Subject:
Dear Mr. Brown:
NORTH CAROLINA
Environmental Quality
January 3, 2022
Compliance Evaluation Inspection
Roanoke River WWTP
NPDES Permit No. NC0024201
Halifax County
On December 16, 2021, Mitch Hayes of the Raleigh Regional Office conducted the subject
inspection with the assistance of Steven Ellis (Operator in Responsible Charge). Mr. Ellis' and Ms.
Isabelle Wilcoxon's, Laboratory Supervisor, assistance with this inspection was greatly
appreciated. Below is a list of findings developed from the inspection and review of the permit:
1. The current permit was reissued October 19, 2018, became effective December 1, 2018
and will expire March 31, 2022. A renewal application was received February 2, 2021 and
is currently under review.
2. The 8.34 MGD consists of the following units: Huber Rotomat cylindrical screen, manual
bar screen; Vortex grit removal; influent pump station with four pumps; two (2) primary
clarifiers; two (2) trickling filters; two (2) 2 MG rectangle secondary clarifiers with
traveling bridge; three (3) 0.5 MG aeration basins; two chlorine contact basins; two (2)
RAS pump stations; three (3) anaerobic digesters with heat exchangers; one (1) WAS
pump station; two (2) gravity settling tanks with gravity belt thickener and lime
stabilization; one (1) 1 MG solids storage tank; effluent pump station; fourteen (14) sludge
drying beds; two (2) on site generators for back-up power source.
3. At the time of inspection, one aeration basin, one trickling filter, one primary clarifier, one
secondary clarifier, one chlorine contact chamber was on line due to low influent. Two
anaerobic digesters were being operated. One sludge bed was being used. Effluent
appeared clear in the chlorine contact tank.
4. Discharge Monitoring Reports for the review period December 2019 through December
2021 were checked for compliance with permit limits and monitoring requirements. TSS
weekly and monthly average limit violation was noted for February 2021 and March 2021.
There were no other violations for the review period.
North Carolina Department of Environmental Quality I Division of Water Resources
Raleigh Regional Office ; 3800 Barrett Drive I Raleigh. North Carolina 27609
919.791.4200
5. Commercial lab results, chain of custody records, and bench sheets were compared with
data submitted on the Discharge Monitoring Report (DMR) for October 2021. No
discrepancies were noted.
6. The laboratory was checked in a cursory manner. All pH buffers were within expiration
date. All calibrations of instruments and temperatures of refrigerators and other equipment
are recorded daily in a log book.
I would like to thank everyone involved with this inspection. If you have any questions concerning
the inspection or this letter, please contact Mitch Hayes at 919.791.4261 or at
mitch.hayes@ncdenr.gov
cc: permit file, Laserfiche
Sincerely,
Scott Vinson, Regional Supervisor
Water Quality Regional Operations Section
Raleigh Regional Office
Division of Water Resources, NC DEQ
North Carolina Department of Environmental Quality I Division of Water Resources
Raleigh Regional Office ! 3800 Barrett Drive ; Raleigh. North Carolina 27609
919.7914200
United States Environmental Protection Agency
E PA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (Le., PCS)
Transaction Code NPDES yrlmolday Inspection
1 112 i 2 E 3 1 NC0024201 111 121 21/12/16 117
Type
1812I
l l I I I
Inspector
1911.1
Fac Type
2011
211111 l l I I I I II I I I I I I I I I I I I I I I I I
I II
I I I I 1 r6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA
67I
1 j 70 � LJ I 71 I I 72 1 i I
1 Li
Reserved
73I I I74 71
I 1180
11 1 HI
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Roanoke River WWTP
135 Aqueduct Rd
Weldon NC 27890
Entry Time/Date
10:0OAM 21/12/16
Permit Effective Date
18/12/01
Exit Time/Date
11:15AM 21/12/16
-
Permit Expiration Date
22/03/31
Name(s) of Onsite Representative(s)ftles(s)/Phone and Fax Number(s)
/11
Steven L Ellis//252-536-4884 /2525364885
Steven Lee Eflis/ORC/252-536-4884/
Other Facility Data
Name, Address of Responsible OfficiallTitlelPhone and Fax Number
Contacted
Steven L EIIis,PO Box 308 Ronok Rpd Afs NC 27870/1252-536-4884/2525364885
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
• Permit • Flow Measurement Operations & Maintenar II Records/Reports
Self -Monitoring Progran Sludge Handling Dispo: Facility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Mitchell S Hayes DWR/RRO WO/919-791-4200/
il/RC/1/t.GUI S, - H- el ••. ht1 O 3, Z G Z z
Signature of Management() A Reviewer Agency/Office/Phone and Fax Numbers Date
)747:7-e--ykrt--/ ?i? - ,V-• /1.),.c2_ 0--, t-ez,-71' Y, 4, 2-2--
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
1
NPDES
NC0024201
yr/mo/day
21/12/16 117
18 Li
Inspection Type
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The current permit was reissued October 19, 2018, became effective December 1, 2018 and will
expire March 31, 2022. A renewal application was received February 2, 2021 and is currently under
review.
