HomeMy WebLinkAboutNc0085359_Compliance Evaluation Inspection_20211105ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
S. DANIEL SMITH
Director
Bart Farmer
Union County
4600 Goldmine Rd
Monroe, NC 28110
NORTH CAROLINA
Environmental Quality
November 5, 2021
SUBJECT: Compliance Inspection Report
Twelve Mile Creek WRF
NPDES WW Permit No. NC0085359
Union County
Dear Mr. Farmer:
The North Carolina Division of Water Resources conducted an inspection of the Twelve Mile
Creek WRF on November 3, 2021. This inspection was conducted to verify that the facility
is operating in compliance with the conditions and limitations specified in NPDES WW Permit
No. NC0085359. The findings and comments noted during this inspection are provided in
the enclosed copy of the inspection report entitled "Compliance Inspection Report".
If you should have any questions, please do not hesitate to contact Roberto Scheller with
the Water Quality Regional Operations Section in the Mooresville Regional Office at
704-663-1699 or via email at roberto.scheller@ncdenr.gov.
Sincerely,
CFor DocuSigned by
91C2A007838943E...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: WQS Mooresville Regional Office - Enforcement File
NPDES Compliance/Enforcement Unit
NORTH CAROLINA
Dep®rlmont of Environmental Onolit
North Carolina Department of Environmental Quality 1 Division of Water Resources
Mooresville Regional Office 1610 East Center Avenue, Suite 301 I Mooresville, North Carolina 28115
704.663.1699
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code
1 IN I 2 IL I
21IIIIII
NPDES yr/mo/day Inspection
3 I NC0085359 111 12I 21/11/03 I17
Type
1810I
IIIIIIIIIII
Inspector Fac Type
19I S I 2011
IIIIIIIIIII IIIIIII I IIIIII
P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
671 I 70I4 I 711 1 72 I N I 73I 1 74 71
I I
I I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Twelve Mile Creek WWTP
8299 Kensington Dr
Waxhaw NC 28173
Entry Time/Date
09:53AM 21/11/03
Permit Effective Date
21/07/01
Exit Time/Date
01:04PM 21/11/03
Permit Expiration Date
25/12/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Jonathan Brian Jordan/ORC/704-562-4542/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Bart Farmer,4600 Goldmine Rd Monroe NC 28110/Water Reclamation Facilities
Superintendant/704-296-4227/7042897395 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signature(s)
Roberto Scheller
of Inspector(s) Agency/Office/Phone and Fax Numbers
DocuSigned by:
Rj, S,ll„ DWR/MRO WQ/707-235-2204/
Date
11/5/2021
"-91C2A007838943E...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
11/5/2021
W. Corey Basinger DWR/Division of Water Quality/704-235-2194/
DocuSigned by:
For
EPA Frm ( v 9-4-#144it5us editions are obsolete.
91C2A007838943E...
Page# 1
31
NPDES yr/mo/day
NC0085359 111 121 21 /11 /03
117
Inspection Type
18 [j
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The subject facility is permitted to discharge 7.5 MGD via Outfall 001 into Twelve Mile Creek,
classified C waters in the Catawba River Basin. The curernt permit became effective on July 1, 2021
and expires on December 31, 2025.
A 12-month compliance history was reviewed from September 2020 through August 2021. One
violation was reported on 2/2021 (NOD-2021-LV-0070)for Flow.
Wastewater Performance Report for fiscal year 2019-2020 was reviewed on Union County web site.
12 month average flow for calendar year 2020 was caculated at 5.4 MGD or 72% of permitted flow.
Page# 2
Permit: NC0085359
Inspection Date: 11/03/2021
Owner - Facility: Twelve Mile Creek WWTP
Inspection Type: Compliance Evaluation
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new
application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment: Permit became effective on July 1, 2021 and expires on December 31, 2025.
