HomeMy WebLinkAboutWQ0003468_Compliance Evaluation Inspection_20211222DocuSign Envelope ID: 432B866B-6616-4DA0-9917-BCA0263BCCBC
t�. STATE q,
ROY COOPER��� >
Governor O
ELIZABETH S. BISER
Secretary
S. DANIEL SMITH NORTH CAROLINA
Director Environmental Quality
December 17, 2021
Thomas G Jordan
West Fraser Inc
816 E Durst Ave
Greenwood, SC 29649
SUBJECT: Compliance Inspection Report
Armour Lumber Mill CLRS
Non -discharge Permit No. WQ0003468
Columbus County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Armour Lumber Mill
CLRS on 12/06/2021. This inspection was conducted to verify that the facility is operating in compliance
with the conditions and limitations specified in Non -discharge Permit No. WQ0003468. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report".
Please respond in writing to this office within 30 calendar days of your receipt of this letter regarding your plans
or measures to be taken to address the following issues:
1. Based on the recent site inspection, a process flow diagram was provided on 12/14/2021. Upon
review of this information, please specify on the diagram where the flow through the water
softeners recirculates back into the water stream;
2. Please specify where the backwash water line from the water softeners is directed; and,
3. Please identify what products are used to regenerate the water softeners and if any additional
products are injected into the water stream. Please provide chemical data sheet(s) for any of
these products as well as an account of quantity used for 2021.
If you should have any questions, please do not hesitate to contact Bryan Lievre with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
bryan.lievre@ncdenr.gov.
ATTACHMENT
Cc: Laserfiche
DocuSigned by:
Sincerely, Ev,1E3ABAl4AC7DC434...
bmLta Sa Al"
Morella Sanchez -King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
D_E Q�� North Carolina Department of Environmental Quality I Division of Water Resources
Wilmington Regional Office 1 127 Cardinal Drive Extension I Wilmington, North Carolina 28405
ft /`� 910.796,7215
DocuSign Envelope ID: 432B866B-6616-4DA0-9917-BCA0263BCCBC
ZrE STATE' q,.
ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
Q qM N
S. DANIEL SMITH
NORTH CAROLINA
Director
Environmental Quality
December 17, 2021
Gary W Townsend
West Fraser Inc
PO Box 57
Riegelwood, NC 28456
SUBJECT: Compliance Inspection Report
Armour Lumber Mill CLRS
Non -discharge Permit No. WQ0003468
Columbus County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Armour Lumber Mill
CLRS on 12/06/2021. This inspection was conducted to verify that the facility is operating in compliance
with the conditions and limitations specified in Non -discharge Permit No. WQ0003468. The findings and
comments noted during this inspection are provided in the enclosed copy of the inspection report
entitled "Compliance Inspection Report".
Please respond in writing to this office within 30 calendar days of your receipt of this letter regarding your plans
or measures to be taken to address the following issues:
1. Based on the recent site inspection, a process flow diagram was provided on 12/14/2021. Upon
review of this information, please specify on the diagram where the flow through the water
softeners recirculates back into the water stream;
2. Please specify where the backwash water line from the water softeners is directed; and,
3. Please identify what products are used to regenerate the water softeners and if any additional
products are injected into the water stream. Please provide chemical data sheet(s) for any of
these products as well as an account of quantity used for 2021.
If you should have any questions, please do not hesitate to contact Bryan Lievre with the Water
Quality Regional Operations Section in the Wilmington Regional Office at 910-796-7215 or via email at
bryan.lievre@ncdenr.gov.
