HomeMy WebLinkAboutNC0028941_Compliance Evaluation Inspection_20211109ROY COOPER
Governor
ELIZABETH S. BISER
Secretory
S. DANIEL SMITH
Director
Mr. Shannon V. Becker
Aqua North Carolina, Inc.
202 Mackenan Court
Cary, NC 28511
Dear Mr. Becker:
NORTH CAROLINA
Environmental Quality
November 9, 2021
SUBJECT: Compliance Evaluation Inspection
Pine Valley S/D WWTP
NPDES Permit NC0028941
Rowan County, NC
On November 4, 2021, Roberto Scheller of this Office conducted a compliance inspection at the
subject facility. This inspection was conducted as a Compliance Evaluation Inspection (CEI) to
ensure compliance with permit requirements and conditions.
At the time of inspection facility appeared to be well operated and was producing a good quality
effluent. We wish to thank the operating staff for assistance regarding this inspection. The
enclosed report should be self-explanatory; however, should you have any questions, please do
not hesitate to contact myself or Roberto Scheller at (704) 235-2204 or
roberto.scheller(a�ncdenr.gov.
Enclosure: CEI Report
Sincerely,
1- DocuSigned by:
44.01414V H P:z
�F161FB69A2D84A3...
for
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Division of Water Resources, NCDEQ
CC: Ricky Reynolds, ORC, email: ricky.reynolds(a�aguaamerica.com
D_E
1N�.O.�R�TH CARO.I
•vp.nmept 0T EnVlrQIno
nm,n,0I Q03�k�
North Carolina Department of Environmental Quality I Division of Water Resources
Mooresville Regional Office 1610 East Center Avenue, Suite 301 I Mooresville, North Carolina 28115
704.663.1699
United States Environmental Protection Agency
E PA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code
1 IN I 2 IL
21IIIIII
NPDES yr/mo/day
I 3 I NC0028941 111 121 21/11/04 117
Inspection
Type
1810I
IIIIIIIIIII
Inspector Fac Type
19I S I 2011
IIIIIIIIIII IIIIIII I IIIIII
P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA
671 I 70I3 I 711 1 72 I
Reserved
N I 73I 1 74 71
I I 1
I I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES Dermit Number)
Pine Valley Subdivision WWTP
NCSR 1802
Salisbury NC 28144
Entry Time/Date
09:21AM 21/11/04
Permit Effective Date
19/06/01
Exit Time/Date
10:17AM 21/11/04
Permit Expiration Date
24/03/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Ricky Dean Reynolds/ORC//
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Joseph R Pearce,202 Mackenan Crt Cary NC 27511/Director of
Operations/919-653-6964/9194601788 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling Dispo: Facility Site Review Compliance Schedules
Effluent/Receiving Wate Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signa
Roberto Scheller
ure(s) of Inspector(s) Agency/Office/Phone and Fax Numbers
DocuSigned by:
(ram Sa LA,t;�oti DWR/MRO WQ/707-235-2204/
Date
11/9/2021
"-91C2A007838943E...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numb
W. Corey Basinger DWR/Division of Water Quality/704-235-219
DocuSigned by: for WCB Date
/A"' H P'4.'} 11.9.21
F161FB69A2D84A3...
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page# 1
31
NPDES yr/mo/day
NC0028941 111 121 21 /11 /04
117
Inspection Type
18 [j
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The current NPDES permit was issued on June 1, 2019 and expires March 31, 2024. Permit is for the
operation of a 0.025 MGD wastewater treatment plant that discharges into Setman Branch which is
classified as Class C waters in the Yadkin -Pee Dee River Basin.
Review of 12-month compliance history from October 2020 through September 2021 no permit limit
violations were reported.
At time of inspection effluent at point of discharge was clear with no visible suspended solids. Facility
appeared to be well operated.
Page# 2
Permit: NC0028941
Inspection Date: 11/04/2021
Owner - Facility: Pine Valley Subdivision WWTP
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new El El ❑
application?
Is the facility as described in the permit? • El El El
# Are there any special conditions for the permit? • El El El
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • El El El
Comment: Current NPDES Permit # NC0028941 became effective June 1, 2021 and expires on
March 31, 2024.
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Comment: Records reviewed were current and up to date.
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
•
• ❑ ❑ ❑
❑ ❑ ❑ ❑
▪ El El El
• ❑ ❑ ❑
Laboratory Yes No NA NE
Page# 3
Permit: NC0028941
Inspection Date: 11/04/2021
Owner - Facility: Pine Valley Subdivision WWTP
Inspection Type: Compliance Evaluation
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: Contract Laboratory Water Tech performs analyses under certification #50. Field
analyses are performed under Field Certification #5035. Field equipment calibration
sheets were reviewed and found up to date.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ❑ ❑ ❑
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment: Screenings are placed in dumpster for final disposal in sanitary landfill.
Yes No NA NE
•
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Is the basin free of dead spots? • ❑ ❑ ❑
Are surface aerators and mixers operational? ❑ ❑ • ❑
Are the diffusers operational? • ❑ ❑ ❑
Is the foam the proper color for the treatment process? • ❑ ❑ ❑
Does the foam cover less than 25% of the basin's surface? • ❑ ❑ ❑
Page# 4
Permit: NC0028941
Inspection Date: 11/04/2021
Owner - Facility: Pine Valley Subdivision WWTP
Inspection Type: Compliance Evaluation
Aeration Basins
Is the DO level acceptable?
Is the DO level acceptable?(1.0 to 3.0 mg/I)
I=1 El El IN
Yes No NA NE
Comment: At time of inspection 30 minute settability test was on going. MLSS had good color and
appeared to flocking together well.
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • ❑ El El
Is the site free of excessive buildup of solids in center well of circular clarifier? El El • El
Are weirs level? • El ❑ ❑
Is the site free of weir blockage? ■ El El El
Is the site free of evidence of short-circuiting? ■ ❑ El El
Is scum removal adequate? • El El El
Is the site free of excessive floating sludge? • El ❑ ❑
Is the drive unit operational? El El • El
Is the return rate acceptable (low turbulence)? ■ ❑ El El
Is the overflow clear of excessive solids/pin floc? • El El El
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) ❑ El ❑ •
Comment: At time of inspection effluent from secondary calrifier was clear with few visible soids.
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Disinfection -Tablet Yes No NA NE
Are tablet chlorinators operational? • El El El
Are the tablets the proper size and type? • ❑ El El
Number of tubes in use? 2
Is the level of chlorine residual acceptable? El El El •
Is the contact chamber free of growth, or sludge buildup? • El El El
Is there chlorine residual prior to de -chlorination? • ❑ El El
Page# 5
Permit: NC0028941
Inspection Date: 11/04/2021
Owner - Facility: Pine Valley Subdivision WWTP
Inspection Type: Compliance Evaluation
Disinfection -Tablet Yes No NA NE
Comment:
De -chlorination Yes No NA NE
Type of system ? Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)? ❑ ❑ • ❑
Is storage appropriate for cylinders? ❑ El • El
# Is de -chlorination substance stored away from chlorine containers? ❑ El • El
Comment:
Are the tablets the proper size and type? • El ❑ ❑
Are tablet de -chlorinators operational? ■ ❑ ❑ ❑
Number of tubes in use? 4
Comment: At point of discharge into Setman Branch there was no foam of floating solids. Effluent
was clear with no visible suspended solids.
Compliance Schedules
Is there a compliance schedule for this facility?
Is the facility compliant with the permit and conditions for the review period?
Comment:
Yes No NA NE
❑ ❑ • ❑
❑ ❑ • ❑
Page# 6