HomeMy WebLinkAboutNC0026565_Chemical Addendum_20220118 Ramseur
Where Family and Friends Meet
TOWN OF RAMSEUR
724 Liberty Street, PO Box 545
Ramseur,North Carolina 27316
336-824-8530/336-824-4111
COMMISSIONERS MAYOR TOWN CLERK/FINANCE OFFICER
Jim McIntosh VICKI CAUDLE Carol Akers
J.C.Parrish
Tim Cranford DEPSITY TOWN CLERK/FINANCE OFFICER
Joy Hooker
Diana Brower Adrienne Hagood
January 7,2022
Mr.Michael Montebello
NC Department of Environmental Quality
Division of Water Resources RECEIVED
Water Quality Permitting-NPDES
1617 Mail Service Center .14 N 1 8 2022
Raleigh,NC 27699-1617
RE: . Town of Ramseur WWTP NCDEQ/DWR/NpDtS
NPDES Permit Renewal-Chemical Addendum
Permit#0026565
Dear Mr.Montebello:
As a supplement to the Ramseur Wastewater Treatment Plant NPDES Application Package that is currently under review,the
Town of Ramseur is submitting additional information per Session Law 2018-5,Senate Bill 99,Section 13.1(r). At the
request of the Division of Environmental Quality(DEQ),the Town conducted additional WWTP influent sampling in July,
August,and September 2019 for 1,4-Dioxane.The analysis was done in accordance with EPA Method 624.1,which is a
certified method in 40 CFR Part 136.Accordingly,the Town is providing a Chemical Addendum to the NPDES Application
for the 1,4 Dioxane influent sampling results.
Additionally,at the request of DEQ,the Town performed WWTP influent sampling for a series of PFOA/PFAS analytes in
July,August,and September 2019.This sampling is not certified by the Town as there is not a 40 CFR Part 136 certified
analysis method for the analytes.This data was previously provided to DEQ following the three sampling events in 2019.
Although this data is not being certified by the Town and was already provided to DEQ,we are providing a summary of the
results as an attachment to this for clarity.
The following attachments are being provided as a supplement to the Ramseur WWTP NPDES Permit Application.
Attachment 1: Chemical Addendum to NPDES Application
Attachment 2: Lab Reports from 1,4 Dioxane Sampling Results
Attachment 3: Uncertified Emerging Compound Sampling Data Summary
Please let us know if you have any questions on the information provided.
Respectfully,
TQ N OF MS U'
i
McIntosh,ORC
Mayor Pro Tem/Commissioner
EPA Identification Number NPDES Number Facility Name Outfall Number
FRSID110006710648 NC0026565 Town of Ramseur WWTP 001
Method Number(if Estimated Concentration (If
Pollutant(Required) CAS number Applicable) Reason Pollutant Believed Present in Discharge Known)
Median of three influent
sampling events(July,August,
1,4 Dioxane 123-91-1 EPA624.1 Influent sampling results(July,August,September 2019) September 2019)was 2 ug/L
•
8/9/18 Chain of Custody Record (COC) ��NPDES#: Oaz lo �
INC. Client: 5 7-4-) r�eaµte zt.�Ut4 Phone: 3342 `,VzY'-mil
, Address:f 5 04c-yp[ ,-rr--/Crt Fax:
.P" \ ENVIRONMENTAL LABORATORIES P`cz~ s.o-u— /J_C.- 2- 7 1(, Email:
4-t. i.. 642 Tamco Rd. Phone: 336-342-4748 Project:
Reidsville NC 27320 Fax: 336-342-1522 P.0.#:
,.. - Email: info@meritechlabs.com Attentan: Net i)2_a /31gi A/ Turn Around Time*
*RUSH work needs prior approval,
How would you like your report sen ? Charges Apply
www.meritechlabs.com Circle all that apply: Email(preferred), Fax, Mail Std 10 da s) 3-5 Days 24-48 Hrs
Sampling Dates & Times Person T g sa ple Sign/Print): r t j J Lab Use Only
Sample Location and/or ID # Start End / Let,
On 1ce7 pH OK?
Comp? #o Test(s) equired On
Cl OK?
f Date Time Date _ Time Grab? Cont.
