HomeMy WebLinkAboutNC0088765_NOV-2016-PC-0174_20160602 PAT MCCRORY
Gvw
DONALD R. VAN DER VAART
s
WOWResources
64vnrol HOWTAL QUALITY S. JAY ZIMMERMAN
Da lw
Certified Mail # 7012 1010 0002 1965 5617
Return Receipdeguested
May 23, 2016 RECENEDINCDE(IIDWR
Mr. Wayne Smith JUN 01 2016
51 Bridge Street Water Quality
Sylva, North Carolina 28779 Permitting Section
SUBJECT: NOTICE OF VIOLATION and NOTICE OF RECOMMEDATION FOR ENFORCEMENT
Tracking Number: NOV-2016-PC-0174
Permit No. NCO088765
Tinseltown RV Park (AKA Tuckaseegee RV Resort) WWTP
Jackson County
Dear Permittee:
The North Carolina Division of Water Resources conducted a compliance inspection with sampling of the
Tinseltown RV Park(AKATuckaseegee RV Resort)WWTP Facility, located at 78 Wilmont Cemetary Rd, Whittier,
NC 28789 on May 18, 2016. Also present during the inspection was Dale Wike of Environmental, Inc. This
inspection was conducted to verify that the facility is operating in compliance with the conditions
and limitations specified in NPDES WW Permit No. NC0088765.
The facility was found to be non-compliant with the Permit No. NCO088765. The following items
were noted during the inspection and must be corrected in order to comply with Permit NCO088765:
NPDES Standard Permit Conditions:
Section C. Operation and Maintenance of Pollution Controls, 2. Proper Operation and Maintenance:
• Weeds and vegetation have significantly overgrown the facility and must be removed. This presents
both an operational barrier and safety hazard to the ORC and inspector. Institute a regular program for
weed/vegetation control.
• A significant number of the spray nozzles for the synthetic surface media pods were not functioning at
the time of the inspection. Repair the nozzles and perform regular inspection and documentation of the
spray nozzle system.
State of North Carolina I Environmental Quality I Water Resources
2090 U.S.70 Highway,Swannanoa,NC 28778
828-2964500
. permit No. NCO088765
Page 3 of 3
The Deemed Collection System serving Tuckaseegee RV Resort was also inspected concurrent with the WWTP. The
collection system appeared to be well maintained and operated, and compliant with Permit No. WQCSD0451.
If you should have any questions, please do not hesitate to contact Tim Heim with the Water Quality
Regional Operations Section in the Asheville Regional Office at 828-296-4500.
Sincerely,
G. Landon Davidson, P.G., Regional Supervisor
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: Dale Wike, ORC— Environmental Inc.
WQS Asheville Regional Office
NPDES Compliance/Enforcement Unit
\\wp3dnfpo6.eads.ncads.net\data\WR\WQVadcson\Wastewater\Minors\Tinsletown RV Park 88765\NOV-2016-PC-0130 May 2016 CEIS.doa
Permit: NCO088765 Owner•Facility: Tu I<oseegee RV Resort
Inspection Date: 05118/2016 Inspection Type: compliance Sampling
Disinfection - UV Yes No NA NE
Is effluent clear and free of solids? ❑ 0 ❑ ❑
Comment: The UV disinfection system did not appear to be operating at the time of the inspection and
at least one of the lamps was completely disconnected The ORC did not have a way to
regularly check status and function of the lamps Repair the UV system and perform regular
inspection and documentation of the UV disinfection system.
Effluent was discolored and appeared high in TSS. Sample results for fecal coliform
indicated significant exceedance of the permit discharge limits.
Effluent Pipe Yes No NA NE
Is right of way to the ouffall properly maintained? 0 ❑ ❑ ❑
Are the receiving water free of foam other than trace amounts and other debris? 0 ❑ ❑ ❑
If effluent (diffuser pipes are required) are they operating property? M ❑ ❑ ❑
Comment:
Standby Power Yes No NA NE
Is automatically activated standby power available? 0 ❑ ❑ ❑
Is the generator tested by interrupting primary power source? ❑ ❑ ❑ 0
Is the generator tested under load? ❑ ❑ ❑ 0
Was generator tested&operational during the inspection? ❑ 0 ❑ ❑
Do the generator(s)have adequate capacity to operate the entire wastewater site? M ❑ ❑ ❑
Is there an emergency agreement with a fuel vendor for extended run on back-up power? M ❑ ❑ ❑
Is the generator fuel level monitored? ❑ 0 ❑ ❑
Comment: The generator backup power was not functional during the inspection (The ORC was not
able to activate the backup generator)
Perform and document regular testing of the standby power source. Perform repair and
maintenance as needed.
Page# 4