ATTACHMENT
Cc: Laserfiche
DocuSigned by:
Sincerely, Ev,1E3ABAl4AC7DC434...
bmYa Sa Alm
Morella Sanchez -King, Regional Supervisor
Water Quality Regional Operations Section
Wilmington Regional Office
Division of Water Resources, NCDEQ
North Carolina Department of Environmental Quality I Division of Water Resources
Wilmington Regional Office 1 127 Cardinal Drive Extension I Wilmington, North Carolina 28405
910.796,7215
DocuSign Envelope ID: 432B866B-6616-4DAO-9917-BCA0263BCCBC
Compliance Inspection Report
Permit: WQ0003468 Effective: 06/01/19 Expiration: 11/30/23 Owner: West Fraser Inc
SOC: Effective: Expiration: Facility: Armour Lumber Mill CLRS
County: Columbus 361 Federal Rd
Region: Wilmington
Riegelwood NC 28456
Contact Person: Thomas G Jordan Title: Phone: 864-229-4413
Directions to Facility:
From the center of Riegelwood, travel 0.6 miles north on State Route 87 and turn left. The plant is approximately 0.9 miles on the
left.
System Classifications:
Primary ORC: Certification: Phone:
Secondary ORC(s):
On -Site Representative(s):
Related Permits:
Inspection Date: 12/06/2021 Entry Time 09:OOAM
Primary Inspector: Bryan Lievre
Secondary Inspector(s):
Tyler G Benson
Reason for Inspection: Routine
Permit Inspection Type: Closed -Loop Recycle
Facility Status: Compliant ❑ Not Compliant
Question Areas:
Miscellaneous Questions Treatment
Treatment Lagoons Storage
(See attachment summary)
Exit Time: 10:30AM
Phone: 910-796-7215
Inspection Type: Compliance Evaluation
Record Keeping
Page 1 of 4
DocuSign Envelope ID: 432B866B-6616-4DA0-9917-BCA0263BCCBC
Permit: WQ0003468 Owner - Facility: West Fraser Inc
Inspection Date: 12/06/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Inspection Summary:
A routine compliance inspection of the West Fraser, Inc., Armour Lumber Mill Closed Loop Recycle System (CLRS), was
performed on December 6, 2021. The purpose of the inspection was to verify that the facility is operating in compliance with
the conditions and limitations specified within Permit W00003468. Emily Blank, Environmental Health & Safety Officer, was
present during the inspection.
According to the current permit which was issued 1/9/2019, became effective 6/1/2019 and expires 11/30/2023, the
wastewater treatment and closed loop recycle facility consists of:
- Two (2) 0.167 million gallon settling basins with freeboard measurement gauges
- A SWACO 414 centrifuge dewatering system
- A 13,000-gallon makeup water tank
- A 300 gallon per day vehicle wash -down area with:
- A sump with a 100 gallon per minute pump
- A grit/sediment trap
- A 1,000 gallon oil/water separator
- A 500 gpm recycle pump; and,
- All associated piping, valves, controls, and appurtenances.
The recycle system receives gravity influent flow from air pollution scrubbers, boiler blowdown, stormwater and effluent from
an oil water separator that treats stormwater and washwater from an equipment washing area. The influent flows into the
two basins (or ponds), which are set up in series to allow for gravity settling of solids. The water can then be recycled back
into the 13,000-gallon makeup water tank for process water or be combined with municipal water supply water back into the
process water stream. Although a centrifuge dewatering system was installed, the unit was found to have been effective but
unable to handle all of the flow to enable the closing of the ash ponds and for this reason, the unit was taken off-line and has
been removed.
Based on the recent site inspection, a process flow diagram was provided on 12/14/2021. Upon review of this information,
additional clarification is needed to understand the process and ascertain any potential affects on the environment Most
noteably, it is uncertain where the water which flows through the softeners re-enters the process flow, where the backwash
water from the softeners is directed and if any additional chemicals might be added to the process water. It should be noted
that the last request was also made following an inspection of the facility by Division staff on November 2, 2013. A review of
our files does not indicate that this information was ever received in response to this request.
A review of monitoring records since the last inspection indicate that the system has not had any reportable incidents or
violations. Ms. Blank was very knowledgeable of the facility and the facility seemed to be well maintained although constant
upkeep is required to deal with corrosive conditions. Records were reviewed and found to be detailed, well organized and
complete. The facility is compliant with the discharge Permit W00003468. Please review the comment sections of the
inspection report for more details.