I�lP.4-ALL 7-'9"(q l[Ott -7- j9 100 G`` . 3 I 1 DreC7fcaf't`e t-13 .
i
Temperature Upon
Receipt: 7
Method of ***Dechlorination(<0.5 ppm)of Ammonia,Cyanide,Phenol and TKN samples must be done in the field prior to preservation.***
Comments: Compositor#
Shipment:
11 UPS Jug#
Fed Ex Are these results for regulatory purposes? Yes [-J. ,„No Report results in: mg/L r mg/kg ug/L
Re' yi i! Da Time: Received by: Da Time:
Hand Delivery B/// -�� / ( . /D
4
Other Refi quishe / /y, , Time: .:20Rece e [Date: Tim
, :. -?
t r� Timed r= Received ;
b: ,.firn _ fr.. Time: '`
`��(f �Y°_�i�� 4 A . _
Meritech Inc.
Environmental Laboratory
Laboratory Certification No.165
Contact: Nadine Blackweel&Terry Lewallan Report Date: 7/19/2019
Client: Suez Environmental NPDES#: NC0026565
4735 Roundleaf Rd
Ramseur,NC 27316 Date Sample Rcvd: 7/10/2019
Meritech Work Order# 071019173 Sample: Influent Grab 7/8/19
Parameters Results Analysis Date Reporting Limit Method
I
1,4 Dioxane+ Trip Blank Attached 7/11/19 - EPA 624.1
ti
ii
I hereby certify that I have reviewed and approve these data. ;
Laboratory Representative
642 Tamco Road, Reidsville,North Carolina 27320
tel.(336)342-4748 fax.(336)342-1522
MERITECH, INC.
. " Environmental Laboratories
} Laboratory Certification#165
Client: Suez Water/Ramseur WWTP Merited' ID#: 071019173
Project: 1,4 Dioxane Analysis: 07/11/19
Client Sample ID: Influent Analyst: VWV
Sample Collection: 07/08/19 Dilution Factor: 1 •
Report Date: 07/15/19
EPA 624.1 VOLATILE ORGANICS
Parameter Result
1,4-Dioxane(p-Dioxane) < 1.00 ug/L
Trip Blank < 1.00 ug/L 1;
Batch Blank = Below Reporting Limit (Yes I/No
Internal Standards method criteria acceptable (Yes)/No
Surrogate Recoveries Spike Cone Spike Recovery Limits
Toluene-d8 30 ug/I, 97% 67-151%
Bromofluorobenzene 30 ug/L 97% 45-161%
*-If "no" is selected, see second page for details.
I hereby certify that I have reviewed and approve these data. _
Labora ry Repre 9 tive
642 Tamco Road * Reidsville, NC 27320
(336) 342-4748 * info@meritechlabs.com
L
EA/to Chain of Custody Record (COC) NPDES#: 00210565
1tl1LRIT�� C. Client: SC .Z 6/Ruiviee too-trphone: 3 lo— 8z4 3`i31
„� �! Address: (173-S get c.-.dAP4C-1�'-- Fax:
-,-.. ENVIRONMENTAL LABORATORIES R��n5euv) ski L -7316 Email:
; 642 Tamco Rd. Phone: 336-342-4748 Project:
Reidsville NC 27320 Fax: 336-342-1522 P.O.#:
Email: info@meritechlabs.com Attention: t�Cc.d✓ 8&k�.-e,,� Turn Around Time'
*RUSH work needs prior approval,
How would you like your report sent? Charges Apply
viw'.meritechlabs.Com Sid(10da s) 3-5 Da s 24-48Hrs
Circle all that apply: Email(preferred), Fax, Mail
Sampling Dates &Times Person Taking sample(Sign/Print): Lab Use Only
Sample Location and/or ID # Start End On Ice? pH OK?
Comp? #of Test(s) Required Yes / No
Date Time Date Time Grab?!Cont. y CI OK?
:,;—mac C--hu, -$— 8-6-i 6ci to `i I ct o c ib & 1 3 if ti O,`p-.�(,c`4_,,,e 1(. 1
1
Temperature Upon
Receipt: y
Method of ***Dechlorination(<0.5 ppm)of Ammonia,Cyanide, Phenol and TKN samples must be done in the field prior to preservation.***
Comments: Compositor#
Shipment:
LI UPS Jug#
Fed Ex Are these results for regulatory purposes? Yes No IIT, Report results in: mg/L M mg/kg ug/L
Relinquished.' Date Time: Received by i l Date. Time:
Hand Delivery lL _./ �(y—t y �& - l t3 .
Relinquished by: Date: p' & Time: �- yJ Received by:
J Other ,.,4 Ii _ / r-6`"/ 1 l('S /,i_I ,b e: /^ Time:i s�
Relinquished �/ p b l? Time: �'i 'eceived byLab: y / !_. 7
�— O /L /��� t a �i r+1f /`7 Da,,,A,.' Time: _
MERITECH INC.
