Loading...
HomeMy WebLinkAboutWQ0042937_Application (FTSE)_20211011DWR Division of Water Resources State of North Carolina Department of Environmental Quality Division of Water Resources 15A NCAC 02T .0300 — FAST TRACK SEWER SYSTEM EXTENSION APPLICATION FTA 04-16 & SUPPORTING DOCUMENTATION Application Number: vti 1Dt?` ckS-1 (to be completed by DWR) All items must be completed or the application will be returned I. APPLICANT INFORMATION: 1. Applicant's name: Orange Water and Sewer Authority (company, municipality, HOA, utility, etc.) 2. Applicant type: ❑ Individual ❑ Corporation ❑ General Partnership ❑ Privately -Owned Public Utility ❑ Federal ❑ State/County ® Municipal ❑ Other 3. Signature authority's name: Todd Taylor per 15A NCAC 02T .0106(b) Title: Executive Director 4. Applicant's mailing address: 400 Jones Ferry Rd n City: Carrboro State: NC Zip: 27510- d 5. Applicant's contact information: v Phone number: (919) 537-4215 Email Address: dkalyanam®a,owasa.org y II. PROJECT INFORMATION: '� o °a' 3 2. Application/Project status: ® Proposed (New Permit) ❑' Existing Permit/Project r t r If a modification, provide the existing permit number: WQ00 and issued date: Q . If new construction but part of a master plan, provide the existing permit number: WQ00 oN 3. County where project is located: Orange 4. Approximate Coordinates (Decimal Degrees): Latitude: 35.91072 Longitude:-79.06886' 5. Parcel ID (if applicable): 9778865048 (Parcel ID to closest downstream sewer: project located in NCDOT right-of-way) (or Parcel ID to closest downstream sewer) 1. Project name: East Main Street Sanitary Sewer Rehabilitation and Replacement - Phase 1 III. CONSULTANT INFORMATION: I. Professional Engineer: Michael Penny License Number: 046994 Firm: McKim & Creed, Inc. V-rt.c Mailing address: 170 Varsity Dr., Suite 500 City: Raleigh State: NC Zip: 27606-2689 Phone number: (919) 233-8091 Email Address: mpenny@mckimcreed.com IV. WASTEWATER TREATMENT FACILITY (WWTF) INFORMATION: I. Facility Name: Mason Farm Wastewater Treatment Plant Permit Number: NC002524.1 Owner Name: Orange Water and Sewer Authority V. RECEIVING DOWNSTREAM SEWER INFORMATION (if different than WWTF): I. Permit Number(s): WQ0031 Downstream (Receiving) Sewer Size: 10 inch System Wide Collection System Permit Numbers) (if applicable): WQCS0031 Owner Name(s): Orange Water and Sewer Authority FORM: FTA 04-16 Page 1 of 5 VI. GENERAL REQUIREMENTS 1, If the Applicant is a Privately -Owned Public Utility, has a Certificate of Public Convenience and Necessity been attached? ❑ Yes ❑No ®N/A 2. If the Applicant is a Developer of lots to be sold, has a Developer's Operational Agreement (FORM: DEV I been attached? ❑ Yes ❑No ®N'A 3. If the Applicant is a Homer'Pro!erty Owners' Association, has an Operational Agreement (FORM; HOA) been attached? ❑ Yes ❑No ®NIA 4. Origin of wastewater: (check all that apply): ❑ Residential Owned ❑ Residential Leased ❑ School ,' preschool / day care ❑ Food and drink facilities ❑ Businesses / offices / factories ❑ Retail (stores, centers, malls) ❑ Retail with food preparation.'service ❑ Medical 1 dental ! veterinary facilities ❑ Church ❑ Nursing Home ❑ Car Wash ❑ Hotel and/or Motels ❑ Swimming Pool ,'Clubhouse ❑ Swimming Pool/Filter Backwash ❑ Other (Explain in Attachment) 5. Nature of wastewater : % Domestic/Commercial % Commercial Industrial (See 15A NCAC 02T .010300)) Is there a Pretreatment Program in effect? 