
Instream Assessment (67b)
Speculative Limits
Environmental Assessment (EA)
Permit
History
Document Date:
September 16, 1997
This; document is primtea on reuse paper - ignore any
content on the remrersese ride
State of North Carolina
Department of Environment,
Health and Natural Resources
Division of Water Quality
James B. Hunt, Jr., Governor
Wayne McDevitt, Secretary
A. Preston Howard, Jr., P.E., Director
Mr. Donald H. Parsons, Chairman
Resources Planning Corporation
PO Box 2185
Cashiers, North Carolina 28717
Dear Mr. Parsons:
A.T77A
C)EHNR
September 16, 1997
Subject: NPDES Permit Issuance
Permit No. NC0068918
Cedar Hill Development
Jackson County
In accordance with the application for a discharge permit received March 3, 1997, the Division is
forwarding herewith the subject NPDES permit. This permit is issued pursuant to the requirements of
North Carolina General Statute 143-215.1 and the Memorandum of Agreement between North Carolina
and the US Environmental Protection Agency dated December 6, 1983.
If any parts, measurement frequencies or sampling requirements contained in this permit are
unacceptable to you, you have the right to an adjudicatory hearing upon written request within thirty (30)
days following receipt of this letter. This request must be in the form of a written petition, conforming to
Chapter 150B of the North Carolina General Statutes, and filed with the Office of Administrative
Hearings, Post Office Drawer 27447, Raleigh, North Carolina 27611-7447. Unless such demand is
made, this decision shall be final and binding.
Please take notice this permit is not transferable. Part II, E.4. addresses the requirements to be
followed in case of change in ownership or control of this discharge.
This permit does not affect the legal requirements to obtain other permits which may be required by
the Division of Environmental Water Quality or permits required by the Division of Land Resources,
Coastal Area Management Act or any other Federal or Local governmental permit that may be required.
If you have any questions concerning this permit, please contact Mr. Mack Wiggins at telephone
number (919)733-5083, extension 542.
Sincerely,
Original Signed By
David A. Goodrich
A. Preston Howard, Jr., P.E.
cc: Central Files
Asheville Regional Office/Water Quality Section
Mr. Roosevelt Childress, EPA
NPDES Unit
Point Source Compliance/Enforcement Unit
P.O. Box 29535, Raleigh, North Carolina 27626-0535 Telephone 919-733-5083 FAX 919-733-9919
An Equal Opportunity Affirmative Action Employer 50% recycled/ 10% post -consumer paper
Permit No. NC0068918
STATE OF NORTH CAROLINA
DEPARTMENT OF ENVIRONMENT, HEALTH, AND NATURAL RESOURCES
DIVISION OF WATER QUALITY
PERMIT
TO DISCHARGE WASTEWATER UNDER THE
NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM
In compliance with the provision of North Carolina General Statute 143-215.1, other lawful standards
and regulations promulgated and adopted by the North Carolina Environmental Mangement Commission,
and the Federal Water Pollution Control Act, as amended,
Resources Planning Corporation
is hereby authorized to discharge wastewater from a facility located at
Sleepy Valley
on US Highway 64 County
east of Cashiers
Jackson County
to receiving waters designated as Horsepasture River in the Savannah River Basin
in accordance with effluent limitations, monitoring requirements, and other conditions set forth in Parts I,
II, and III hereof.
The permit shall become effective October 1, 1997
This permit and the authorization to discharge shall expire at midnight on August 31, 2002
Signed this day September 16, 1997
Original Signed By
David A. Goodrich
A. Preston Howard, Jr., P.E.; Director
Division of Water Quality
By Authority of the Environmental Mangement Commission
Permit No. NC0068918
SUPPLEMENT TO PERMIT COVER SHEET
Resource Planning Corporation
is hereby authorized to:
1. After receiving an Authorization to Construct from the Division of Water Quality, construct and
operate a 0.10 wastewater treatment facility located at Sleepy Valley, on U.S. Highway 64, east
of Cashiers, Jackson County (See Part III of this Permit), and
2. Discharge from said treatment works at the location specified on the attached map into
Horsepasture River which is classified Class C-Trout waters in the Savannah River Basin.
•.4. -
4
1
ROAD CLASSIFICATION
PRIMARY HIGHWAY
HARD SURFACE
SECONDARY HIGHWAY
HARD SURFACE Cif
M HY-D-0 D SROADDA HARD
UNIMPROVED ROAD
OWNED
Latitude; 35°08'03" Longitude; 83°04'14"
Map # G6NE Sub -basin 03-13-02
Stream Class C-Trout
Discharge Class Domestic
Receiving Stream Horse Pasture River
Permit exp. 08/31/2002 Ow 0.100 MGD
M0G0-Sleepy Valley
NC0068918
Jackson County
A. (). EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS SUMMER (April 1 - October 31) Permit No. NC0068918
During the period beginning on the effective date of the permit and lasting until expiration, the Permittee is authorized to discharge from
outfall(s) serial number 001. Such discharges shall be limited and monitored by the permittee as specified below:
Effluent Characteristics
Discharge Limitations
Monthly Avg.
