Loading...
HomeMy WebLinkAboutWQ0031988_Regional Office Historical File Pre 2018Michael F. Easley, Governor William G. Ross Jr., Secretary North Carolina Department of Environment and Natural Resources Coleen Sullins, Director Division of Water Quality July 24, 2007 Mr. Eric Davis, Town Manager Town of China Grove • 305 Swink Street China Grove, NC 28023 Subject: Permit No. WQ0031988 Millers Grant Subdivision Wastewater Collection System Extension Rowan County, North Carolina Dear Mr. Davis, In accordance with your application received on July 12, 2007, we are forwarding herewith Permit No. WQ0031988, dated July 24, 2007, to the Town of China Grove for the construction and operation of the subject wastewater collection system extension. This permit shall be effective from the date of issuance until rescinded, and shall be subject to the conditions and limitations as specified therein. This cover letter shall be considered a part of this permit and is therefore incorporated therein by reference. Please pay particular attention to Permit Condition 3 which requires that the wastewater collection facilities be properly operated and maintained in accordance with 15A NCAC 2T .0403 or any individual system -wide collection system permit issued to the Permittee. Permitting of this project does not constitute an acceptance of any part of the project that does not meet 1) 15A NCAC 2T; 2) the Division of Water Quality's (Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996, as applicable; 3) and the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000, as applicable, unless specifically mentioned herein. Division approval is based on acceptance of the certification provided by a North Carolina -licensed Professional Engineer in the application. It shall be the Permittee's responsibility to ensure that the as -constructed project meets the appropriate design criteria and rules. Failure to comply may result in penalties in accordance with North Carolina General Statute §143-215.6A through §143-215.6C, construction of additional or replacement wastewater collection facilities, and/or referral of the North Carolina -licensed Professional Engineer to the licensing board. Mooresville Regional Office 610 East Center Ave., Suite 301 Mooresville, NC 28115 Phone: (704) 663-1699 Fax: (704) 663-6040 Internet: www.ncmwaterquality.org Customer Service: 1-877-623-6748 An Equal Opportunity/Affirmative Action Employer— 50% Recycled/10% Post Consumer Paper No ` 2VaCaro ina turaij rJuly Mr. Davis Page 2 24, 2007 In accordance with the provisions of Article 21 of Chapter 143, General Statutes of North Carolina as amended, and other applicable Laws, Rules, and Regulations, permission is hereby granted for the construction and operation of approximately 5,930 linear feet of 8-inch gravity sewer and the discharge of 41,760 gallons per day of collected domestic wastewater into the City of Salisbury existing sewerage system, pursuant to the application received July 12, 2007, and in conformity with 15A NCAC 2T; the Division's Gravity Sewer Minimum Design Criteria adopted February 12, 1996, as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000, as applicable; and other supporting data subsequently filed and approved by the Department of Environment and Natural Resources and considered a part of this permit. The sewage and wastewater collected by this system shall be treated in the City of Salisbury WVVi'P (NPDES No. NC0023884) prior to being discharged into the receiving stream. If any parts, requirements, or limitations contained in this permit are unacceptable, you have the right to request an adjudicatory hearing upon written request within 30 days following receipt of this permit. This request must be in the form of a written petition, conforming to Chapter 150B of North Carolina General Statutes, and filed with the Office of Administrative Hearings, 6714 Mail Service Center, Raleigh, NC 27699-6714. Unless such demands are made, this permit shall be final and binding. If you need additional information concerning this matter, please contact Dee Browder at (704) 663-1699. Sincerely, IC -- for Coleen H. Sullins cc: Mooresville Regional Office, Collection System Permit File David Treme, City of Salisbury Paul Campbell, NorthEast Engineering, PA Surface Water Protection Central Files Tom Asenzo, PERCS NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES RALEIGH WASTEWATER COLLECTION SYSTEM EXTENSION PERMIT This permit shall be effective from the date of issuance until rescinded and shall be subject to the following specified conditions and limitations: 1. This permit shall become voidable unless the wastewater collection facilities are constructed in accordance with the conditions of this permit; 15A NCAC 2T; the Division of Water Quality's (Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996, as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000, as applicable; and other supporting materials unless specifically mentioned herein. 