November 15, 2021
SUBJECT: Compliance Evaluation Inspection
Clearview at Misenheimer WWTP
NPDES Permit NC0041718
Stanly County
Mr. Smith:
On November 10, 2021, Roberto Scheller of this Office conducted a compliance inspection at
the subject facility. This inspection was conducted as a Compliance Evaluation Inspection (CEI)
to ensure compliance with permit requirements and conditions.
At the time of inspection facility appeared to be well operated and was producing a good quality
effluent. We wish to thank the operating staff for assistance regarding this inspection. The
enclosed report should be self-explanatory; however, should you have any questions, please do
not hesitate to contact myself or Roberto Scheller at (704) 235-2204 or
roberto.scheller@ncdenr.gov.
Enclosure: CEI Report
Dap®rlmant of Enr romrcnlal Ouant_NORTH CAROLINA
Sincerely,
1- DocuSigned by:
P444.4
�F 161 FB69A2D84A3...
for
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
North Carolina Department of Environmental Quality 1 Division of Water Resources
Mooresville Regional Office 1610 East Center Avenue, Suite 301 I Mooresville, North Carolina 28115
704.663.1699
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction
1 IN
Code
I 2
IL
NPDES yr/mo/day Inspection Type Inspector Fac
I 3 I NC0041718 111 121 21/11/10 117 1810I 19I S I 2011
Type
21IIIIII
IIIIIIIIIII
IIIIIII
I
IIIIII
IIIIIIIIIII
P6
Inspection
671
Work Days
Facility Self -Monitoring
I 70I3
Evaluation Rating
I 711
B1
1
72
QA
I N I
73I
1
I I
Reserved
74 71
J
I
I I
I
I
I
180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Clearview at Misenheimer
48708 US Hwy 52
Misenheimer NC 28109
Entry Time/Date
11:48AM 21/11/10
Permit Effective Date
19/04/01
Exit Time/Date
12:39PM 21/11/10
Permit Expiration Date
24/02/29
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
John Walter Ritchie/ORC/704-788-4164/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Paul J Smith,85 N Hillside Dr North Myrtle Beach SC 29582//843-280-4460/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s)
Roberto Scheller
of Inspector(s) Agency/Office/Phone and Fax Numbers Date
,-Docusigned by: 11/15/2021
DWR/MRO WQ/707-235-2204/
54..,
"-91C2A007838943E...
Signature of Man
W. Corey Ba
emMuaNellgewer for WCB Agency/Office/Phone and Fax Numbers Date
inge4F161Fr BH69A2D84A3P R/Division of Water Quality/704-235-2194/ 11.15.21
...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
31
NPDES yr/mo/day
NC0041718 111 121 21 /11 /10
117
Inspection Type
18 [j
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The current permit (NC0041718) became effective April 1, 2019 and expires on February 29, 2024.
Permit is for the continued operation of an existing 0.005 MGD extended air wastewater treatment
system that discharges into Curl Tail Creek which is classified as WS-IV water in the Yadkin -Pee Dee
River Basin. Facility consist of Barscreen, Aeration Basin, Two (2) Aeration Blowers, Clarifier,
Chlorine Contact Chamber with Tablet Chlorine and Dechlorination, and Effluent Air Diffuser. Effluent
discharges into Curl Tail Creek via outfall #001.
Review of compliance history was conducted from October 2020 through September 2021. Violations
were noted for Daily Maximum Limit Violations of Fecal Coliform on June/2021, July/2021 and
August/2021.
At time of subject inspection facility appeared to be well operated. Effluent at point of discharge was
clear with no visible suspended solids. There was no foam or floating solids at the point of discharge.
Page# 2
Permit: NC0041718
Inspection Date: 11/10/2021
Owner - Facility: Clearview at Misenheimer
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new ❑ ❑ ❑
application?
Is the facility as described in the permit? • ❑ El El
# Are there any special conditions for the permit? • ❑ ❑ ❑
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment:
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Comment: Records and copy of permit are stored off site due to vandalism.
Bar Screens
Type of bar screen
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
•
• ❑ ❑ ❑
❑ ❑ • ❑
❑ ❑ • ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Yes No NA NE
Page# 3
Permit: NC0041718
Inspection Date: 11/10/2021
Owner - Facility: Clearview at Misenheimer
Inspection Type: Compliance Evaluation
Bar Screens Yes No NA NE
a.Manual •
b.Mechanical ❑
Are the bars adequately screening debris? • ❑ ❑ ❑
Is the screen free of excessive debris? • ❑ ❑ ❑
Is disposal of screening in compliance? • ❑ ❑ ❑
Is the unit in good condition? • ❑ ❑ ❑
Comment:
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots? • ❑ ❑ ❑
Are surface aerators and mixers operational? El El • ❑
Are the diffusers operational? • El El El
Is the foam the proper color for the treatment process? • El ❑ ❑
Does the foam cover less than 25% of the basin's surface? • El El El
Is the DO level acceptable? • El ❑ ❑
Is the DO level acceptable?(1.0 to 3.0 mg/I) El El El •
Comment:
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ • ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Page# 4
Permit: NC0041718
Inspection Date: 11/10/2021
Owner - Facility: Clearview at Misenheimer
Inspection Type: Compliance Evaluation
Secondary Clarifier Yes No NA NE
Comment:
Disinfection -Tablet Yes No NA NE
Are tablet chlorinators operational? • ❑ ❑ ❑
Are the tablets the proper size and type? • ❑ ❑ ❑
Number of tubes in use? 2
Is the level of chlorine residual acceptable? ❑ ❑ El •
Is the contact chamber free of growth, or sludge buildup? • ❑ ❑ ❑
Is there chlorine residual prior to de -chlorination? • ❑ ❑ ❑
Comment:
De -chlorination Yes No NA NE
Type of system ? Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)? • ❑ ❑ ❑
Is storage appropriate for cylinders? ❑ ❑ • ❑
# Is de -chlorination substance stored away from chlorine containers? El El ❑ •
Comment:
Are the tablets the proper size and type? ■ El El El
Are tablet de -chlorinators operational? • El ❑ ❑
Number of tubes in use? 2
Comment:
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • El El El
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable MOE El
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment: At time of inspection effluent was clear with no visible suspended soids.
Page# 5