6. Has a flow reduction been approved under I5A NCAC 02T .01 14(t)? ❑ Yes ➢ If yes, provide a copy of flow reduction approval letter 7. Summarize wastewater generated by project: ❑ Yes ❑ No ❑ No Establishment Type (see 02T.0114(f» Daily Design Flow 10 No. of Units Flow gal/ GPD gal/ GPD gal/ GPD gal/ GPD gal/ GPD gal/ G P D Total GPD a See 15A NCAC 02T .01 14(b), (rd), {e)( 1) and (e)(2) for caveats to wastewater design flow rates (i.e., minimum flow per dwelling; proposed unknown non-residential development uses; public access facilities located near high public use areas; and residential property located south or east of the Atlantic Intracoastal Waterway to be used as vacation rentals as defined in G.S. 42A-4). b Per I5A NCAC 02T .0114(c), design flow rates for establishments not identified [in table I 5A NCAC 02T.0114] shall be determined using available flow data, water using fixtures, occupancy or operation patterns, and other measured data. 8. Wastewater generated by project: 0 GPD (per 15A NCAC 02T .01 14) ➢ Do not include future flows or previously permitted allocations If permitted flow is zero, indicate why: ❑ Pump Station or Gravity Sewer where flow will be permitted in subsequent permits that connect to this line ❑ Flow has already been allocated in Permit Number: ❑ Rehabilitation or replacement of existing sewer with no new flow expected ❑ Other (Explain): FORM: FTA 04-16 Page 2 of 5 VII. GRAVITY SEWER DESIGN CRITERIA (1f Applicable) - 02T .0305 & MDC (Gravity Sewers): 1. Summarize gravity sewer to be permitted: Size (inches) Length (feet) Material 12 297 DIP or PVC ➢ Section II & III of the MDC for Permitting of Gravity Sewers contains information related to design criteria ➢ Section III contains information related to minimum slopes for gravity sewer(s) ➢ Oversizing lines to meet minimum slope requirement is not allowed and a violation of the MDC VIII. PUMP STATION DESIGN CRITERIA (If Applicable) — 02T .0305 & MDC (Pump Stations/Force Mains): COMPLETE FOR EACH PUMP STATION INCLUDED IN THIS PROJECT I. Pump station number or name: 2. Approximate Coordinates (Decimal Degrees): Latitude: Longitude: - 3. Design flow of the pump station: millions gallons per day (firm capacity) 4. Operational point(s) of the pump(s): gallons per minute at feet total dynamic head (TDH) 5. Summarize the force main to be permitted (for this Pump Station): Size (inches) Length (feet) Material 6. Power reliability in accordance with 15A NCAC 02T ,0305(h)(1): ❑ Standby power source or pump with automatic activation and telemetry - 15A NCAC 02T .0305(h)(1)(B) > Required for all pump stations with an average daily flow greater than or equal to 15,000 gallons per day > Must be permanent to facility Or if the pump station has an average daily flow less than 15,000 gallons per day: ❑ Portable power source with manual activation, quick -connection receptacle and telemetry - 15A NCAC 02T .0305(h)(1)(C) or ❑ Portable pumping unit with plugged emergency pump connection and telemetry - i 5A NCAC 02T .0305(h)(1)(C): > It shall be demonstrated to the Division that the portable source is owned or contracted by the applicant (draft agreement) and is compatible with the station. ➢ If the portable power source or pump is dedicated to multiple pump stations, an evaluation of all the pump stations' storage capacities and the rotation schedule of the portable power source or pump, including travel timeframes, shall be provided in the case of a multiple station power outage. FORM: FTA 04-16 Page 3 of 5 IX. SETBACKS & SEPARATIONS — (02B .0200 & 15A NCAC 02T .0305(f)): 1. Does the project comply with all separations found in 15A NCAC 02T .0305(f) & (g$ ➢ I5A NCAC 02T.0305(f) contains minimum separations that shall be provided for sewer systems: Yes ❑ No Setback Parameter* Separation Required Storm sewers and other utilities not listed below (vertical) 24 inches Water mains (vertical -water over sewer including in benched trenches) 18 inches Water mains (horizontal) 10 feet Reclaimed water lines (vertical - reclaimed over sewer) 18 inches Reclaimed water lines (horizontal - reclaimed over sewer) 2 feet **Any