Page 2 of 4
DocuSign Envelope ID: 432B866B-6616-4DA0-9917-BCA0263BCCBC
Permit: WQ0003468 Owner - Facility: West Fraser Inc
Inspection Date: 12/06/2021 Inspection Type: Compliance Evaluation
Reason for Visit: Routine
Type
Yes No NA NE
Lagoon Spray, LR
❑
Reuse (Quality)
❑
Infiltration System
❑
Activated Sludge Spray, HR
❑
Single Family Spray, LR
❑
Activated Sludge Spray, LR
❑
Single Family Drip
❑
Activated Sludge Drip, LR
❑
Recycle/Reuse
Treatment Yes No NA NE
Are Treatment facilities consistent with those outlined in the current permit? ❑ 0 ❑ ❑
Do all treatment units appear to be operational? (if no, note below.) ❑ 0 ❑ ❑
Comment: On the date of the inspection, the centrifuge dewaterinq system was observed to have been
removed from operation and an oil skimming system had been installed within the vehicle
wash -down area. According to permitting staff in Raleigh, these system alterations amount to
minor modifications to the permit, but should be properly documented.
Record Keeping
Yes No NA NE
Is a copy of current permit available?
0
❑ ❑ ❑
Are monitoring reports present: NDMR?
❑
❑ ❑
NDAR?
❑
❑ ❑
Are flow rates less than of permitted flow?
❑
❑ ❑
Are flow rates less than of permitted flow?
❑
❑ ❑
Are application rates adhered to?
❑
❑ ❑
Is GW monitoring being conducted, if required (GW-59s submitted)?
❑
❑ ❑
Are all samples analyzed for all required parameters?
❑
❑ ❑
Are there any 2L GW quality violations?
❑
❑ ❑
Is GW-59A certification form completed for facility?
❑
❑ ❑
Is effluent sampled for same parameters as GW?
❑
❑ ❑
Do effluent concentrations exceed GW standards?
❑
❑ ❑
Are annual soil reports available?
❑
❑ ❑
# Are PAN records required?
❑
❑ ❑
# Did last soil report indicate a need for lime?
❑
❑ ❑
If so, has it been applied?
❑
❑ ❑
Are operational logs present?
❑ ❑ ❑
Are lab sheets available for review?
❑
❑ ❑
Page 3 of 4
DocuSign Envelope ID: 432B866B-6616-4DA0-9917-BCA0263BCCBC
Permit: WQ0003468 Owner - Facility: West Fraser Inc
Inspection Date: 12/06/2021 Inspection Type: Compliance Evaluation Reason for Visit: Routine
Do lab sheets support data reported on NDMR? ❑ ❑ 0 ❑
Do lab sheets support data reported on GW-59s? ❑ ❑ ❑ ❑
Are Operational and Maintenance records present? 0 ❑ ❑ ❑
Were Operational and Maintenance records complete? 0 ❑ ❑ ❑
Has permittee been free of public complaints in last 12 months? ❑ ❑ ❑
Is a copy of the SOC readily available? ❑ ❑ 0 ❑
No treatment units bypassed since last inspection? ❑ ❑ ❑
Comment: As a closed loop recvcle permitted facilitv, the system does not have anv discharge limits to
adhere to. The staff maintain adequate records within a Fire Inspection Log Book, work
orders, logs of residuals removed, and inspection information of pond levels. Pond levels were
being recorded on a daily basis, however the system is now equipped with electronic liquid
levels for the ponds and make-up tank and this information is recoeded every 10 minutes. The
ponds had a freeboard of approximately six feet on the date of the inspection. Records of
sludge removed from the ponds were also well documented with -1003 tns removed in 3/2021
& -488 tons removed 11/2020 with all sludge brought to Lewis Farms for disposal.
Page 4 of 4