HomeMy WebLinkAboutNC0073539_Compliance Evaluation Inspection_20211122ROY COOPER Governor ELIZABETH S. BISER Secretary S. DANIEL SMITH Director Shannon Becker, President Aqua North Carolina, Inc. 202 MacKenan Court Cary, North Carolina 27511 Dear Mr. Becker: NORTH CAROLINA Environmental Quality November 22, 2021 Subject: Compliance Evaluation Inspection Willowbrook Subdivision WWTP NPDES Permit No. NC0073539 Mecklenburg County Enclosed is a copy of the Compliance Evaluation Inspection (CEI) Report for the inspection conducted at the subject facility on November 16, 2021, by Mr. Wes Bell of this Office. Please advise the facility's Operator -in -Responsible Charge (ORC) of our findings by forwarding a copy of the enclosed report. Should you have any questions concerning this report, please do not hesitate to contact Mr. Bell at (704) 235-2192, or via email at wes.bell@ncdenr.gov. Enclosure: Inspection Report NORTH Dep®rlmont of Environmental Onolit Sincerely, DocuSigned by: A w H Nut4 F161 FB69A2D84A3... fo r W. Corey Basinger, Regional Supervisor Water Quality Regional Operations Section Division of Water Resources, NCDEQ North Carolina Department of Environmental Quality 1 Division of Water Resources Mooresville Regional Office 1610 East Center Avenue, Suite 301 I Mooresville, North Carolina 28115 704.663.1699 United States Environmental Protection Agency EPA Washington, D.C. 20460 Water Compliance Inspection Report Form Approved. OMB No. 2040-0057 Approval expires 8-31-98 Section A: National Data System Coding (i.e., PCS) Transaction Code 1 IN I 2 IL 21 1 1 1 1 1 NPDES yr/mo/day Inspection I 3 I NC0073539 111 121 21/11/16 I17 Type 1810I I I 1 1 1 Inspector Fac Type 191 S I 2011 1 1 1 1 11 1 1 1 I I I 1 1 1 1 1 1 I I I I I 1 11 1 1 1 I 1 P6 Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved 67I2.0 I 70I4 I 71IN I 72 I N I 73I 1 74 751 I I 1 I I I I I I 180 l Section B: Facility Data Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include POTW name and NPDES permit Number) Willowbrook Subdivision WWTP 12309 Ramah Creek Ct Huntersville NC 28078 Entry Time/Date 12:25PM 21/11/16 Permit Effective Date 19/02/01 Exit Time/Date 02:15PM 21/11/16 Permit Expiration Date 23/11/30 Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s) /// Daniel G Wimpey/ORC/337-215-1165/ Other Facility Data Name, Address of Responsible Official/Title/Phone and Fax Number Contacted Shannon V Becker,202 Mackanan Ct Cary NC 275116447//919-653-5570/ No Section C: Areas Evaluated During Inspection (Check only those areas evaluated) Permit Flow Measurement Operations & Maintenar Records/Reports Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate Laboratory Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) (See attachment summary) Name(s) and Signature(s) Wes Bell of Inspector(s) Agency/Office/Phone and Fax Numbers Date -Docusiyned by: DWR/MRO WQ/704-663-1699 Ext.2192/ 11/22/2021 "-A61696D90CC3437... Signature of Ma Andrew Pitn RvenliOsell Reviewer Agency/Office/Phone and Fax Numbers Date rA444144' H P 3WR/MRO WQ/704-663-1699 Ext.2180/ 11.22.21 F161 FB69A2D84A3... EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete. Page# 1 NPDES yr/mo/day 31 NC0073539 111 121 21/11/16 I17 Inspection Type 18 [j 1 Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) Page# 2 Permit: NC0073539 Inspection Date: 11/16/2021 Owner - Facility: Willowbrook Subdivision WWTP Inspection Type: Compliance Evaluation Permit Yes No NA NE (If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ •❑ application? Is the facility as described in the permit? • ❑ ❑ ❑ # Are there any special conditions for the permit? ❑ ❑ • ❑ Is access to the plant site restricted to the general public? • ❑ ❑ ❑ Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑ Comment: Overall, the facility is adequately described in the Permit; however, the description does not include an aerated flow equalization tank. The facility description should be updated to include the equalization tank during the next permit renewal process. The last compliance evaluation inspection at this facility was performed by DWR staff on 9/25/19. Record Keeping Yes No NA NE Are records kept and maintained as required by the permit? • ❑ ❑ ❑ Is all required information readily available, complete and current? • ❑ ❑ ❑ Are all records maintained for 3 years (lab. reg. required 5 years)? • ❑ ❑ ❑ Are analytical results consistent with data reported on DMRs? • ❑ ❑ ❑ Is the chain -of -custody