HomeMy WebLinkAboutNC0069841_Compliance Evaluation Inspection_20210922ROY COOPER
Governor
ELIZABETH S. BISER
Secretary
S. DANIEL SMITH
Director
Mark Watson, County Manager
Union County
500 N Main Street, Suite 918
Monroe, NC 28112
NORTH CAROLINA
Environmental Quality
September 22, 2020
SUBJECT: Compliance Evaluation Inspection
Permit No. NC0069841
Crooked Creek WWTP #2
Union County
Mr. Watson:
The North Carolina Division of Water Resources conducted a Compliance Evaluation
Inspection (CEI) of the Crooked Creek WWTP #2 on September 16, 2020. This inspection
was conducted to verify that the facility is operating in compliance with the conditions and
limitations specified in NPDES WW Permit No. NC0069841. A summary of the findings and
comments noted during the inspection are provided in the enclosed copy of the inspection
report.
We would like to thank the operating staff for their assistance during this inspection. If you
should have any questions, please do not hesitate to contact Roberto Scheller with the Water
Quality Regional Operations Section in the Mooresville Regional Office at 704-663-1699.
Sincerely,
/--DocuSigned by:
A14CC681AF27425...
W. Corey Basinger, Regional Supervisor
Water Quality Regional Operations Section
Mooresville Regional Office
Division of Water Resources, NCDEQ
ATTACHMENTS
Cc: WQS Mooresville Regional Office - Enforcement File
NPDES Compliance/Enforcement Unit - Enforcement File
NORTH CAROLINA
Dep®rlmont of Environmental Onolit
North Carolina Department of Environmental Quality 1 Division of Water Resources
Mooresville Regional Office 1610 East Center Avenue, Suite 301 I Mooresville, North Carolina 28115
704.663.1699
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code
1 IN I 2 L
21IIIIII
NPDES yr/mo/day Inspection
3 I NC0069841 111 121 21/09/16 117
Type
1810I
IIIIIIIIIII
Inspector Fac Type
191S I 2011
IIIIIIIIIII IIIIIII I IIIIII
P6
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
671 I 70I3 I 711 1 72 I N I 731 1 74 71
I I 1
I I I I I I 180
l
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES Dermit Number)
Crooked Creek WWTP #2
4015 Sardis Church Rd
Monroe NC 28110
Entry Time/Date
10:OOAM 21/09/16
Permit Effective Date
18/08/01
Exit Time/Date
12:12PM 21/09/16
Permit Expiration Date
22/10/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Wyatt James Ryland Howell/ORC/704-289-1434/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Contacted
Bart Farmer,4600 Goldmine Rd Monroe NC 28110//704-296-4227/7042897395
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement Operations & Maintenar Records/Reports
Self -Monitoring Progran Sludge Handling DispoFacility Site Review Effluent/Receiving Wate
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signat
Roberto Scheller
g,�fsl ej tor(s) Agency/Office/Phone and Fax Numbers
C
�r V--+
Date
9/22/2021
DWR/MRO WQ/707-235-2204/
91C2A007838943E...
Signature of Management Q A Reviewer Agency/Office/Phone and Fax Numbers Date
W. Corey Basinger DWR/Division of Water Quality/704-235-2194/
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
DocuSigned by:
9/22/2021
"-A14CC681AF27425...
Page# 1
31
NPDES yr/mo/day
NC0069841 111 121 21/09/16
17
Inspection Type
18 [j
(Cont.)
1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The current NPDES Permit (NC0069841) was issued on August 1, 2018 and expires on October 31,
2022. Please note that in order to receive automatic authorization to discharge beyond the expiration
date, the Permittee shall submit such information, forms, and fees as are required by the agency
authorized to issue permits no later than 180 days prior to the expiration date unless permission for a
later date has been granted by the Director.
NPDES Permit #NC0069841 is for the continued operation of an existing 1.9 MGD wastewater
treatment facility that discharges into North Fork Crooked Creek which is classified as C waters in the
Yadkin -Pee Dee River Basin.
Please be aware that Part I, Section A.(5.), Schedule of Compliance for Ammonia -Nitrogen
Limitations, (4.) requires the Permittee achieve compliance with NH3-N limitations specified in section
A.(2.) by January 31, 2022. In that Ammonia -Nitrogen Limits change from Monthly Average (Summer)
2.0 mg/I, (Winter) 4.0 mg/I to final limits (Summer) 1.0 mg/I, (Winter) 1.9 mg/I. Weekly Average Limits
of (Summer) 6.0 mg/I, (Winter) 12.0 mg/I to final limits (Summer) 3.0 mg/I, (Winter) 5.7 mg/I.
Part I, Section A.(4.), Effluent Pollutant Scan; it was noted that samples have been collected for the
years 2019, 2020, with the last sampling conducted August 2021.