2. This permit shall be effective only with respect to the nature and volume of wastes described in the application and other supporting data. 3. The wastewater collection facilities shall be properly maintained and_operatedat all times_The Permittee shall maintain compliance with an individual system -wide collection system permit for the operation and maintenance of these facilities as required by 15A NCAC 2T .0403. if an individual permit is not required, the following performance criteria shall be met as provided in 15A NCAC 2T .0403: a. The sewer system shall be effectively maintained and operated at all times to prevent discharge to land or surface waters, and any contravention of the groundwater standards in 15A NCAC 2L .0200 or the surface water standards in 15A NCAC 2B .0200. b. A map of the sewer system shall be developed and shall be actively maintained. c. An operation and maintenance plan shall be developed and implemented. d. Pump stations that are not connected to a telemetry system shall be inspected every day (i.e. 365 days per year). Pump stations that are connected to a telemetry system shall be inspected at least once per week. e. High -priority sewer lines shall be inspected at least once per every six-month period of time. f. A general observation of the entire sewer system shall be conducted at least once per year. g. Inspection and maintenance records shall be maintained for a period of at least three years. h. Overflows and bypasses shall be reported to the appropriate Division regional office in accordance with 15A NCAC 2B .0506(a), and public notice shall be provided as required by North Carolina General Statute §143-215.1C. 1 4. This permit shall not be transferable. In the event there is a desire for the wastewater collection facilities to change ownership, or there is a name change of the Permittee, a formal permit request shall be submitted to the Division accompanied by documentation from the parties involved, and other supporting materials as may be appropriate. The approval of this request shall be considered on its merits and may or may not be approved. 5. Construction of the gravity sewers, pump stations, and force mains shall be scheduled so as not to interrupt service by the existing utilities nor result in an overflow or bypass discharge of wastewater to the surface waters of the State. 6. Per 15A NCAC 2T .0116, upon completion of construction and prior to operation of these permitted facilities, the completed Engineering Certification form attached to this permit shall be submitted with the required supporting documents to the address provided on the form. A complete certification is one where the form is fully executed and the supporting documents are provided as applicable. 7. A copy of the construction record drawings shall be maintained on file by the Permittee for the life of the wastewater collection facilities. 8. Failure to abide by the conditions and limitations contained in this permit; 15A NCAC 2T; the Division's Gravity Sewer Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Station and Force Mains adopted June 1, 2000 as applicable; and other supporting materials may subject the Permittee to an entorcement action by the Division, in accordance with North Carolina General Statutes §143- 215.6A through §143-215.6C. 9. In the event that the wastewater collection facilities fail to perform satisfactorily, including the creation of nuisance conditions, the Permittee shall take immediate corrective action, including those as may be required by this Division, such as the construction of additional or replacement facilities. 10. The issuance of this permit shall not exempt the Permittee from complying with any and all statutes, rules, regulations, or ordinances that may be imposed by other government agencies (local, state and federal) which have jurisdiction, including but not limited to applicable river buffer rules in 15A NCAC 2B .0200, erosion and sedimentation control requirements in 15A NCAC Ch. 4 and under the Division's General Permit NCG010000, and any requirements pertaining to wetlands under 15A NCAC 2B .0200 and 15A NCAC 2H .0500. 