HomeMy WebLinkAboutNC0032131_NOV2021LV0817_Response_20211111MRPB Systems
Construction Services • Contract Operations • Maintenance
November 11, 2021
Mr. Lon Snider
NCDWR, NCDEQ
Winston-Salem Regional Office
450 West Hanes Mill Road, Suite 300
Winston-Salem, NC 27105
Re: Notice of Violation
NOV-2021-LV-0817
NPDES NC0032131
Tweetsie Railroad
Mr. Snider,
This letter is in response to your November 2, 2021 NOV-2020-LV-0817letter to
Tweetsie Railroad attached.
The violation is correct for exceeding daily maximum of 7.5 mg/L BOD with a 9.8 mg/L.
The high BOD result for the first week of the month was a result of several days in the
7,000 gpd flow range to 1,000 gpd low flow. Wide swings in seasonal flow make the
biological population very unstable to maintain less than 7.5 mg/L BOD's. The next four
weeks of BOD were compliant.
If you have any questions, please call anytime.
Robert Barr
P.O. Box 1325 Asheville, N.C. 28802
(828)-251-1900 (828)-251-1945