HomeMy WebLinkAboutNC0065480_Authorization to Construct_20060330NPDES DOCUI ENT SCANNINO COVER SHEET
NC0065480
Beau Rivage WWTP
NPDES Permit:
Document Type:
Permit Issuance
Wasteload Allocation
};..-: ,r.•L.",:.'_':::-Y.,MF• i.:r,k!:iirCd2l:h i.: t+.. Y-., .
c,,„
Authorization to Construct
(AtC)
nA-S3-n'a .:.-t`c..ri i:dN"dT::>iT.i!Y:..; }.i ✓'...i::°..: ;'kVj"_:..
Permit Modification
Complete File - Historical
Engineering Alternatives (EAA)
Staff Report
Instream Assessment (67b)
Speculative Limits
Environmental Assessment (EA)
Permit
History
Document Date:
March 30, 2006
'Thin document is printed on reuse paper - igiore any
content on the reYerse /side
7
March 30, 2006
Mr. Michael Myers
Aqua North Carolina, Inc.
P.O. Box 4889
Cary, North Carolina 27519
Michael F. Easley, Governor
William G. Ross Jr., Secretary
North Carolina Department of Environment and Natural Resources
Alan W. Klimek, P.E. Director
Division of Water Quality
;ECEOWE
1.1 APR 7 2006 J
DENR - WATER QUALITY
POINT SOURCE BRAt4CH
SUBJECT: Authorization to Construct
A to C No. 065480A01
Aqua North Carolina, Inc.
Beau Rivage WWTP
New Hanover County
Dear Mr. Myers:
A letter of request for Authorization to Construct was received November 10, 2005, by
the Division, and final plans and specifications for the subject project have been reviewed and
found to be satisfactory. Authorization is hereby granted for the construction of modifications to
the existing 0.1 MGD Beau Rivage Wastewater Treatment Plant, with discharge of treated
wastewater into the Cape Fear River in the Cape Fear River Basin.
This authorization results in an increase in design and permitted capacity to 0.2 MGD
MGD, and is awarded for the construction of the following specific modifications:
Construction of a new 0.2 MGD dual train package WWTP including a manual
bar screen with t inch clear space, a 50,000 gallon flow equalization basin with
dual. 208 GPM submersible pumps, two 109,596 gallon aeration basins, two
35,367 gallon clarifiers, two 140 square foot tertiary filters, post aeration, dual 0.2
MGD UV disinfection systems, and a 46,882 gallon sludge storage tank, in
conformity with the project plans, specifications, and other supporting data
subsequently filed and approved by the Department of Environment and Natural
Resources.
This Authorization to Construct is issued in accordance with Part III, Paragraph A of
NPDES Permit No. NC0065480 issued October 26, 2005, and shall be subject to revocation
unless the wastewater treatment facilities are constructed in accordance with the conditions and
limitations specified in Permit No. NC0065480.
The sludge generated from these treatment facilities must be disposed of in accordance
with G.S. 143-215.1 and in a manner approved by the North Carolina Division of Water Quality.
N()` a Carolina
taralii
North Carolina Division of Water Quality 1617 Mail Service Center Raleigh, NC 27699-1617 Phone (919) 733-7015 Customer Service
Internet:__512 N. Salisbury St.
Raleigh. NC 27604 FAX (919) 733-2496 1-877-623-6748
An Equal Opportunity/Affirmative Action Employer - 50% Recycled/10% Post Consumer Paper
Mr. Michael Myers
March 30, 2006
Page 2
In the event that the facilities fail to perform satisfactorily, including the creation of
nuisance conditions, the Permittee shall take immediate corrective action, including those as may
be required by this Division, such as the construction of additional or replacement wastewater
treatment or disposal facilities.
The Wilmington Regional Office, telephone number (910) 796-7215, shall be notified at
least forty-eight (48) hours in advance of operation of the installed facilities so that an on site
inspection can be made. Such notification to the regional supervisor shall be made during the
normal office hours from 8:00 a.m. until 5:00 p.m. on Monday through Friday, excluding State
Holidays.
Upon completion of construction and prior to operation of this permitted facility, a
certification must be received from a professional engineer certifying that the permitted facility
has been installed in accordance with the NPDES Permit, this Authorization to Construct and the
approved plans and specifications. Mail the Certification to Cecil G. Madden, Jr., P.E.,
Construction Grants & Loans, DWQ / DENR, 1633 Mail Service Center, Raleigh, NC 27699-
1633.
Upon classification of the facility by the Certification Commission, the Permittee shall
employ a certified wastewater treatment plant operator to be in responsible charge (ORC) of the
wastewater treatment facilities. The operator must hold a certificate of the type and grade at
least equivalent to or greater than the classification assigned to the wastewater treatment
facilities by the Certification Commission.
The Permittee must also employ a certified back-up operator of the appropriate type and
grade to comply with the conditions of T15A:8G.0202. The ORC of the facility must visit each
Class I facility at least weekly and each Class II, III and IV facility at least daily, excluding
weekends and holidays, must properly manage the facility, must document daily operation and
maintenance of the facility, and must comply with all other conditions of T15A:8G.0202.
A copy of the approved plans and specifications shall be maintained on file by the
Permittee for the life of the facility.
During the construction of the proposed additions/modifications, the permittee shall
continue to properly maintain and operate the existing wastewater treatment facilities at all times,
and in such a manner, as necessary to comply with the effluent limits specified in the NPDES
Permit.
You are reminded that it is mandatory for the project to be constructed in accordance
with the North Carolina Sedimentation Pollution Control Act, and, when applicable, the North
Carolina Dam Safety Act. In addition, the specifications must clearly state what the contractor's
responsibilities shall be in complying with these Acts.
Failure to abide by the requirements contained in this Authorization to Construct may
subject the Permittee to an enforcement action by the Division of Water Quality in accordance
with North Carolina General Statute 143-215.6A to 143-215.6C.
Mr. Michael Myers
March 30, 2006
Page 3
The issuance of this Authorization to Construct does not preclude the Permittee from
complying with any and all statutes, rules, regulations, or ordinances which may be imposed by
other government agencies (local, state, and federal) which have jurisdiction.
One (1) set of approved plans and specifications is being forwarded to you. If you have
any questions or need additional information, please contact Cecil G. Madden, Jr., P.E. at
telephone number (919) 715-6203.
Sincerely,
W. Klimek, P.E.
MH:cgm
cc: Gerald Hatton, P.E. — Arcadis, Charlotte Office
New Hanover County Health Department
DWQ Wilmignton Regional Office, Surface Water Protection
Technical Assistance and Certification Unit
Daniel Blaisdell, P.E.
Point Source Branch, NPDES Program
Cecil G. Madden, Jr., P.E.
Mark Hubbard, P.E.
A to C File