complete? • ❑ ❑ ❑ Dates, times and location of sampling • Name of individual performing the sampling • Results of analysis and calibration • Dates of analysis • Name of person performing analyses • Transported COCs ■ Are DMRs complete: do they include all permit parameters? • ❑ ❑ ❑ Has the facility submitted its annual compliance report to users and DWQ? ❑ ❑ • ❑ (If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified ❑ ❑ • ❑ operator on each shift? Is the ORC visitation log available and current? • ❑ ❑ ❑ Is the ORC certified at grade equal to or higher than the facility classification? • ❑ ❑ ❑ Is the backup operator certified at one grade less or greater than the facility • ❑ ❑ ❑ classification? Is a copy of the current NPDES permit available on site? • ❑ ❑ ❑ Facility has copy of previous year's Annual Report on file for review? ❑ ❑ • ❑ Page# 3 Permit: NC0073539 Inspection Date: 11/16/2021 Owner - Facility: Willowbrook Subdivision WWTP Inspection Type: Compliance Evaluation Record Keeping Yes No NA NE Comment: The records reviewed during the inspection were organized and well maintained. Discharge monitoring reports (eDMRs) were reviewed for the period October 2020 through September 2021. No effluent limit and/or monitoring violations were reported. Laboratory Are field parameters performed by certified personnel or laboratory? Are all other parameters(excluding field parameters) performed by a certified lab? # Is the facility using a contract lab? # Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)? Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ Comment: On -site effluent field analyses (dissolved oxygen, pH, temperature and total residual chlorine) are performed under the Aqua NC's field laboratory certification #5035. Water Tech Labs (Certification #50) has been contracted to provide analytical support. The ORC must ensure all future calibration logs have the meter serial numbers listed. In addition, the ORC must ensure the theoretical DO is documented (for comparison) during all future DO calibration/verification events. A copy of the NC Wastewater/Groundwater Laboratory Certification approved procedure for the analysis/calibration of DO has been emailed to the ORC for reference. Effluent Sampling Yes No NA NE Is composite sampling flow proportional? • ❑ ❑ ❑ Is sample collected below all treatment units? • ❑ ❑ ❑ Is proper volume collected? • ❑ ❑ ❑ Is the tubing clean? ■ ❑ El El # Is proper temperature set for sample storage (kept at less than or equal to 6.0 • El El El degrees Celsius)? Is the facility sampling performed as required by the permit (frequency, sampling type • ❑ El El representative)? Comment: The subject permit requires effluent composite and grab samples. Upstream / Downstream Sampling Yes No NA NE Is the facility sampling performed as required by the permit (frequency, sampling type, • El El El and sampling location)? Comment: Operations & Maintenance Is the plant generally clean with acceptable housekeeping? Yes No NA NE Page# 4 Permit: NC0073539 Inspection Date: 11/16/2021 Owner - Facility: Willowbrook Subdivision WWTP Inspection Type: Compliance Evaluation Operations & Maintenance Yes No NA NE Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑ Solids, pH, DO, Sludge Judge, and other that are applicable? Comment: The wastewater treatment facility appeared to be properly operated and well maintained. Process control measurements were being documented and maintained on -site. Equalization Basins Is the basin aerated? Is the basin free of bypass lines or structures to the natural environment? Is the basin free of excessive grease? Are all pumps present? Are all pumps operable? Are float controls operable? Are audible and visual alarms operable? # Is basin size/volume adequate? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Comment: The telemetry type alarm system (high water) was operational during the on -site test. Bar Screens Type of bar screen a.Manual b.Mechanical Are the bars adequately screening debris? Is the screen free of excessive debris? Is disposal of screening in compliance? Is the unit in good condition? Yes No NA NE • • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Comment: The old bar screen has been removed. Screenings are transported and disposed into the dumpster located at the Hwy. 150/River Park WWTP. The dumpster contents are disposed at a permitted landfill. Aeration Basins Yes No NA NE Mode of operation Ext. Air Type of aeration system Diffused Is the basin free of dead spots? • ❑ ❑ ❑ Are surface aerators and mixers operational? ❑ ❑ • ❑ Are the diffusers operational? • ❑ ❑ ❑ Page# 5 Permit: NC0073539 Inspection Date: 11/16/2021 Owner - Facility: Willowbrook Subdivision WWTP Inspection Type: Compliance Evaluation Aeration Basins Yes No NA NE Is the foam the proper color for the treatment process? Does the foam cover less than 25% of the basin's surface? Is the DO level acceptable? Is the DO level acceptable?