11. Noncompliance Notification: The Permittee shall verbally report to a Division of Water Quality employee at the Mooresville Regional Office, telephone number (704) 663-1699, as soon as possible, but in no case more than 24 hours or on the next working day, following the occurrence or first knowledge of the occurrence of either of the following: a. Any process unit failure, due to known or unknown reasons, that renders the facility incapable of adequate wastewater transport, such as mechanical or electrical failures of pumps, line blockage or breakage, etc.; or b. Any failure of a pumping station or sewer line resulting in a by-pass directly to receiving waters without treatment of all or any portion of the influent to such station or facility. 2 Voice mail messages or faxed information is permissible, but shall not be considered as the initial verbal report. Overflows and spills occurring outside normal business hours may also be reported to the Division of Emergency Management at telephone number (800) 858-0368 or (919) 733-3300. Persons reporting any of the above occurrences shall file a spill report by completing Part I of Form CS-SSO (or the most current Division approved form), within five days following first knowledge of the occurrence. This report shall outline the actions taken or proposed to ensure that the problem does not recur. Part it of Form CS-SSO (or the most current Division approved form) can also be completed to show that the SSO was beyond control. Permit issued this the 24th day of July, 2007. NORTH CAROLINA ENVIRONMENTAL MANAGEMENT COMMISSION for Coleen H. Sullins, Director Division of Water Quality By Authority of the Environmental Management Commission Permit Number WQ0031988 3 ast Track Engineering Certification ermit No. WQ0031988 July 24, 2007 Owner/WQCS WWTP/WQCS Eric Davis, Town Manager David Treme Town of China Grove City of Salisbury 305 Swink Street 217 South Main Street China Grove, NC 28023' Salisbury, NC 28145 PE Paul Campbell NorthEast Engineering, PA PO Box 931 Concord, NC 28026 Complete and submit this form to the permit issuing regional office with the following: • One copy of the project record drawings (plan & profile views of sewer lines) of the wastewater collection system extension • Supporting design calculations (selected pumps, system curve, operating point, available storage if portable generator(s) or storage greater than longest past three year outage reliability option selected) for any pump stations permitted as part of this project • Changes to the project should be clearly identified on the record drawings or in written summary form. Permit modifications are required for any changes resulting in non-compliance with this permit, regulations or minimum design criteria. This project shall not be considered complete nor allowed to operate until this Engineer's Certification and all required supporting documentation have been received by the Division. Therefore, it is highly recommended that this certification be sent in a manner that provides proof of receipt by the Division. ENGINEER'S CERTIFICATION Partial 11 Final , as a duly registered Professional Engineer in the State of North Carolina, having been authorized to observe (❑ periodically, ❑ weekly, ❑ full time) the construction of Miller Grant Subdivision, a Rowan County project for the Permittee, hereby state that, to the best of my abilities, due care and diligence was used in the observation of the construction such that the construction was observed to be built within substantial compliance of this permit; 15A NCAC 2T; the Division of Water Quality's (Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting materials. North Carolina Professional Engineer's seal, signature, and date: SEND THIS FORM & SUPPORTING DOCUMENTATION WITH REQUIRED ATTACHMENTS TO THE FOLLOWING ADDRESS MOORESVILLE REGIONAL OFFICE SURFACE WATER PROTECTION 610 EAST CENTER AVENUE, SUITE 301 MOORESVILLE NC 28115 The Permittee is responsible for tracking all partial certifications up until a final certification is received. Any wastewater flow made tributary to the wastewater collection system extension prior to completion of this Engineer's Certification shall be considered a violation of the permit and shall subject the Permittee to appropriate enforcement actions. iiT--TRACK APPLICATION for GC.AVITY SEWERS, PUMP STATIONS, AND FORCE MAINS PAGE 4 z Provide the wastewater flow calcul .02190) for Item B(7) or the design that in 15A NCAC2H .0219(I)(1-2) NCAC 2H .0219(I)(3). x 360 gpd per lot nns used in determining the permitted flow in accordance with 15A NCAC 2H