HomeMy WebLinkAboutNC0043125_Compliance Evaluation Inspection_20211122DocuSign Envelope ID: FABEC846-1C2D-46B9-9631-32FB6F303F86
ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
S. DANIEL SMITH
DirectOr
NORTH CAROLENA
Environmental Qualify
SENT VIA ELECTRONIC MAIL ONLY: NO HARD COPY WILL BE MAILED.
November 22, 2021
Dawn Turner, Patterson School Foundation Inc
Patterson School WWTP
E-mail: business@psfinc.org
SUBJECT: Compliance Inspection Report
Patterson School
NPDES WW Permit No. NC0043125
Caldwell County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Patterson School on
11/17/2021. This inspection was conducted to verify that the facility is operating in compliance with the
conditions and limitations specified in NPDES WW Permit No. NC0043125. The findings and comments
noted during this inspection are provided in the enclosed copy of the inspection report entitled
"Compliance Inspection Report".
There were no significant issues or findings noted during the inspection and therefore, a response to this
inspection report is not required.
If you should have any questions, please do not hesitate to contact Timothy Heim with the Water
Quality Regional Operations Section in the Asheville Regional Office at 828-296-4500 or via email at
tim.heim@ncdenr.gov.
ATTACHMENTS
Ec: LF
Josh Greene, ORC
Sincerely,
r—DocuSigned by:
"—E397192DABFB4FF...
Daniel Boss, Asst. Regional Supervisor
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
D_EC�
North Carolina Department of Environmental Quelfy I olvtslon of Water Resources
Asheville Regional Office 12090 O.S. Highway 70 I Swannanoa, Noah Carolina 28778
828.290 4500
DocuSign Envelope ID: FABEC846-1C2D-46B9-9631-32FB6F303F86
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection
1 IN I 2 IL I 3 I NC0043125 111 121 21/11/17 117
Type
1810I
IIIIIIIIIII
Inspector Fac Type
19I S I 2011
21IIIIII IIIIIIIIIIIIIIIIII I IIIIII
P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
671 I 761 I 711 172 I N I 73I 1 74 71
I I J
I I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Patterson School
4646 Patterson School Dr
Lenoir NC 28645
Entry Time/Date
11:OOAM 21/11/17
Permit Effective Date
19/10/01
Exit Time/Date
12:30PM 21/11/17
Permit Expiration Date
23/10/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Joshua Steven Greene/ORC/828-396-4444/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
W J Hogan,PO Box 500 Patterson NC 286610500//828-728-3189/8287545065
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Operations & Maintenar Records/Reports Facility Site Review
Effluent/Receiving Wate
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Timothy H Heim DWR/ARO WQ/828-296-4665/ 11/22/2021
—DocuS,gnea by:
titmegui him
- 002B1105A3CA418..
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
DocuSigned by: 11/22/2021
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
DocuSign Envelope ID: FABEC846-1C2D-46B9-9631-32FB6F303F86
31
NPDES yr/mo/day
NC0043125 111 121 21 /11 /17
I17
Inspection Type
18LI
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Tim Heim of the Asheville Regional Office performed a Compliance Inspection of the Facility on
November 17, 2021. Josh Greene (ORC) assisted with the inspection. The facility is operating again
after it did not receive influent for a significant period of time during the COVID pandemic, and
appeared well maintained and operated at the time of the inspection, and in compliance with Permit
NC0043125.
The following items were noted at the time of the inspection:
Continue to maintain the grounds surrounding the WWTP.
Consider replacing the solid plates covering the WWPT with metal grating to allow easier visualization
of the components.
Improve operator access to the manual bar screen to allow easier regular cleaning and maintenance.
Clean the clarifier troughs to prevent the release of accumulated solids into the effluent.
Page# 2
DocuSign Envelope ID: FABEC846-1C2D-46B9-9631-32FB6F303F86
Permit: NC0043125
Inspection Date: 11/17/2021
Owner - Facility: Patterson School
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ � ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: Continue to maintain the grounds surrounding the WWTP.
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ ❑
application?
Is the facility as described in the permit? • ❑ ❑ ❑
# Are there any special conditions for the permit? ❑ • ❑ ❑
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment:
Bar Screens Yes No NA NE
Type of bar screen
a.Manual •
b.Mechanical ❑
Are the bars adequately screening debris? • ❑ ❑ ❑
Is the screen free of excessive debris? ❑ • ❑ ❑
Is disposal of screening in compliance? • ❑ ❑ ❑
Is the unit in good condition? • ❑ ❑ ❑
Comment: Improve operator access to the manual bar screen to allow easier regular cleaning and
maintenance.
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots? • ❑ ❑ ❑
Are surface aerators and mixers operational? ❑ ❑ • ❑
Are the diffusers operational? • ❑ ❑ ❑
Is the foam the proper color for the treatment process? • ❑ ❑ ❑
Does the foam cover less than 25% of the basin's surface? • ❑ ❑ ❑
Is the DO level acceptable? ❑ ❑ ❑ •
Page# 3
DocuSign Envelope ID: FABEC846-1C2D-46B9-9631-32FB6F303F86
Permit: NC0043125
Inspection Date: 11/17/2021
Owner - Facility: Patterson School
Inspection Type: Compliance Evaluation
Aeration Basins
Is the DO level acceptable?(1.0 to 3.0 mg/I)
Yes No NA NE
Comment: Consider replacing the solid plates covering the WWPT with metal grating to allow
easier visualization of the components.
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • ❑ El El
Is the site free of excessive buildup of solids in center well of circular clarifier? ❑ El • El
Are weirs level? • ❑ ❑ ❑
Is the site free of weir blockage? • ❑ ❑ ❑
Is the site free of evidence of short-circuiting? • ❑ ❑ ❑
Is scum removal adequate? • El El El
Is the site free of excessive floating sludge? • ❑ ❑ ❑
Is the drive unit operational? ❑ ❑ • ❑
Is the return rate acceptable (low turbulence)? ❑ ❑ • ❑
Is the overflow clear of excessive solids/pin floc? ■ ❑ ❑ ❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) • ❑ ❑ ❑
Comment: Clean the clarifier troughs to prevent the release of accumulated solids into the
effluent.
Page# 4