00,
Environmental Laboratories
Laboratory Certification#165
I4
Client: Suez Water/Ramseur WWTP Meritech ID#: 080819164
Project: 1,4-Dioxane Analysis: 08/12/19
Client Sample ID: Influent Analyst: VWV
Sample Collection: 08/06/19 Dilution Factor: 1
Report Date: 08/16/19
EPA 624.1 VOLATILE ORGANICS
Parameter Result
1,4-Dioxane(p-Dioxane) 2.00 ug/L
Trip Blank < 1.00 ug/L
Batch Blank =Below Reporting Limit (Yes)j No
Internal Standards method criteria acceptable (Yes)/No
Surrogate Recoveries Spike Cone Spike Recovery Limits
Toluene-d8 30 ug/L 101% 67-151%
Bromofluorobenzene 30 ug/L 97% 45-161%
*-If "no" is selected, see second page for details.
I hereby certify that I have reviewed and approve these data.
Labors ory Repr sentative
642 Tamco Road * Reidsville, NC 27320
(336) 342-4748 * info@meritechlabs.com
Meritech, Inc.
Environmental Laboratory
Laboratory Certification No. 165
Contact: Nadine Blackwell Report Date: 8/20/2019
Client: Suez Environmental NPDES#: NC0026565
4735 Roundleaf Rd
Ramseur, NC 27316 Date Sample Rcvd: 8/8/2019
Meritech Work Order# 080819164 Sample: Influent Grab 8/6/19
Parameters Results Analysis Date Reporting Limit Method
1,4 Dioxane+ Trip Blank Attached 8/12/19 - EPA 624.1
I
hereby certify that I have reviewed and approve these data. ��(�
La oorator Re resentative
Y
642 Tamco Road,Reidsville,North Carolina 27320
tel.(336)342-4748 fax.(336)342-1522
3/9/18 Chain of Custody Record (COC) NPDES#: 00 Z--&SoS
Client: 5(4E2-t v u► ekr Phone: 336,- B `} - i 39
wwrio
McR E H INC•, Address: 3� r 1. Fax:
ENVIRONMENTAL LABORATORIES Ra-I4,t6-attt,-/^a C- 273/, Email:
.
,... 642 Tamco Rd. Phone: 336-342-4748 Project:
,:`Y Reidsville NC 27320 Fax: 336-342-1522 P.O.#:
/( Turn Around Time*
Email: info@meritechlabs.com Attention A f,� 1V kla [1-e1� *RUSH work needs prior approval,
How would you like your report sent? Charees Apply
Vvwv.i.meritechlabS.corn Circle allthata I Email (preferred), Fax, Mail Std(l0da s) 3-5 Davis 24-48Hrs
apply: (.,, . .
Sampling Dates &Times Person Taking Sa ple(Sigq print): Lab Use Only
-"1.tvw �Load (-1, " � ,Q.I _ i
Sample Location and/or ID # Start End �II
Comp.l #of Test(s1 required On Ice? pH OK?
Date Time Date Time Grab?I Cont. On
/ No CI OK?
Ih-Ci LvtlY -- ci-q-1 q 1000 9-$19 l eo a _ G 13 1 ) 01 c.N.Q. vt,e L
r
Temperature Upon
I Receipt: 2 ,1
Method of ***Dechlorination(<0.5 ppm)of Ammonia,Cyanide,Phenol and TKN samples must be done in the field prior to preservation.***
Comments: Compositor#
Shipment:
[J UPS Jug#
Fed Ex Are these results for regulatory purposes? Yes No !, Report results in: mg/L mg/kg 17,1 ug/L L
Re( r y ��pate fn Time: Receiv • date: T/2:
Hand Delivery ``jj !``��s �j -4C-F7
rjRelinquished by: Date: Time: Rece edd�� ^^ Date• I Time:
Other Vp){ ('/V}�^� of-ti.t1 �.5�p
e: Time: Received by Lab: / it 1 Time: :,
77.
e c- -Gr.VC f�wy.ft115 75M al-4-(°l
R-e 11,1 ,-- 1 /5% 9 /635
MERITECH, INC.
Environmental Laboratories
�' Laboratory Certification#165
Client: Suez Water/Ramseur WWTP Meritech ID#: 09051984
Project: 1,4-Dioxane Analysis: 09/06/19
Client Sample ID: Influent Analyst: VWV
Sample Collection: 09/04/19 Dilution Factor: 2
Report Date: 09/09/19
EPA 624.1 VOLATILE ORGANICS
Parameter Result
1,4-Dioxane(p-Dioxane) 2.08 ug/L
Trip Blank < 1.00 ug/L
Batch Blank =Below Reporting Limit (Yes)/No
Internal Standards method criteria acceptable (Yes)/No
Surrogate Recoveries Spike Cone Spike Recovery Limits
Toluene-d8 30 ug/L 110% 67-151%
Bromofluorobenzene 30 ug/L 102% 45-161%
*-If "no"is selected, see second page for details.