The 8.34 MGD consists of the following units: Huber Rotomat cylindrical screen, manual bar screen;
Vortex grit removal; influent pump station with four pumps; two (2) primary clarifiers; two (2) trickling
filters; two (2) 2 MG rectangle secondary clarifiers with traveling bridge; three (3) 0.5 MG aeration
basins; two chlorine contact basins; two (2) RAS pump stations; three (3) anaerobic digesters with
heat exchangers; one (1) WAS pump station; two (2) gravity settling tanks with gravity belt thickener
and lime stabilization; one (1) 1 MG solids storage tank; effluent pump station; fourteen (14) sludge
drying beds; two (2) on site generators for back-up power source.
At the time of inspection, one aeration basin, one trickling filter, one primary clarifier, one secondary
clarifier, one chlorine contact chamber was on line due to low influent. Two anaerobic digesters were
being operated. One sludge bed was being used. Effluent appeared clear in the chlorine contact
tank.
Discharge Monitoring Reports for the review period December 2019 through December 2021 were
checked for compliance with permit limits and monitoring requirements. TSS weekly and monthly
average limit violation was noted for February 2021 and March 2021. There were no other violations
for the review period.
Commercial lab results, chain of custody records, and bench sheets were compared with data
submitted on the Discharge Monitoring Report (DMR) for October 2021. No discrepancies were
noted.
The laboratory was checked in a cursory manner. All pH buffers were within expiration date. All
calibrations of instruments and temperatures of refrigerators and other equipment are recorded daily
in a log book.
Page# 2
Permit: NC0024201
Owner - Facility: Roanoke River WWTP
Inspection Date: 12/16/2021 Inspection Type: Compliance Evaluation
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment. Permit expires March 31, 2022.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade Tess or greater than the facility
classification?
Yes No NA NE
. 000
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
▪ ❑ ❑ ❑
▪ ❑ ❑ ❑
Yes No NA NE
▪ ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
II
•
•
•
•
• ❑ ❑ ❑
• ❑ ❑ ❑
■ ❑❑❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 3
Permit: NC0024201
Owner - Facility: Roanoke River WWTP
Inspection Date: 12/16/2021 Inspection Typo: Compliance Evaluation
Record Keeping
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Comment:
Yes No NA NE
• ❑ ❑ ❑
MI ❑ ❑ ❑
Effluent Pipe Yes No NA NE
Is right of way to the outfall properly maintained? • 0 ❑ 0
Are the receiving water free of foam other than trace amounts and other debris? • 0 0 ❑
If effluent (diffuser pipes are required) are they operating properly? • 0 0 ❑
Comment' Effluent appeared clear in the reaeration zone.
Flow Measurement - Effluent Yes No NA NE
# Is flow meter used for reporting? MO ❑ ❑
Is flow meter calibrated annually? • 0 0 0
Is the flow meter operational? • 0 0 ❑
(If units are separated) Does the chart recorder match the flow meter? • ❑ 0 ❑
Comment' Flow meter calibrated 10.13.2021.
Anaerobic Digester Yes No NA NE
Type of operation: Floating cover
Is the capacity adequate? • ❑ ❑ ❑
# Is gas stored on site? • ❑ ❑ 0
Is the digester(s) free of tilting covers? • 0 0 0
Is the gas burner operational? 0 0 • 0
Is the digester heated? ❑ ❑ ❑
Is the temperature maintained constantly? • ❑ Cl 0
Is tankage available for properly waste sludge? •❑ ❑ ❑
Comment- Three primary anaerobic digesters in operation.