Flow 0.100 MGD
BOD, 5 day, 20°C 30.0 m g / I
Total Suspended Residue 30.0 m g / I
NH3 as N 11.0 mg/I
Fecal Coliform (geometric mean) 200 /100 ml
Total Residual Chlorine
Total Nitrogen (NO2 + NO3 + TKN)
Total Phosphorus
Temperature
Weekly Avg.
Daily Max
45.0 m g/I
45.0 mg/l
400 /100 ml
28 pg/I
Monitoring
Measurement
Frequency
Continuous
Weekly
Weekly
Weekly
Weekly
2/Week
Semi-annually
Semi-annually
Daily
Requirements
Sample
Type
Recording
Composite
Composite
Composite
Grab
Grab
Composite
Composite
Grab
*Sample
Location
1 or E
E
E
E
E
E
E
E
E
* Sample locations: E - Effluent, I - Influent, U - Upstream 50 feet from discharge, D - Downstream 50 to 100 feet from discharge.
The pH shall not be less than 6.0 standard units nor greater than 9.0 standard units and shall be monitored weekly at the effluent by grab
sample.
There shall be no discharge of floating solids or visible foam in other than trace amounts.
A. (). EFFLUENT LIMITATIONS AND MONITORING REQUIREMENTS WINTER (November 1 - March 31) Permit No. NC0068918
During the period beginning on the effective date of the permit and lasting until expiration, the Permittee is authorized to discharge from
outfall(s) serial number 001. Such discharges shall be limited and monitored by the permittee as specified below:
Effluent Characteristics
Discharge Limitations
Monthly Avg.
Flow 0.100 MGD
BOD, 5 day, 20°C 30.0 mg/I
Total Suspended Residue 30.0 mg/I
NH3asN 14.0 mg/I
Fecal Coliform (geometric mean) 200 /100 mi
Total Residual Chlorine
Total Nitrogen (NO2 + NO3 + TKN)
Total Phosphorus
Temperature
Weekly Avg. Daily Max
45.0 mg/I
45.0 mg/I
400 /100 ml
28.0 pg/I
Monitoring
Measurement
Frequency
Continuous
Weekly
Weekly
Weekly
Weekly
2/Week
Semi-annually
Semi-annually
Daily
Requirements
Sample
Type
Recording
Composite
Composite
Composite
Grab
Grab
Composite
Composite
Grab
*Sample
Location
1 or E
E
E
E
E
E
E
E
E
* Sample locations: E - Effluent, I - Influent, U - Upstream 50 feet from discharge, D - Downstream 50 to 100 feet from discharge.
The pH shall not be less than 6.0 standard units nor greater than 9.0 standard units and shall be monitored weekly at the effluent by grab
sample.
There shall be no discharge of floating solids or visible foam in other than trace amounts.
Permit Summary
NC0068918
This is a permit renewal for a discharge into Horsepasture River in the
Savannah River Basin. As per the project engineer, the facility has not
been constructed. In 1992 the Division granted an AtoC for a 0.013 MGD
facility and the project was canceled. At this time no AtoC has been granted
to Resource Planning Corporation for construction of a 0.10 MGD facility.
Permits and Engineering will recommend existing limitations with
monitoring reflective of current regulations for a class II facility. If the
Permittee chooses to install ultraviolet disinfection, the chlorine limit
should be removed. Once construction is complete, the region must verify
facility class and components.
io
Staff Review and Evaluation
NPDES Wastewater Permit
FACILITY INFORMATION
Facility Resource Planning Corporation
NPDES No. NC0068918
Design Flow (MGD) 0.10 MGD
Facility Class II
STREAM CHARACTERISTICS
Stream Name Horsepasture River
Stream Class C Tr
Sub -basin 031302
Drainage Area (mi2) 3.8
S7Q10 (cfs) 2.0
W7Q10 (cfs) 1.2
30Q2 (cfs) 4.1
IWC (%) 0.19
Proposed Changes
Parameters Affected
Basis for change(s)
Monitoring frequency
BOD5, TSS, Ammonia, Fecal,
Temperature, Total Residual
Chlorine and pH
per regulation 2B .0500
Limitation
Total Residual Chlorine
per regulation for trout streams
Limitations
Ammonia (Summer)
per mass balance calculation
Compliance Schedule: None
Special Condition(s): None
Permits & Engineering Comments:
This is a permit renewal for a discharge into Horsepasture River in the Savannah River Basin. As per
the project engineer, the facility has not been constructed. In 1992 the Division granted an AtoC for a
0.013 MGD facility and the project was canceled. At this time no AtoC has been granted to Resource
Planning Corporation for construction of a 0.10 MGD facility. Permits and Engineering will recommend
existing limitations with monitoring reflective of current regulations for a class II facility. If the
Permittee chooses to install ultraviolet disinfection, the chlorine limit should be removed. Once
construction is complete, the region must verify facility class and components.
