HomeMy WebLinkAboutNC0020800_Compliance Evaluation Inspection_20211116DocuSign Envelope ID: A6620B88-A9EE-4DOD-9A8C-F836618A7F78
ROY COOPER
Governor
ELIZABETH S. BISER
Secretory
S. DANIEL SMITH
Orrerter
NORTH CAROLINA
Environmental Qualify
SENT VIA ELECTRONIC MAIL ONLY: NO HARD COPY WILL BE MAILED.
November 16, 2021
Sandy Dobson, Town Administrator
Town of Andrews
E-mail: townadministrator@andrewsnc.org
SUBJECT: NOTICE OF VIOLATION
Tracking Number: NOV-2021-PC-0567
Permit No. NC0020800
Andrews WWTP
Cherokee County
Dear Permittee:
The North Carolina Division of Water Resources conducted an inspection of the Andrews WWTP on November
9, 2021. This inspection was conducted to verify that the facility is operating in compliance with the conditions
and limitations specified in NPDES WW Permit No. NC0020800. A summary of the findings and comments noted
during the inspection are provided in the enclosed copy of the inspection report.
The Compliance Evaluation inspection was conducted by Division of Water Resources staff from the Asheville
Regional Office. The following violation(s) were noted during the inspection:
Inspection Area Description of Violation
Pump Station - Influent Only 2 of the 3 influent pumps are currently able to operate.
Execute and complete the influent pump station project.
Trickling Filter The south trickling filter drive unit is not operational. This is likely contributing to NH3 effluent
limit violations in the summer months. Repair the drive unit.
Remedial actions should have already been taken to correct this problem and prevent further occurrences in the
future. The Division of Water Resources may pursue enforcement action for this and any additional violations of
State law.
North Carolina Department of Environmental Quelfy I olvtslon of Water Resources
Asheville Regional Office 12090 O.S. Highway 70 I Swannanoa, Noah Carolina 28778
828.290 4500
DocuSign Envelope ID: A6620B88-A9EE-4D0D-9A8C-F836618A7F78
To prevent further action, please respond in writing to this office within 30 days upon your receipt of this Notice
of Violation regarding your plans or measures to be taken to address the indicated violations and other identified
issues, if applicable.
If you should have any questions, please do not hesitate to contact Timothy Heim with the Water Quality
Regional Operations Section in the Asheville Regional Office at 828-296-4500.
ATTACHMENTS
Ec: LF
Tim Wood, Andrews WWTP ORC
Sincerely,
r—DocuSigned by:
S 022
�E397192DABFB4FF...
Daniel Boss, Asst. Regional Supervisor
Water Quality Regional Operations Section
Asheville Regional Office
Division of Water Resources, NCDEQ
North Carolina Department of Environmental Quelfy I olvtslon of Water Resources
Asheville Regional Office 12090 O.S. Highway 70 I Swannanoa, Noah CaroI0a 28778
828.290 4500
DocuSign Envelope ID: A6620B88-A9EE-4DOD-9A8C-F836618A7F78
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction
1 IN
Code
I 2
IL
NPDES yr/mo/day Inspection Type Inspector Fac
I 3 I NC0020800 111 121 21/11/09 117 1810I 19I S I 2011
Type
21IIIIII
IIIIIIIIIII
IIIIIII
I
IIIIII
IIIIIIIIIII
P6
Inspection
671
Work Days
Facility Self -Monitoring
I 70I
Evaluation Rating
I 711
B1
1
72
QA
I N I
731
1
I I
Reserved
74 71
I
I I
I
I
I
180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Andrews WWTP
Reagan Ave
Andrews NC 28901
Entry Time/Date
10:OOAM 21/11/09
Permit Effective Date
19/09/01
Exit Time/Date
12:OOPM 21/11/09
Permit Expiration Date
23/08/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Timothy Brian Wood/ORC/828-557-8630/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Michael Ladd,PO Box 1210 Andrews NC 289011210//828-321-3113/
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Operations & Maintenar Sludge Handling Dispo: Facility Site Review
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Timothy H Heim DWR/ARO WQ/828-296-4665/
�DocuSignetl by: 11/16/2021
I iwib{iu At iKA
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
jDocuSignetl by: 11/16/2021
�roco„nocon cc
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
DocuSign Envelope ID: A6620B88-A9EE-4D0D-9A8C-F836618A7F78
3I
NPDES yr/mo/day
NC0020800 I11 121 21 /11 /09
117
Inspection Type
18LI
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Tim Heim of the Asheville Regional Office performed a Compliance Inspection of the Facility on
November 9, 2021. Tim Wood (Andrews WWTP ORC) assisted with the inspection. Although the
ORC is maintaining and operating the facility to the best extent possible, this facility includes many
components at the end of their service life and requiring upgrade or replacement. Priority should be
given to completing planned projects in the immediate future, and a comprehensive facility upgrade in
the longer term.