Drying Beds Yes No NA NE
Is there adequate drying bed space? • ❑ ❑ ❑
Is the sludge distribution on drying beds appropriate? • 0 0 ❑
Are the drying beds free of vegetation? •❑ 0 0
# Is the site free of dry sludge remaining in beds? • 0 0 0
Page# 4
Permit: NC0024201
Owner - Facility: Roanoke River WWTP
Inspection Date: 12/16/2021 Inspection Type: Compliance Evaluation
Drying Beds
Is the site free of stockpiled sludge?
Is the filtrate from sludge drying beds returned to the front of the plant?
# Is the sludge disposed of through county landfill?
# Is the sludge land applied?
(Vacuum filters) Is polymer mixing adequate?
Comment' One out of 14 drvinq beds was in use.
Solids Handling Equipment
Is the equipment operational?
Is the chemical feed equipment operational?
Is storage adequate?
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Comment: Belt filter presses was not in operation at the time of inspection.
Yes No NA NE
MOOD
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Yes No NA NE
■ ❑❑❑
■ ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
❑ ❑ ❑
❑ ❑ • ❑
• ❑ ❑ ❑
Chemical Feed Yes No NA NE
Is containment adequate? ■ ❑ ❑ ❑
Is storage adequate? • 0 ❑ ❑
Are backup pumps available? •❑ ❑ ❑
Is the site free of excessive leaking? • ❑ ❑ ❑
Comment:
Pump Station - Effluent Yes No NA NE
Is the pump wet well free of bypass lines or structures? ■ ❑ ❑ ❑
Are all pumps present? • ❑ ❑ ❑
Are all pumps operable? 111000
Are float controls operable? ❑ ❑ ❑•
is SCADA telemetry available and operational? •❑ ❑ ❑
Is audible and visual alarm available and operational? • ❑ ❑ ❑
Comment:
Page# 5
Permit: NC0024201
Owner - Facility: Roanoke River WWTP
Inspection Date: 12/16/2021 Inspection Type: Compliance Evaluation
Pump Station - Influent Yes No NA NE
Is the pump wet well free of bypass lines or structures? • 0 0 0
Is the wet well free of excessive grease? 0 0 0 •
Are all pumps present? ❑ ❑ ❑
Are all pumps operable? • 0 0 0
Are float controls operable? 0 ❑ 0
Is SCADA telemetry available and operational? • 0 0 0
Is audible and visual alarm available and operational? • 0 0 0
Comment:
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Grit Removal
Type of grit removal
a.Manual
b.Mechanical
Is the grit free of excessive organic matter?
Is the grit free of excessive odor?
# Is disposal of grit in compliance?
Comment. Grit removal is not being operated.
Yes No NA NE
•
•
• ❑ ❑ ❑
• ❑ ❑ ❑
II ❑ ❑ ❑
NI ❑ Q ❑
Yes No NA NE
o
•
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Equalization Basins Yes No NA NE
Is the basin aerated? 0 • 0 0
Is the basin free of bypass lines or structures to the natural environment? • 0 ❑ ❑
Is the basin free of excessive grease? • 0 0 0
Are all pumps present? • 0 0 0
Page# 6
Permit: NC0024201
Owner - Facility: Roanoke River WWTP
Inspection Date: 12/16/2021 Inspection Type: Compliance Evaluation
Equalization Basins Yes No NA NE
Are all pumps operable? •❑ ❑ ❑
Are float controls operable? 0 0 • ❑
Are audible and visual alarms operable? 00.0
# Is basin size/volume adequate? ■ ❑ ❑ ❑
Comment: Two - 375.000 gallons EQ basins. Used for high flow situations.
Primary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • ❑ 0 0
Is the site free of excessive buildup of solids in center well of circular clarifier? • 0 ❑ ❑
Are weirs level? • ❑ 0 0
Is the site free of weir blockage? • ❑ ❑ ❑
Is the site free of evidence of short-circuiting? • 0 0 0
Is scum removal adequate? •❑ ❑ ❑
Is the site free of excessive floating sludge? • 0 ❑ 0
Is the drive unit operational? • ❑ ❑ ❑
Is the sludge blanket level acceptable? • 0 ❑ 0
Is the sludge blanket level acceptable? (Approximately Y4 of the sidewall depth) MI 0 ❑ 0
Comment: One out of two in operation.