private or public water supply source, including any wells, WS-I waters of Class 1 or Class 1I impounded reservoirs used as a source of drinking water 100 feet **Waters classified WS (except WS-I or WS-V), B, SA, ORW, HQW, or SB from normal high water (or tide elevation) and wetlands (see item IX.2) 50 feet **Any other stream, lake, impoundment, or ground water lowering and surface drainage ditches 10 feet Any building foundation 5 feet Any basement 10 feet Top slope of embankment or cuts of 2 feet or more vertical height 10 feet Drainage systems and interceptor drains 5 feet Any swimming pools 10 feet Final earth_srade (vertical) 36 inches > 15A NC AC 02T.0305(g) contains alternatives where separations in 02T.0305(f) cannot be achieved. ➢ **Stream classifications can be identified using the Division's NC Surface Water Classifications webpage > If noncompliance with 02T.0305(1) or (g), see Section X of this application 2. Does the project comply with separation requirements for wetlands? (50 feet of separation) ❑ Yes ❑ No ®N; A ➢ See the Division's draft separation requirements for situations where separation cannot be meet ➢ No variance is required if the alternative design criteria specified is utilized in design and construction ➢ As built documents should reference the location of areas effected 3. Does the project comply with setbacks found in the river basin rules per 15A NCAC 02B .0200? ❑ Yes ❑ No ® NA ➢ This would include Trout Buffered Streams per 15A NCAC 2B.0202 4. Does the project require coveragerauthorization under a 404 Nationwide or individual permits or 401 Water Quality Certifications? ➢ Information can be obtained from the 401 & Buffer Permitting Branch ❑ Yes ®No 5. Does project comply with 15A NCAC 02T.0105(c)(6) (additional permits.'certifications)? ® Yes ❑ No Per 15A NCAC 02T.0105(c)(61, directly related environmental permits or certification applications are being prepared, have been applied for, or have been obtained. Issuance of this permit is contingent on issuance of dependent permits (erosion and sedimentation control plans, stormwater management plans, etc.). 6. Does this project include any sewer collection lines that are deemed "high -priority?" Per 15A NCAC 02T.0402, "high -priority sewer" means "any aerial sewer, sewer contacting surface waters, siphon, or sewer positioned parallel to streambanks that is subject to erosion that undermines or deteriorates the sewer. ❑ Yes ❑ No ® NA ➢ If yes, include an attachment with details for each line, including type (aerial line, size, material, and location). High priority lines shall be inspected by the permittee or its representative at least once every six -months and inspections documented per 15A NCAC 02T.0403(a)(5) or the permitee's individual System -Wide Collection permit. FORM: FTA 04-16 Page 4 of 5 X. CERTIFICATIONS: 1. Does the submitted system comply with I5A NCAC 02T, the Minimum Design Criteria for the Permitting of Pump Stations and Force Mains (latest version). and the Gravity Sewer Minimum Design Criteria (latest version) as applicable? ® Yes ❑ No If No, complete and submit the Variance/Alternative Design Request application (VADC 10-14) and supporting documents for review. Approval of the request is required prior to submittal of the Fast Track Application and supporting documents. 