Yes No NA NE
❑ ❑ • ❑
▪ El El El
• ❑ ❑ ❑
• ❑ ❑ ❑
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? • ❑ ❑ ❑
Is all required information readily available, complete and current? • ❑ ❑ ❑
Are all records maintained for 3 years (lab. reg. required 5 years)? • ❑ ❑ ❑
Are analytical results consistent with data reported on DMRs? • ❑ El El
Is the chain -of -custody complete? • El El El
Dates, times and location of sampling •
Name of individual performing the sampling •
Results of analysis and calibration ■
Dates of analysis •
Name of person performing analyses •
Transported COCs ■
Are DMRs complete: do they include all permit parameters? • El El ❑
Has the facility submitted its annual compliance report to users and DWQ? • El El El
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified • El ❑ ❑
operator on each shift?
Is the ORC visitation log available and current? • El El El
Is the ORC certified at grade equal to or higher than the facility classification? • El ❑ ❑
Is the backup operator certified at one grade less or greater than the facility • El El El
classification?
Is a copy of the current NPDES permit available on site? • ❑ El El
Facility has copy of previous year's Annual Report on file for review? • El El El
Comment: Wastewater Performance Report for Fiscal Year 2019-2020 was reviewed on the Union
County web site.
Bar Screens Yes No NA NE
Page# 3
Permit: NC0085359
Inspection Date: 11/03/2021
Owner - Facility: Twelve Mile Creek WWTP
Inspection Type: Compliance Evaluation
Bar Screens Yes No NA NE
Type of bar screen
a.Manual ❑
b.Mechanical •
Are the bars adequately screening debris? • ❑ ❑ ❑
Is the screen free of excessive debris? • ❑ ❑ ❑
Is disposal of screening in compliance? • ❑ ❑ ❑
Is the unit in good condition? • ❑ ❑ ❑
Comment: Debris from barscreens appeared compacted and dry. Debris is placed in dumpster
for disposal at landfill.
Pump Station - Influent Yes No NA NE
Is the pump wet well free of bypass lines or structures? • ❑ ❑ ❑
Is the wet well free of excessive grease? ❑ ❑ ❑ •
Are all pumps present? • ❑ ❑ ❑
Are all pumps operable? ■ ❑ ❑ ❑
Are float controls operable? • ❑ ❑ ❑
Is SCADA telemetry available and operational? • ❑ ❑ ❑
Is audible and visual alarm available and operational? ❑ ❑ ❑ •
Comment:
Chemical Feed Yes No NA NE
Is containment adequate? • ❑ ❑ ❑
Is storage adequate? ■ ❑ ❑ ❑
Are backup pumps available? • ❑ ❑ ❑
Is the site free of excessive leaking? • ❑ ❑ ❑
Comment: Alkalinity (lime) is added at influent pump station.
Grit Removal
Type of grit removal
a.Manual
b.Mechanical
Is the grit free of excessive organic matter?
Is the grit free of excessive odor?
# Is disposal of grit in compliance?
Yes No NA NE
❑ ❑ ❑
Page# 4
Permit: NC0085359
Inspection Date: 11/03/2021
Owner - Facility: Twelve Mile Creek WWTP
Inspection Type: Compliance Evaluation
Grit Removal
Comment:
Flow Measurement - Influent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: Flow meter is calibrated ever 6 months. Influent flow meter was last calibrated on
09/14/2021.
Influent Sampling
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is sampling performed according to the permit?
Comment: At time of inspection influent sampler was recorded at 3 degrees Celsius.
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Nutrient Removal Yes No NA NE
# Is total nitrogen removal required? ❑ ❑ • ❑
# Is total phosphorous removal required? • ❑ El El
Type Chemical
# Is chemical feed required to sustain process? • El El El
Is nutrient removal process operating properly? • El El El
Comment: NH3 as N removal is required to Monthly Average of 1.0 mg/I (Summer), 2.0 mg/i
(Winter).
Total Phosphorus removal is required to a Monthly Average of 41.70 Ibs/day and
12-Month Average of 20.85 Ibs/day.