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • ❑ ❑ ❑
Is the site free of excessive buildup of solids in center well of circular clarifier? MID ❑ ❑
Are weirs level? • 0 ❑ ❑
Is the site free of weir blockage? ■ ❑ ❑ ❑
Is the site free of evidence of short-circuiting? • 0 0 ❑
Is scum removal adequate? IN 0 0 0
Is the site free of excessive floating sludge? ■ 0 0 0
Is the drive unit operational? • 0 0 0
Is the return rate acceptable (low turbulence)? • ❑ ❑ ❑
Is the overflow clear of excessive solids/pin floc? • 0 0 ❑
Is the sludge blanket level acceptable? (Approximately 'A of the sidewall depth) • ❑ ❑ 0
Comment. SB was two feet with a 14 feet sidewall depth.
Page# 7
Permit: NC0024201 Owner - Facility: Roanoke River WWTP
Inspection Date: 12/16/2021 Inspection Type: Compliance Evaluation
Trickling Filter Yes No NA NE
Is the filter free of ponding? •❑ ❑ ❑
Is the filter free of leaks at the center column of filter's distribution arms? • 0 0 0
Is the distribution of flow even from the distribution arms? • 0 0 0
Is the filter free of uneven or discolored growth? • 0 ❑ 0
Is the filter free of sloughing of excessive growth? • ❑ 0 ❑
Are the filter's distribution arms orifices free of clogging? • ❑ 0 ❑
Is the filter free of excessive filter flies, worms or snails? • 0 0 ❑
Comment. Both trickling filters were in operation.
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots? • 0 0 0
Are surface aerators and mixers operational? • 0 ❑ 0
Are the diffusers operational? • ❑ 0 0
Is the foam the proper color for the treatment process? • ❑ ❑ 0
Does the foam cover Tess than 25% of the basin's surface? 111 ❑ 0 ❑
Is the DO level acceptable? • 0 0 0
Is the DO level acceptable?(1.0 to 3.0 mg/I) • ❑ 0 ❑
Comment' One out of three basins were in use.
De -chlorination Yes No NA NE
Type of system ? Liquid
Is the feed ratio proportional to chlorine amount (1 to 1)? • 0 0 0
Is storage appropriate for cylinders? 0 ❑ • 0
# Is de -chlorination substance stored away from chlorine containers? • ❑ ❑ ❑
Comment:
Are the tablets the proper size and type? 0 ❑ • ❑
Are tablet de -chlorinators operational? ❑ ❑ • ❑
Number of tubes in use?
Comment:
Page# 8
Permit: NC0024201 Owner - Facility: Roanoke River WWTP
Inspection Date: 12/16/2021 Inspection Type: Compliance Evaluation
Pumps-RAS-WAS Yes No NA NE
Are pumps in place? •❑ ❑ ❑
Are pumps operational? •❑ ❑ ❑
Are there adequate spare parts and supplies on site? •❑ ❑ ❑
Comment:
Disinfection -Liquid
Is there adequate reserve supply of disinfectant?
(Sodium Hypochlorite) Is pump feed system operational?
Is bulk storage tank containment area adequate? (free of leaks/open drains)
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑❑❑
• ❑ ❑ ❑
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? •❑ ❑ ❑
Are all other parameters(excluding field parameters) performed by a certified lab? •❑ ❑ ❑
# Is the facility using a contract lab? •❑ ❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 MOOD
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ■ ❑ ❑ ❑
Incubator (BOD) set to 20.0 degrees Celsius +1- 1.0 degrees? • ❑ ❑ ❑
Comment. Environment 1 in Greenville is contract laboratory.
Influent Semolina Yes No NA NE
# Is composite sampling flow proportional? 0 • 0 0
Is sample collected above side streams? ■ ❑ ❑ ❑
Is proper volume collected? ■ ❑ ❑ ❑
Is the tubing clean? ■ ❑ ❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 •❑ ❑ ❑
degrees Celsius)?
Is sampling performed according to the permit? • 0 0 0
Comment: No influent flow meter.
Page# 9
Permit: NC0024201
Owner - Facility: Roanoke River WWTP
Inspection Date: 12/16/2021 Inspection Type: Compliance Evaluation
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? • ❑ 0 ❑
Is sample collected below all treatment units? • ❑ 0 ❑
Is proper volume collected? •❑ ❑ ❑
Is the tubing clean? • 0 0 0
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 • 0 0 0
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type MOOD
representative)?
Comment:
Page# 10