HomeMy WebLinkAboutWQ0017710_Regional Office Historical File Pre 2018State of North Carolina
Department of Environment
and Natural Resources
Division of Water Quality
James B. Hunt, Jr., Governor
Bill Holman, Secretary
Kerr T. Stevens, Director
March 27, 2000
Mr. Jon C. Dyer, Director of Public Works
Union County
400 N. Church Street
Monroe, North Carolina 28111
Dear Mr.. Dyer:
NCDENR
NoRm CAROLINA DEPARTMENT OF
ENV6RONMENT AND NAT -t ► DES
Subject: Permit No. WQ0017710
Union County
Maintenance Facility
Wastewater Collection System.
Union County
Iaccordance with your application received November 23, 1999, and additional information received
February 8, 2000 and March 17, 2000, we are forwarding herewith Permit No. WQ0017710 dated March 27,
2000, to Union County for the construction and operation of the subject wastewater collection extension. This
permit shall be effective from the date of issuance until rescinded and shall be subject to the conditions and
limitations as specified therein.
This permit shall be effective from the date. of issuance until rescinded and shall be subject to the
conditions and lirrutations as specified therein.
If any parts, requirements, or lirrtitatrons contained in this permit are unacceptable, you have the right
to request an adjudicatory hearing upon written request within thirty (30) days following receipt of this permit.
This request must be in the form of a written petition, conforming to Chapter 150E of the North Carolina
General Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service Center, Raleigh, NC
27699-6714. Unless such demands are made this permit shall be final and binding.
One set of approved plans and specifications is being forwarded to you. If you need additional
information concerning this matter, please contact Mr. Bennie Goetze, Jr., P. E. at (919) 733-5083 extension
362.
cc: Union County Health Department
Mooresville Regional Office, Water Quality Section (Twelve Mile Creek WWTP)
Eagle Engineering, Inc
1617 Mail Service Center, Raleigh, North Carolina 27699-1617 Telephone (91
733-5083 Fax (919) 715-6048
An Equal Opportunity Affirmative Action Employer 50% recyclerill 0% post -consumer paper
NORTH CAROLINA
ENVIRONMENTAL MANAGEMENT COMMISSION
DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES
RALEIGH
WASTEWATER COLLECTION PERMIT
In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as amended,
and other applicable Laws, Rules, and Regulations
PERMISSION IS HEREBY GRANTED TO
Union County
Union County
FOR THE
construction and operation of a 32-GPM pump station with duplex pumps, on -site audible and visual high water
alarms, and portable standby generator; and approximately 2,353 linear feet of 2-inch force main to serve the
Union County Maintenance Facility, and the discharge of 6,677 GPD of collected domestic wastewater into the
Union County's existing sewerage system, pursuant to the application received November 23, 1999, and in
conformity with the project plan, specifications, and other supporting data subsequently filed and approved by the
Department of Environment and Natural Resources and considered a part of this permit.
This permit shall be effective from the date of issuance until rescinded and shall be subject to the following
specified conditions and limitations:
l . This permit shall become voidable unless the facilities are constructed in accordance with the conditions of
this permit, the approved plans and specifications, and other supporting data.
2. This permit is effective only with respect to the nature and volume of wastes described in the application
and other supporting data.
3. The facilities must be properly maintained and operated at all times.
4. The sewage and wastewater collected by this system shall be treated in the Union County Twelve Mile
Creek Wastewater Treatment Facility (NPDES Permit No. NC0085359) prior to being discharged into the
receiving stream.
5. This permit is not transferable. In the event there is a desire for the facilities to change ownership, or there
is a name change of the Permittee, a formal permit request must be submitted to the Division of Water
Quality (Division) accompanied by an application fee, documentation from the parties involved, and other
supporting materials as may be appropriate. The approval of this request will be considered on its merits
and may or may not be approved.
6. Construction of the sewers, pump station(s) and force main shall be scheduled so as not to interrupt service
by the existing utilities nor result in an overflow or bypass discharge of wastewater to the surface waters of
the State.
1
r7. Upon completion of construction and prior to operation of this permitted facility, a certification must be
received from a professional engineer certifying that the permitted facility has been installed in accordance
with this permit, the approved plans and specifications, and other supporting materials. If this project is to
be completed in phases and partially certified, you shall retain the responsibility to track further
construction approved under the same permit, and shall provide a final certificate of completion once the
entire project has been completed. Mail the Certification to the Non -Discharge Permitting Unit, 1617 Mail
Service Center, Raleigh, NC 27699-1617.
8. A copy of the approved plans and specifications shall be maintained on file by the Permittee for a minimum
of five years from the date of the completion of construction.
9. FaiIure to abide by the conditions and limitations contained in this permit may subject the Permittee to an
enforcement action by the Division, in accordance with North Carolina General Statute 143-215.6A to 143-
215.6C.
10. The issuance of this permit does not preclude the Permittee from complying with any and all statutes, rules,
regulations, or ordinances which may be imposed by other government agencies (local, state, and federal)
which have jurisdiction.
11. The Permittee shall provide for the pump station and force main the following items:
a. Pump on/off elevations located so that 2-8 pumping cycles may be achieved per hour in the pump
station,
b. An air relief valve located at all high points along the force main,
c. A screened vent for the wet well,
d. Fillets located in the wet well at the intersection of the flooring and sidewalls,
e. Three feet of cover (minimum) over the force main or the use of ferrous material where three feet
cannot be maintained,
f. Sufficient devices which will protect the pump station from vandals, and
g. Flood protection if the pump station is located below the 100-year flood elevation.
12. In the event that the facilities fail to perform satisfactorily, including the creation of nuisance conditions, the
Permittee shall take immediate corrective action, including those as may be required by this Division, such
as the construction of additional or replacement wastewater collection facilities.
13. NONCOMPLIANCE NOTIFICATION:
The Permittee shall report by telephone to the Mooresville Regional Office, telephone number (704) 663-
1699, as soon as possible, but in no case more than 24 hours or on the next working day following the
occurrence or first knowledge of the occurrence of either of the following:
a. Any process unit failure, due to known or unknown reasons, that renders the facility incapable of
adequate wastewater transport, such as mechanical or electrical failures of pumps, line blockage or
breakage, etc.; or
b. Any failure of a pumping station or sewer line resulting in a by-pass directly to receiving waters
without treatment of all or any portion of the influent to such station or facility.
2
Persons reporting such occurrences by telephone shall also file a written report in letter form within five (5)
days following first knowledge of the occurrence. This report must outline the actions taken or proposed to
be taken to ensure that the problem does not recur.
Permit issued this t; e 27th day o March, 2000.
NORTH
AROLIN
ENTAL MANAGEMENT COMMISSION
Kerr T. Stevens, Director
Division of Water Quality
By Authority of the Environmental Management Commission
Permit Number WQ0017710
3
Vt No. WQ0017710
March 27, 2000
ENGINEER'S CERTIFICATION
Partial Final
IF
I, , as a duly registered Professional Engineer in the State of
North Carolina, having been authorized to observe (periodically, weekly, full time) the construction of the project,
Project Name Location and County
for the Permittee hereby state that, to the best of my abilities, due care and diligence was used in the observation
of the construction such that the construction was observed to be built within substantial compliance and intent of
this permit, the approved plans and specifications, and other supporting materials.
Signature Registration No.
Date
4