Facility has 4 treatment trains with an anoxic zone at the head of each train. Facility
can also add Sodium Aluminate to aid in Phosphorous removal.
Aeration Basins Yes No NA NE
Mode of operation Ext. Air
Type of aeration system Diffused
Page# 5
Permit: NC0085359
Inspection Date: 11/03/2021
Owner - Facility: Twelve Mile Creek WWTP
Inspection Type: Compliance Evaluation
Aeration Basins Yes No NA NE
Is the basin free of dead spots? • ❑ ❑ ❑
Are surface aerators and mixers operational? ❑ El • El
Are the diffusers operational? • ❑ ❑ ❑
Is the foam the proper color for the treatment process? • ❑ ❑ ❑
Does the foam cover less than 25% of the basin's surface? • ❑ ❑ ❑
Is the DO level acceptable? • ❑ ❑ ❑
Is the DO level acceptable?(1.0 to 3.0 mg/I) • ❑ ❑ ❑
Comment: Treatment train consist of anocix zone, high oxidation zone (DO 2.32 mg/I) and lower
oxidation zone (DO 1.16 mg/I).
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • ❑ ❑ ❑
Is the site free of excessive buildup of solids in center well of circular clarifier? • ❑ ❑ ❑
Are weirs level? • ❑ ❑ ❑
Is the site free of weir blockage? • ❑ El ❑
Is the site free of evidence of short-circuiting? • ❑ ❑ ❑
Is scum removal adequate? • El ❑ ❑
Is the site free of excessive floating sludge? ■ El El El
Is the drive unit operational? • El El El
Is the return rate acceptable (low turbulence)? • ❑ ❑ ❑
Is the overflow clear of excessive solids/pin floc? • El ❑ ❑
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth) El ❑ El •
Comment: Effluent from clarifiers #2 and #6 was clear with few visible suspended solids.
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Comment:
Aerobic Digester
Is the capacity adequate?
Is the mixing adequate?
Yes No NA NE
• ❑ ❑ ❑
Yes No NA NE
Page# 6
Permit: NC0085359
Inspection Date: 11/03/2021
Owner - Facility: Twelve Mile Creek WWTP
Inspection Type: Compliance Evaluation
Aerobic Digester
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Comment: WAS is dewatered and transported to New Hill compost facility.
Yes No NA NE
• ❑ ❑ ❑
Filtration (High Rate Tertiary) Yes No NA NE
Type of operation: Cross flow
Is the filter media present? • ❑ ❑ ❑
Is the filter surface free of clogging? • ❑ ❑ ❑
Is the filter free of growth? • ❑ El El
Is the air scour operational? • ❑ ❑ ❑
Is the scouring acceptable? • ❑ ❑ ❑
Is the clear well free of excessive solids and filter media? ❑ ❑ • ❑
Comment:
Disinfection - UV Yes No NA NE
Are extra UV bulbs available on site? ❑ ❑ ❑ •
Are UV bulbs clean? • ❑ ❑ ❑
Is UV intensity adequate? ■ ❑ ❑ ❑
Is transmittance at or above designed level? • ❑ ❑ ❑
Is there a backup system on site? • ❑ ❑ ❑
Is effluent clear and free of solids? • ❑ ❑ ❑
Comment:
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? • ❑ ❑ ❑
Is sample collected below all treatment units? • ❑ ❑ ❑
Is proper volume collected? ■ El ❑ ❑
Is the tubing clean? • El El El
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 ■ ❑ ❑ ❑
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • El El El
representative)?
Page# 7
Permit: NC0085359
Inspection Date: 11/03/2021
Owner - Facility: Twelve Mile Creek WWTP
Inspection Type: Compliance Evaluation
Effluent Sampling Yes No NA NE
Comment: At time of inspection effluent sample was recorded at 3 degrees Celsius.
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
❑ ❑ • ❑
Comment: Flow meter is calibrated every 6 months by CITI. Last meter calibration was performed
on 9/14/2021.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ El ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable El El El
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Page# 8