w fdr line or pump station sizing if zero flow in the space below, Values other than ust be supported with actual water or wastewater use data in accordance with 15A 10. Summary of Lines to be Permitted (attach additional sheets if necessary) Length (feet) 5930 Size (inches) 8" ENTER TOTAL LINE LENGTH IN MILES 1.12 umrnary of Pump Stations to be Permitted (attach additional sheets as necessary) Gravity or Force Ma n (use the pull down menu) Gravity Location ID Power Reliability Option (self chosen - as shown on Design Flow Operational Point (1- dual line feed; 2- permanent generator w/ATS; 3- plans for cross-reference) (MGD) GPM a TDH portable generator w/telemetry; 4-wet well storage) 12_ Does the sewer system comply avith the Minimum Design Criteria for the Fast Track Permitting of Pump Stations and Force Mains (latest version), the Gravity Sewer Minimum Design Criteria (latest version) and 15A NCAC 2H .0200 as applicable? Yes D No If no, please reference the pertinent minimum design criteria or regulation and indicate why a variance is requested. SUBMIT TWO COPIES OF PLANS, SPECIFICATIONS OR CALCULATIONS PERTINENT TO THE VARIANCE WITH YOUR APPLICATION Have the following permits/certifications been submitted for approval? Wetland/Stream Crossings - General Permit or 401 Certification? 0 Yes Q No N/A Sedimentation and Erosion Control Plan? I Yes E1 No © N/A Stormwater? © Yes fl No N/A 14, Does this project involve aerial lines or siphons? 0 These lines will be considered high priority and must be checked once every six months FTA 02103 - Rev, 3 04(05 MAST -TRACK APPLICATION for GRAVITY SEWERS, PUMP STATIONS, AND FORCE MAINS PAGE 5 Q 0 I ❑ A Stream Classification is not needed because the design does not depend on wet well storage as a power reliability 1. Use the Division's guidance document entitled, "DETERMINING STREAM CLASSIFICATIONS FOR FORM FTA 02103 I (FAST TRACK SEWER SYSTEMS)" to collect and record the stream classification data below (attach additional sheets as necessary). This document is available from our web site or by contacting the appropriate Division of Water Quality regional office (see instructions for addresses) OR indicate the following: ❑ A Stream Classification is not needed because all parts of the project are at least 100 feet away from any down slope waterbody; AND, option for any pump station near a Class C down slope waterbody. Location ID on Map 1 l CO .j (self chosen -as shown on 1 Name of map for cross-reference) .. __ _ Waterbody - MH la 1 Grants Creek Waterbody Stream Waterbody __.._...__._.._.__._..'.__....... - .._..._.- .._ _.....—.2. County. River Basin 1 index Classification Rowan Yadkin ! 12-110 C 1- i .Lu 11 f l Submit the 8.5" x 11" COLOR topographic map as required in Instruction VI regardless of whether a classification is provided! Applicant's Certification: 1, Eric Davis , attest that this application for Miller's Grant Subdivision has been reviewed by me and is accurate and complete to the best of my knowledge. ! understand that if all required pats of this application are not completed and that if all required supporting documentation and attachments are not included, this application package is subject to being retumed as incomplete. Note: in accordance with North Carolina General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false statement, representation, or certification in any application shall be guilty of a Class 2 misdemeanor which may include a fine not to exceed $10, 000 as well as civil penalties up to $25, 000 per violation. Signing Official Signature p. Professional Engineer's Certification: Ol attest that this application for Miller's Grant Subdivision has been reviewed by me and is accurate, complete and consistent with the information in the engineering plans, calculations, and all other supporting documentation to the best of I-' my knowledge. ! further attest that to the best of my knowledge the proposed design has been prepared in accordance with the applicable regulations, Gravity Sewer Minimum Design Criteria for Gravity Sewers adopted February 12, 1996, LW' 31-r27 Date and the Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 and the watershed classification in accordance with Division guidance. Although certain portions of this submittal package may have been developed by other professionals, inclusion of these materials under my signature and seal signifies that l have reviewed this material and have judged it to be consistent with the proposed design. Note: In accordance with NC Genera! Statutes 143 215.6A and 143-215.6B, any person who knowingly makes any false statement, representation, or certification in any application shall be guilty of a Class 2 misdemeanor which may include a fine not to exceed $10, 000 as well as civil penalties up to $25, 000 per violation. 