The following items were non -complaint with NC0020800:
Only 2 of the 3 influent pumps are currently operational. The town's engineering consultant has
designed an influent pump station replacement project, but is waiting to finalize and send the project
to bid. Construction is anticipated to start in Spring 2022. Execute and complete the influent pump
station project.
The south trickling filter drive unit is not operational. Operators must manually rotate the distributor
arms. This results in poor hydraulic distribution and is likely contributing to NH3 effluent limit violations
in the summer months. Repair the drive unit
The following additional items were noted at the time of the inspection:
The south clarifier was experiencing high levels of scum at the time of the inspection, likely due to
seasonal diurnal temperature fluctuations. Monitor the scum levels and removal effectiveness to
make sure they do not impact effluent quality.
Page# 2
DocuSign Envelope ID: A6620B88-A9EE-4D0D-9A8C-F836618A7F78
Permit: NC0020800
Inspection Date: 11/09/2021
Owner - Facility: Andrews WWTP
Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable II ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Pump Station - Influent Yes No NA NE
Is the pump wet well free of bypass lines or structures? • ❑ ❑ ❑
Is the wet well free of excessive grease? ■ ❑ ❑ ❑
Are all pumps present? • ❑ ❑ ❑
Are all pumps operable? ❑ • ❑ ❑
Are float controls operable? • ❑ ❑ ❑
Is SCADA telemetry available and operational? ❑ ❑ • ❑
Is audible and visual alarm available and operational? • ❑ ❑ ❑
Comment: Only 2 of the 3 influent pumps are currently operational. The town's engineering
consultant has designed an influent pump station replacement project, but is waiting to
finalize and send the project to bid. Construction is anticipated to start in Spring 2022.
Execute and complete the influent pump station project.
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Trickling Filter
Is the filter free of ponding?
Is the filter free of leaks at the center column of filter's distribution arms?
Is the distribution of flow even from the distribution arms?
Is the filter free of uneven or discolored growth?
Is the filter free of sloughing of excessive growth?
Yes No NA NE
•
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ • ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 3
DocuSign Envelope ID: A6620B88-A9EE-4D0D-9A8C-F836618A7F78
Permit: NC0020800
Inspection Date: 11/09/2021
Owner - Facility: Andrews WWTP
Inspection Type: Compliance Evaluation
Trickling Filter
Are the filter's distribution arms orifices free of clogging?
Is the filter free of excessive filter flies, worms or snails?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The south trickling filter drive unit is not operational. Operators must manually rotate
the distributor arms. This results in poor hydraulic distribution and is likely contributing
to NH3 effluent limit violations in the summer months. Repair the drive unit.
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: The south clarifier was experiencing high levels of scum at the time of the inspection,
likely due to seasonal diurnal temperature fluctuations. Monitor the scum levels and
removal effectiveness to make sure they do not impact effluent quality.
Disinfection -Gas
Are cylinders secured adequately?
Are cylinders protected from direct sunlight?
Is there adequate reserve supply of disinfectant?
Is the level of chlorine residual acceptable?
Is the contact chamber free of growth, or sludge buildup?
Is there chlorine residual prior to de -chlorination?
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No.
7782-50-5)?
If yes, then is there a Risk Management Plan on site?
If yes, then what is the EPA twelve digit ID Number? (1000- - )
If yes, then when was the RMP last updated?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
• ❑ • ❑
Page# 4
DocuSign Envelope ID: A6620B88-A9EE-4D0D-9A8C-F836618A7F78
Permit: NC0020800
Inspection Date: 11/09/2021
Owner - Facility: Andrews WWTP
Inspection Type: Compliance Evaluation
Disinfection -Gas Yes No NA NE
De -chlorination Yes No NA NE
Type of system ? Gas
Is the feed ratio proportional to chlorine amount (1 to 1)? • ❑ ❑ ❑
Is storage appropriate for cylinders? • ❑ ❑ ❑
# Is de -chlorination substance stored away from chlorine containers? • ❑ ❑ ❑
Comment:
Are the tablets the proper size and type?
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment:
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
Comment:
Drying Beds
Is there adequate drying bed space?
Is the sludge distribution on drying beds appropriate?
Are the drying beds free of vegetation?
# Is the site free of dry sludge remaining in beds?
Is the site free of stockpiled sludge?
Is the filtrate from sludge drying beds returned to the front of the plant?
# Is the sludge disposed of through county landfill?
# Is the sludge land applied?
(Vacuum filters) Is polymer mixing adequate?
❑ ❑ ■ ❑
❑ ❑ • ❑
Yes No NA NE
• ❑ ❑ ❑
❑ ❑ ❑ •
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Page# 5
DocuSign Envelope ID: A6620B88-A9EE-4D0D-9A8C-F836618A7F78
Permit: NC0020800
Inspection Date: 11/09/2021
Owner - Facility: Andrews WWTP
Inspection Type: Compliance Evaluation
Drying Beds Yes No NA NE
Comment:
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