2. Professional Engineer's Certification: 4104110.,-p,f' Jy I, (Professional Engineer's name from Application Item II1.1.) attest that this application for has been reviewed by me and is accurate, complete and consistent with the information supplied in the plans, specifications, engineering calculations, and all other supporting documentation to the best of my knowledge. I further attest that to the best of my knowledge the proposed design has been prepared in accordance with the applicable regulations, Gravity Sewer Minimum Design Criteria for Gravity Sewers (latest version), and the Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains (latest version). Although other professionals may have developed certain portions of this submittal package, inclusion of these materials under my signature and seal signifies that 1 have reviewed this material and have judged it to be consistent with the proposed design. NOTE - In accordance with General Statutes 143-215.6A and I43-215.6B, any person who knowingly makes any false statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may include a fine not to exceed $10,000, as well as civil penalties up to $25,000 per violation. North Carolina Professional Engineer's seal, signature, and date: +,,,,lf7'F i,,,r SEAL 046994 7/3o/Zo?i ' 1 r ';qEL D-frrt" 3. Applicant's Certification per 15A NCAC 02T .0106(b): Vi attest that this application for (Signature Authority's name & title from Application Item 1.3.) has been reviewed by me and is accurate and complete to the best of my knowledge. 1 understand that if all required parts of this application are not completed and that if all required supporting documentation and attachments are not included, this application package is subject to being returned as incomplete. 1 understand that any discharge of wastewater from this non - discharge system to surface waters or the land will result in an immediate enforcement action that may include civil penalties, injunctive relief, and/or criminal prosecution. 1 will make no claim against the Division of Water Resources should a condition of this permit be violated. I also understand that if all required parts of this application package are not completed and that if all required supporting information and attachments are not included, this application package will be returned to me as incomplete. NOTE - In accordance with General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per violation, Signature: Date: i 124.s2-1 FORM: FTA 04-16 Page 5 of 5 DESIGN NARRATIVE FOR FAST TRACK SANITARY SEWER PERMIT ORANGE WATER AND SEWER AUTHORITY EAST MAIN STREET SANITARY SEWER REHABILITATION AND REPLACEMENT — PHASE 1 400 Jones Ferry Rd Carrboro, North Carolina 27510 M&C Project # 01519-0055 October 2021 Prepared by: v McKEM&CREED ENGINFFRS SURVEYORS PIANNFRS Michael Penny, PE McKim & Creed, Inc. 1730 Varsity Drive, Suite 500 Raleigh, NC 27606 P: 919 233-8091 DESIGN NARRATIVE 1.0 PROJECT DESCRIPTION The East Main Street Sanitary Sewer Rehabilitation and Replacement Phase 1 project involves the removal and replacement of seven (7) sanitary sewer pipes, two (2) sanitary sewer pipe point repairs, eight (8) manhole replacements, and two (2) new manhole installations. The Orange Water and Sewer Authority (OWASA) recently performed CCTV inspections of existing sanitary sewer collection system in downtown Carrboro and Chapel Hill, identifying that several pipeline segments are at a critical risk of failure. The project includes impacts to the following NCDOT roads: E Main St (SR 1010) and N Greensboro St (SR 1772)/S Greensboro St (SR 1919). 2.0 EXISTING SYSTEM Preliminary review of CCTV inspections, record drawings, and GIS data for this portion of OWASA's sanitary sewer collection system revealed that pipe diameters range between 8- and 10-inches; pipe materials consist of ductile iron, vitrified clay, reinforced concrete, and CIPP- lined segments of ductile iron or reinforced concrete; and pipe age ranges from the 1920s to the 2010s. The project area involves impacts to the following streets: E Main St (NCDOT-owned), Greensboro St (NCDOT-owned), E Weaver St, W Rosemary St, and Lloyd St. The downstream receiving sewer is 10-inch and permitted under #WQ0031. 