Prepared by:
d( 64
•
Regional Office Evaluation and Recommendations:
NC0068918
Residual Chlorine
7010 (CFS)
DESIGN FLOW (MGD)
DESIGN FLOW (CFS)
STREAM STD (UG/L)
UPS BACKGROUND LEVE
IWC (%)
Allowable Concentration
Fecal Limit
Ratio of 12.9 :1
2
0.1
0.155
17.0
0
7.19
2
v
Ammonia as NH3
(summer)
7Q10 (CFS)
DESIGN FLOW (MGD)
DESIGN FLOW (CFS)
STREAM STD (MG/L)
UPS BACKGROUND LEVI
IWC (%)
Allowable Concentration
Ammonia as NH3
(winter)
2
0.1
0.155
1.0
0.22
7.19
1/- 0
7Q10 (CFS) 1.2
200/100mI DESIGN FLOW (MGD) 0.1
DESIGN FLOW (CFS) 0.155
STREAM STD (MG/L) 1.8
UPS BACKGROUND LEVI 0.22
IWC (%) 11.44
Allowable Concentration--
DATE: April 2, 1997
NPDES STAFF REPORT AND RECOMMENDATION
COUNTY Jackson
PERMIT NUMBER NC0068918
PART I - GENERAL INFORMATION
1. Facility and Address:
2. Date of Investigation:
3. Report Prepared By:
Cedar Hill (Formerly
MOGO Sleepy Valley Development)
Post Office Box 2185
Cashiers, NC 28717
April 2, 1997
W. E. Anderson
4. Persons Contacted and Telephone Number:
Donna Tucker
704-743-2118
5. Directions to Site: From the intersection of US Highway 64 and
NCSR 1120 east of Cashiers, travel east on US Highway 64
approximately 0.1 mi. to Cedar Hill Development on the right.
6. Discharge Point(s), List for all discharge points:
Latitude: 35° 08' 03" Longitude: 83° 04' 14"
Attach a USGS map extract and indicate treatment facility site and
discharge point on map.
U.S.G.S. Quad No. 176-NE(G6NE) U.S.G.S. Quad Name Big Ridge
7. Size (land available for expansion and upgrading): N/A
8. Topography (relationship to flood plain included): Relatively
flat, treatment plant will be above 100 year flood.
9. Location of nearest dwelling: No building construction as yet -
off site houses are greater than 500 feet.
-1-
`.S
. �a}Z�cL.ccs rsai� aacc wcaccrS
•
a. classification: "C-Trout"
b. River Basin and Subbasin No.: Savannah 031302
Horse Pasture River.
c. Describe receiving stream features and pertinent downstream
uses: The Horsepasture River downstream of this discharge
has been classified "B-Trout".
PART II* - DESCRIPTION OF DISCHARGE AND TREATMENT WORKS
1. Type of wastewater: 100 o Domestic
0 o Industrial
a. Volume of Wastewater: 0.10 MGD (Design Capacity)
b. Types and quantities of industrial wastewater: None
c. Prevalent toxic constituents in wastewater: Chlorine
d. Pretreatment Program (POTWs only): N/A
in development
should be required
approved
not needed
2. Production rates (industrial discharges only) in pounds per day:
N/A
a. Highest month in the past 12 months: lbs/day
b. Highest year in the past 5 years: lbs/day
3. Description of industrial process (for industries only) and
applicable CFR Part and Subpart: N/A
4. Type of treatment (specify whether proposed or existing): Proposed
extended aeration.
5. Sludge handling and disposal scheme: Not specified.
6. Treatment plant classification : II
7. SIC Codes (s) : 4952
Wastewater Code(s): Primary 05 Secondary
Main Treatment Unit Code: 050-0
-2-
1_ Is this facility being constructed with Construction Grant funds
(municipals only) ? N/A
2. Special monitoring requests: None
3. Additional effluent limits requests: None
4. Other:
PART IV - EVALUATION AND RECOMMENDATIONS
This is a request for permit renewal and a name change. The
facility has not been constructed, a new Authorization to
Construct should be required. Please add notification of this
requirement to the permit cover letter.
Signature of Report Preparer
4/1 elL1
Water Quality Regi al Supervisor
c�— Z-(1-7
Date
-3-