2a. Paul Campbell Professional Engineer Name 2b. NorthEast Engineering, PA Engineering Firm ' 2c. PO Box 931 Mailing Address d. Concord j City State Zip g. 704-788-6372 2h. 704-786-4750 2i. pammpbell@nee-pa.com Telephone Facsimile E-mail 2e. NC 2f. 28026 Seal, Signature & Date FTA 02103 - Rev. 3 04105 "Topozne - USGS China Grove (NC Topo Map Page I of 1 p one S Tee Nape -a 1124K/25e Tope Maps 1, 100K Tape Maps .. t:250l( Tope Mope aetneeat➢c salectiee Hap Slue Small Metllurm ` La View scale . '25,000 Cee lisalte Feleeal UYk4 Map Mane as U 11,2 ter P.4 $e,e U,CS I1 at ertP rtOts romum uee5.. am sr pva cp .. &WM MOM Me Imagery for Cooer Rea? Estate & Ers• Profesionals. you can watt unidlfiritect Satellite our c omp(itar'r http://www,topozone,com/m.ap.asp?lat=7855&lon--8Q.58634&s= size=i&datum=... 5/ 1/2007 2007 3: 35PM Joe Kf7DX Pf o; No. 782 P. 2 TOwN REANACER Eric Jaws l'outp4 CLERK Gail Carter TOWN ATTORNEY Tom Brooke November 3, 2006 TOWN OF CHINA GROVE Mr. Gary Knox 17824 Statesville Road, Suite 122 Cornelius, NC 28031 Water and Sewer Capacity Certification Mr, Knox, In reference to the Millers Grant Subdivision on 152 West wi 1 roposed lots, the Town of China Grove water and sewer systems have more than adequate capacity. The Town's water and sewer contracts with the City of Salisbury are for two million gallons per day, 2 MGD, each. The Town uses approximately 300,000 GPD of water and averages 380,000GPD. System capacity records and documents are available at the China Grove Utilities Department, 618 Salisbury Street in China Grove. MOOR Don Bringlt Tows COUNCIL Butch Myer's Troy Sion Blair Lystski Harold Simpson Allen Welter Rory Kent Mishak, Utilities Director 205 Swink Street, China Grove, NC 28023 • (704) 857-2466 • Fax (704) 855.1855 NEr NORTHEAST ENGINEERING Quality engineering with old friends and familiar faces. LETTER OF TRANSMITTAL To: NCDENR Mooresville Regional Office • Northeast Engineering, P.A. 37 S Union St, Suite D P.O. Box 93I Concord, North Carolina 28026-0931 Phone: 704-788-NEPA (6372) Fax 704-786-4750 www.nee pa.con' Date: 6/4/2007 Attention: Dee Browder Re: Miller's Grant we are sensing you: Copies Date Description 2 ea sewer permit 1 check 1 flow letter ✓❑ For Approval Remarks: ❑As Requested ❑ For Review and Comment ['For Your Use ❑ Other For permit. Please call with questions thx thanks i. ur ci`JVirttjtldra , AND l' ATURAL RESOURCES-"\ V100RE5V,i 1 r - C::ONAL. OFFICE JUN 0 5 2007 WATER QUALITY SECTION Copy To: Signed: co leivc4QQ If enclosures are not as noted above, please contact us immediatley. July 9, 2007 Mr. Kent Mishak Town of China Grave 205 Swink Street China Grove, NC RE: Millers Grant Subdivision Dear Mr. Mishak: JUL� The City's wastewater treatment facility, the Salisbury -Rowan Wastewater Treatment Plant Grant Creek Train, permit # NC0023884, and collection system (Grant Creek. Interceptor) have sufficient capacity to support the 41,760 gpd flow created by Millers Grant Subdivision.. If you have any questions or comments please, contact me at (704) 638-2146. Cc: File 1 Water Street Salisbury, NC 28144 Sind Y7 P.E. Planning Manager Salisbury -Rowan Ut ifles Telephone (7fl4) 638-5205 Fax (704)638-8491 Michael F. Easley, Governor William G. Ross Jr., Secretary North Carolina Department of Environment and Natural Resources Coleen H. Sullins, Director Division of Water Quality June 27, 2007 CERTIFIED MAIL RETURN RECEIPT REQUESTED 7006 2760 0001 8493.9624 Eric Davis, Town Manager Town of China Grove 305 Swink Street China Grove, NC 28023 Subject: Return of Permit Application Package Miller Grant Subdivision Wastewater Collection System Extension Rowan County Dear Mr. Davis The Division of Water Quality's Mooresville Regional Office is unable to accept the enclosed application package (including fee) for review for the following reason(s): ✓ A flow acceptance letter was not provided by the owner of the downstream sewers and/or the owner of the receiving wastewater treatment facility (City of Salisbury) as is required by Instruction V of the application. Flow acceptance letters must contain the following minimum information: applicant and project name, amount of flow accepted and name and permit number of the receiving wastewater treatment facility. The flow acceptance must not expire prior to permit issuance and must be dated less than a year prior