(1.0 to 3.0 mg/I) • II El El El • ❑ ❑ ❑ ❑ ❑ ❑ Comment: Soda ash is added on an as -needed basis to maintain appropriate alkalinity/pH levels. Secondary Clarifier Is the clarifier free of black and odorous wastewater? Is the site free of excessive buildup of solids in center well of circular clarifier? Are weirs level? Is the site free of weir blockage? Is the site free of evidence of short-circuiting? Is scum removal adequate? Is the site free of excessive floating sludge? Is the drive unit operational? Is the return rate acceptable (low turbulence)? Is the overflow clear of excessive solids/pin floc? Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) Yes No NA NE • ❑ ❑ ❑ ❑ ❑ • ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Comment: A significant amount of floating solids was observed in the clarifier; however, the solids were being contained in the clarifier and not entering the effluent. Disinfection -Tablet Yes No NA NE Are tablet chlorinators operational? • El ❑ ❑ Are the tablets the proper size and type? • El El El Number of tubes in use? 3 Is the level of chlorine residual acceptable? • El El El Is the contact chamber free of growth, or sludge buildup? • El El El Is there chlorine residual prior to de -chlorination? • El El El Comment: Calcium hypochlorite tablets were used for disinfection. Flow Measurement - Effluent # Is flow meter used for reporting? Is flow meter calibrated annually? Yes No NA NE Page# 6 Permit: NC0073539 Inspection Date: 11/16/2021 Owner - Facility: Willowbrook Subdivision WWTP Inspection Type: Compliance Evaluation Flow Measurement - Effluent Is the flow meter operational? (If units are separated) Does the chart recorder match the flow meter? Yes No NA NE • ❑ ❑ ❑ Comment: The flow meter is calibrated annually and was last calibrated by Aqua N.C. staff on 1/27/21. De -chlorination Yes No NA NE Type of system ? Tablet Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ • ❑ Is storage appropriate for cylinders? El El • El # Is de -chlorination substance stored away from chlorine containers? • El El El Comment: Are the tablets the proper size and type? Are tablet de -chlorinators operational? Number of tubes in use? 4 • ❑ ❑ ❑ ▪ ❑ ❑ ❑ Comment: Sodium Sulfite tablets were used for dechlorination. Post aeration is provided following dechlorination. Effluent Pipe Is right of way to the outfall properly maintained? Are the receiving water free of foam other than trace amounts and other debris? If effluent (diffuser pipes are required) are they operating properly? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ ❑ ❑ • ❑ Comment: The effluent appeared clear with no floatable solids or foam. The receiving stream did not appear to be negatively impacted. Aerobic Digester Yes No NA NE Is the capacity adequate? • El El El Is the mixing adequate? • El El El Is the site free of excessive foaming in the tank? • El El El # Is the odor acceptable? • El El El # Is tankage available for properly waste sludge? • El El El Comment: Wastewater solids are removed by a contracted company (Lake Norman Sewer & Septic Services). Standby Power Is automatically activated standby power available? Yes No NA NE Page# 7 Permit: NC0073539 Inspection Date: 11/16/2021 Owner - Facility: Willowbrook Subdivision WWTP Inspection Type: Compliance Evaluation Standby Power Is the generator tested by interrupting primary power source? Is the generator tested under load? Was generator tested & operational during the inspection? Do the generator(s) have adequate capacity to operate the entire wastewater site? Is there an emergency agreement with a fuel vendor for extended run on back-up power? Is the generator fuel level monitored? Yes No NA NE • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ • ❑ ❑ ❑ Comment: The backup generator is tested weekly (automatically) and placed under load semi-annually (at a minimum). Managed Generator Services has been contracted to service the generator annually. Page# 8