I hereby certify that I have reviewed and approve these data. tL!IItiItiii
Labo"tory Re'"?a`ntative
642 Tamco Road * Reidsville, NC 27320
(336) 342-4748 * info@meritechlabs.com
Meritech, Inc.
x' Environmental Laboratory
rlajo Laboratory Certification No. 165
Contact: Nadine Blackwell Report Date: 9/11/2019
Client: Suez Environmental NPDES#: NC0026565
4735 Roundleaf Rd
Ramseur, NC 27316 Date Sample Rcvd: 9/5/2019
Meritech Work Order# 09051984 Sample: Influent Grab 9/4/19
Parameters Results Analysis Date Reporting Limit Method
1,4 Dioxane+ Trip Blank Attached 9/6/19 - EPA 624.1
I hereby certify that I have reviewed and approve these data.
aboratory Representative
642 Tamco Road,Reidsville,North Carolina 27320
tel.(336)342-4748 fax.(336)342-1522
it
Narrative Summary
1.7°6
bast
ENTHALPY
A I C A'
EU#0919-708 R 23 of 33
Enthalpy Analytical Narrative Summary
Company Suez Water Ramseur
Job# 0919-708 PFAS—Legacy 24+Gen-X
Client Project# n/a
Custody Hunter Allen of Enthalpy Analytical Wilmington received the sample on
09/08/19 on ice at 2.6°C.Braidy May of Enthalpy Analytical Wilmington
observed the samples were in good condition on 09/09/19.
Prior to,during,and after analysis,the sample was stored in the laboratory
with access only by authorized personnel of Enthalpy Analytical, LLC.
Analysis The sample was analyzed by isotope dilution method for PFAS using
Waters Acquity UPLC equipped with Xevo TQ MS (LC/MS/MS"Kili").
For aqueous samples, 250mL aliquot was weighed and spiked with
Extraction Standard (ES). The sample was then mixed well and
centrifuged.
Cleanup procedures were performed on the supernatant and then
extracted via SPE. Each final sample extract was transferred to an
autosampler vial and spiked with 4004 of Injection Standard(IS),prior
to analysis.
Calibration The analytes and labeled standards in the initial calibration exhibited
RSDs less than 50%with exception of the following:
M8FOSA and d3-N-MeFOSAA
All analytes passed the R2 coefficient correlation criteria. Per DoD QSM
5.3 Table B-15, the ICAL is acceptable for all analytes since R2 met
criteria. All analytes will be reported.
The ICV and continuing calibration (concal) injections met the ±30%
recovery criteria and ±50% ES recovery criteria for all analytes of
interest.
QC Notes The QC injections of the initial extraction did not meet method criteria
requiring re-extraction of samples. The QC of re-extracted samples met
the +50% criteria for ES recoveries with the exception of analyte
M2PFTeDA, which fell below the lower limit in the method blank.
However, this compound was recovered within limits for the OPR for
both native and labeled criteria. Therefore, the data are considered
acceptable and no impact on sample data.
No analytes were detected above the LOD (MDL) in the method blank.
The samples were extracted within the 14-day from collection holding
time (initial extraction—Sept 17 and re-extraction—Sept 20). Extracts
loot dt.
EN I HALL( EU#0919-708R 24 of 33
Enthalpy Analytical Narrative Summary
(continued)
QC Notes were analyzed within the 28-days from extraction to analysis holding time
(continued) required by the method.
Reporting Notes Results from the re-extraction are included in this report.
Analyte PFPeA had elevated values that were not consistent with past
patterns. After investigation, it was concluded the values were valid and
are reported.
Some analytes in the samples fell outside the limits for ES recoveries.
Although the cause was undetermined, it is theorized to be matrix effects.
Based on the native results in the OPR meeting criteria,the out-of-range
ES recoveries have no impact on the accuracy of the target analyte
(native)compounds. Therefore,the data are considered acceptable.
These analyses met the requirements of the TNI Standard. Any
deviations from the requirements of the reference method or TNI
Standard have been stated above.
The results presented in this report are representative of the samples as
provided to the laboratory.
The samples, calibrations and standards for the data presented in this
report were analyzed at 2714 Exchange Drive, Wilmington,NC 28405.
EN LHALM
EU#0919-708 R 25 of 33