HomeMy WebLinkAboutNC0086894_Inspection_20051123>.
William G. Ross Jr., Secretary
North Carolina Department of Environment and Natural Resources
Alan W. Klimek, P.E. Director
Division of Water Quality
November 23, 2005
Myron Edward Neville
Robeson County Water Department
265 McGirt Rd
Maxton NC.28364
SUBJECT: November 22, 2005 Compliance Evaluation Inspection
Robeson County Water Department
Raemon Well WTP
Permit No: NC0086894
Robeson County
Dear Mr. Neville:
Enclosed please find a copy of the Compliance Evaluation Inspection form from the inspection conducted
on November 22, 2005. The Compliance Evaluation Inspection was conducted by Chad Turlington of the
Fayetteville Regional Office. The facility was found to be in Compliance with permit NC0086894.
Please refer to the enclosed inspection report for additional observations and comments. If you or your staff
have any questions, please call me at 910-486-1541 Ext.724.
cc: Myron Edward Neville, ORC
Central Files
=7;�; e�,,,e- y�iilile• Fil' s
Sincerely,
165/
Chad Turlington
Environmental Technician
Agile
NCDEN;R
1617 Mail Service Center
Raleigh, NC 27699-1617 (919) 733-7015
Customer Service 1 800 623-7748
United States Environmental Protection Agency
Washington, D.C. 20460
EPA
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection
1 I NI 2 151 31 NC0086894 1 11 121 05/11/22 1 17
Type Inspector Fac Type
18I C1 191gl 20II
Remarks
211111111111111111111111111111111111111111111111166
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ------ ------Reserved---------------
67I 3.0 1 69 701 I 711 I 72I NI I731
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Raemon Well WTP
NCSR 1170 0' Quinn Rd
Maxton NC 28364
Entry Time/Date
12:30 PM 05/11/22
Permit Effective Date
05/01/01
Exit Time/Date
01:30 PM 05/11/22
Permit Expiration Date
09/08/31
Name(s) of Onsite Representative(s)lfitles(s)/Phone and Fax Number(s)
///
Myron Edward Neville/ORC/910-844-5611/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Myron Edward Neville,265 McGirt Rd Maxton MC 28364//910-844-5611/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement • Operations & Maintenance • Records/Reports
Self -Monitoring Program • Facility Site Review • Effluent/Receiving Waters • Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Chad Turlington FRO WQ//910-486-1541 Ext.724/ 11 (L)310 C
617-12JC`A,U4?
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
Belinda S Henson-1y ''if 7'D FRO WQ//910-486-1541 Ext.726/ II/426 ,5
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page # 1
NPDES
N00086894
111 121
yr/mo/day
05/11/22
117
Inspection Type
18ICI
(cont.) 1
Section D: Summary of. Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
Wastewater at this facility is primarily filter backwash water. The backwash water is pumped into a settling
basin where the solids settle to the bottom. When the basin reaches capacity, the supernatant water is
discharged to a drainage ditch which flows to the receiving stream. Sludge from the settling basin is
removed when needed by pumper truck and hauled to the Maxton WTP to be dewatered on drying beds
and then disposed of in the Robeson County Landfill. Review of DMR's and lab reports for this facility
revealed no permit violations or descrepencies.
Page # 2
Permit: NC0086894 Owner - Facility: Raemon Well WTP
Inspection Date: 11/22/2005 Inspection Type: Compliance Evaluation
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment:
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable
Judge, and other that are applicable?
Comment:
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
Is proper temperature set for sample storage (kept at 1.0 to 4.4 degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Comment:
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Yes No NA NE
n n■n
■ nnn
n ■nn
■ nnn
■ nnn
Yes No NA NE
■ nnn
Solids, pH, DO, Sludge 0 0 ■ n
Yes No NA NE
■ nnn
■ nnn
■ nnn
n nn■
n n■n
n n■n
Yes No NA NE
■ nnn
■ nnn
■ nnn
■ nnn
■nnn
■
■
■
■
■
Page # 3
Permit: NC0086894 Owner - Facility: Raemon Well WTP
Inspection Date: 11/22/2005 Inspection Type: Compliance Evaluation
Record Keeping
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility classification?
Is.a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Comment:
Yes No NA NE
■
■ nnn
n n■n
n n■n
■ nnn
■ nnn
■ nnn
■ nnn
nn■n
Page # 4