to the application date. Intergovernmental agreements or other contracts will not be accepted in lieu of a project -specific flow acceptance letter. Please note that the item(s) listed above must be included and/or completed prior to resubmitting the permit application package (with fee) for approval. Your application is being returned as incomplete in accordance with 15A NCAC 2H .0208. The success of the fast -track approval process depends upon the receipt of complete and accurate applications. Please make the appropriate corrections and resubmit the application. The review process will then begin upon receipt of the completed and/or corrected application. mar Mooresville Regional office 610 East Center Street, Suite 301, Mooresville, NC 28115 DENR Customer Service Center An Equal Opportunity Action Employer Internet http:llh2o.enr.state.nc.us/ Telephone (704) 663-1699 Fax (704) 663-6040 Telephone 1 800 623-7748 50% recycled/10% post -consumer paper NCDENR Page 2 Mr. Davis June 28, 2007 Please be advised that construction and/or operation of wastewater collection system extension without a valid permit is a violation of North Carolina General Statute 143-215.1 and may subject the Applicant to appropriate enforcement actions in accordance with North Carolina General Statute 143-215.6. Civil penalties of up to $25,000 per day per violation may be assessed for failure to secure a permit required by North Carolina General Statute 143-215.1. If you should have any questions regarding the acceptance of your application, please do not hesitate to contact me at 704.235.2203 or dee.browder@ncmail.net. Thank you for your cooperation. ee =r' ' der Environmental Engineer Enclosures cc: Paul Campbell, NorthEast Engineering, PA Application return file Fast Track Engineering Permit No. W00031988 July 24, 2007 Owner/WQCS Eric Davis, Town Manager Town of China Grove 305 Swink Street China Grove, NC 28023' Certification WWTPNVQCS David Treme City of Salisbury 217 South Main Street Salisbury, NC 28145 PE Paul Campbell NorthEast Engineering, PA PO Box 931 Concord, NC 28026 Complete and submit this form to the permit issuing regional office with the following: • One copy of the project record drawings (plan & profile views of sewer lines) of the wastewater collection system extension • Supporting design calculations (selected pumps, system curve, operating point, available storage if portable generator(s) or storage greater than longest past three year outage reliability option selected) for any pump stations permitted as part of this project • Changes to ' project should be clearly identified on the record drawings or in written summary form. Permit modifications ' required for any changes resulting in non-compliance with this permit, regulations or minimum desi -riteria. This project shall no - required supporting dc,•. that this certification be ,lsidered complete nor allowed to operate until this Engineer's Certification and all `ation have been received by the Division. Therefore, it is highly recommended '1 a manner that provides proof of receipt by the Division. • ENGINEER'S CERTIFICATION 1 'artiai Li Final I. P0,01, D CAINnp2" , as a duly registered Professional Engineer in the State of North Carolina, having been authorized to observe (periodically, ❑ weekly, ❑ full time) the construction of Miller Grant Subdivision, a Rowan County project for the Permittee, hereby state that, to the best of my abilities, due care and diligence was used in the observation of the construction such that the construction was observed to be built within substantial compliance of this permit; 15A NCAC 2T; the Division of Water Quality's (Division) Gravity Sewer Minimum Design Criteria adopted February 12, 1996 as applicable; the Division's Minimum Design Criteria for the Fast -Track Permitting of Pump Stations and Force Mains adopted June 1, 2000 as applicable; and other supporting materials. North Carolina Professional Engineer's seal, signature, and date: SEND THIS FORM & SUPPORTING DOCUMENTATION WITH REQUIRED ATTACHMENTS TO THE FOLLOWING ADDRESS MOORESVILLE REGIONAL OFFICE SURFACE WATER PROTECTION 610 EAST CENTER AVENUE, SUITE 301 MOORESVILLE NC 28115 The Permittee is responsible for tracking all partial certifications up until a final certification is received. Any wastewater flow made tributary to the wastewater collection system extension prior to completion of this Engineer's Certification shall be considered a violation of the permit and shall subject the Permittee to appropriate enforcement actions. t _3R-I VO-gFr. tap( (0 , [ R e, o►d?