3.0 PROPOSED ADDITIONS The proposed construction will involve the dig/replacement of 1,275 linear feet of 8-inch sanitary sewer pipe with 8-inch ductile iron pipe, along with approximately 36 linear feet of 8- inch point repairs. Based on email communication with NCDEQ (see attached), this rehabilitation does not require permitting because the sewer is being replaced with the same size and horizontal/vertical alignment. It should be noted that, based on OWASA's Master Plan by CDM Smith, OWASA has indicated that upsizing these sanitary sewer mains for additional capacity will not be necessary. One pipeline segment, which is an existing 10-inch DIP, will be upsized to 12-inch. The increase in diameter is due to current market conditions with material shortages coupled with the fact that 10-inch is an uncommon pipe size. Since additional flow is not being added, and the upsizing is being conducted to install a more common pipe size, the sewer mains downstream do not require upsizing. ouosblivo Mow H 1:1 • -01309a103 3o trio) is aoKri Lair 114 be w J Install New 4' Precast MH 0 2 1n • o co 9ill IZ U Q a) is "O a cLI cc o • c e a) a) Ix 0 Dig and Replace w/ 8" DIP Paint Repair w/ 8" DIP _, wx 1 4 I 1 inch = 200 feet mow• CIJ ISS r-1 4J E dJ ✓ es C4 0 O .r, rl rl �br �*I ICI 3 a• � aJ w Carrboro-Chapel Hill, NC fAu i'•fs" 1tf4 r/ f 4'v11 ai+d��S wiFFY{+EitrYLR6INtrgeltiiVilbb fA015i0.1 1A ♦3 b 7. FF • 2USGS U.S OEPARTMEHT OF THE INTERION u.S. ilaofACAL suRrr. ro n Ft* el4.1.41 .s W•w 4n10M4t1 f rwl 7] 73 7. ry SCALE 1:71 Opp Y ▪ Mt I FIAPEL HILL CHAPEL HILL QUADRANGLE MONTH uRK.M. ,}MMT MRCS 4.Rwa.t.ar. CHAPEL HILL, NC 7Y31 11 11 13 1i ]♦ 74 7s UI IIQNQIi00111 Venture IV Building 1730 Varsity Drove Raleigh, NC 27606 919.233.8091 Fax 9 19.233.803 3 w w w. m e kt in c r e e d.co rn McKIM&CREED NC Dept of Environmental Quality OCT 1 1 2021 ENGINEERS SURVEYORS PLANNERS October 11, 2021 M&C 01519-0055 NCDEQ Water Quality Section 3800 Barrett Drive Raleigh, NC 27609 Raleigh Regional Office RE: Orange Water and Sewer Authority East Main Street Sanitary Sewer Rehabilitation and Replacement — Phase 1 Fast Track Sewer System Extension Application To Whom It May Concern: We respectfully submit this application for a Fast Track Sewer System Extension Application on behalf of OWASA for the subject project. The East Main Street Sanitary Sewer Rehabilitation and Replacement — Phase 1 project involves the removal and replacement of sanitary sewer main and manholes in the existing collection system in downtown Carrboro and Chapel Hill, identified as in disrepair or at critical risk of failure from CCTV and manhole inspection surveys. The project will involve the removal and replacement of the following: seven (7) sanitary sewer pipes, two (2) sanitary sewer pipe point repairs, eight (8) manhole replacements, and two (2) new manhole installations. While only one pipe segment is being upsized and requires permitting, all replacement and rehabilitation work for the project is included in this submittal. Included in this submittal are two copies (one original, one copy) of the following documentation: • Fast Track Application (Form: FTA 04-16) • USGS Quad Map and Aerial Map • Project Narrative • Full size set of final design plans and specifications • Check No. 13932 in the amount of $480.00 Please do not hesitate to contact me should you have any questions or concerns. We appreciate your time and consideration regarding this matter. Sincerely, McKIM & CREED, INC. /(eifpri- Michael Penny, P.E. Project Engineer cc: Deepthi Kalyanam, OWASA Adam Paukovich, McKim & Creed NC Dept of Environmental Quality OCT i 1 2021 Raleigh Regional Office L' 01519',0055 , ENGAO-Permit ',JS-DELI, DER, DOT, etc , WW Perm b..01 2021.10.11 Cocer Letter Ior Submittal.doc