Wastewater Annual Reports for fiscal year 2020/2021 is on file at
www. unioncountync.gov/department/public-works/water-and-sewer/resources/wastewater-performanc
e-summary.
Review of compliance history for the period of July 2020 through June 2021 facility reported missed
samples during sample period of May 2021 for Total Nitrogen and Total Phosphorus.
Review of flow history for the calendar year 2020 found facility at 59% of flow.
At time of inspection the following effluent parameters were recorded:
DO 8.10 mg/I
pH 6.72
Temp. 25.4 Degrees Celsius
Page# 2
Permit: NC0069841
Inspection Date: 09/16/2021
Owner - Facility: Crooked Creek WWTP #2
Inspection Type: Compliance Evaluation
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new DOME
application?
Is the facility as described in the permit? • ❑ ❑ ❑
# Are there any special conditions for the permit? • ❑ ❑ ❑
Is access to the plant site restricted to the general public? • ❑ ❑ ❑
Is the inspector granted access to all areas for inspection? • ❑ ❑ ❑
Comment:
The current permit was issued on August 1, 2018 and expires on October 31, 2022.
Operations & Maintenance Yes No NA NE
Is the plant generally clean with acceptable housekeeping? • ❑ ❑ ❑
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable ▪ El El El
Solids, pH, DO, Sludge Judge, and other that are applicable?
Comment:
Record Keeping
Are records kept and maintained as required by the permit?
Is all required information readily available, complete and current?
Are all records maintained for 3 years (lab. reg. required 5 years)?
Are analytical results consistent with data reported on DMRs?
Is the chain -of -custody complete?
Dates, times and location of sampling
Name of individual performing the sampling
Results of analysis and calibration
Dates of analysis
Name of person performing analyses
Transported COCs
Are DMRs complete: do they include all permit parameters?
Has the facility submitted its annual compliance report to users and DWQ?
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified
operator on each shift?
Is the ORC visitation log available and current?
Is the ORC certified at grade equal to or higher than the facility classification?
Is the backup operator certified at one grade less or greater than the facility
classification?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
•
•
•
Page# 3
Permit: NC0069841
Inspection Date: 09/16/2021
Owner - Facility: Crooked Creek WWTP #2
Inspection Type: Compliance Evaluation
Record Keeping Yes No NA NE
Is a copy of the current NPDES permit available on site?
Facility has copy of previous year's Annual Report on file for review?
Comment: Annual Report on Union County web site.
IN ❑ ❑ ❑
Laboratory Yes No NA NE
Are field parameters performed by certified personnel or laboratory? ■ ❑ ❑ ❑
Are all other parameters(excluding field parameters) performed by a certified lab? • ❑ ❑ ❑
# Is the facility using a contract lab? • ❑ ❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 ■ ❑ ❑ ❑
degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees? ❑ ❑ ■ ❑
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees? ❑ ❑ ■ ❑
Comment: Facility using contract lab Batesville Analyical Cert #440. Facility holds Field
Certification #5658 for DO, pH, Temperature.
Influent Sampling
# Is composite sampling flow proportional?
Is sample collected above side streams?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0
degrees Celsius)?
Is sampling performed according to the permit?
Comment: At time of inspection influent sampler was recorded at 3.8 Degrees Celsius.
Equalization Basins
Is the basin aerated?
Is the basin free of bypass lines or structures to the natural environment?
Is the basin free of excessive grease?
Are all pumps present?
Are all pumps operable?
Are float controls operable?
Are audible and visual alarms operable?
# Is basin size/volume adequate?
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
▪ El El El
• ❑ ❑ ❑
• ❑ ❑ ❑
Page# 4
Permit: NC0069841
Inspection Date: 09/16/2021
Owner - Facility: Crooked Creek WWTP #2
Inspection Type: Compliance Evaluation
Equalization Basins Yes No NA NE
Comment:
Chemical Feed Yes No NA NE
Is containment adequate? ❑ ❑ ❑ •
Is storage adequate? • ❑ ❑ ❑
Are backup pumps available? • ❑ ❑ ❑
Is the site free of excessive leaking? ■ ❑ ❑ ❑
Comment: Liquid lime is being added for supplemental alkalinity.
Bar Screens
Type of bar screen
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment:
Grit Removal
Type of grit removal
a.Manual
b.Mechanical
Is the grit free of excessive organic matter?
Is the grit free of excessive odor?
# Is disposal of grit in compliance?
Yes No NA NE
•
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
•
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: Mechanical barscreen is equiped with manual bypass bar screen. Debris from bar
screen and grit are placed in dumpster and disposed of at the county landfill.
Oxidation Ditches Yes No NA NE
Are the aerators operational? • ❑ ❑ ❑
Are the aerators free of excessive solids build up? • ❑ ❑ ❑
# Is the foam the proper color for the treatment process? • ❑ ❑ ❑
Does the foam cover less than 25% of the basin's surface? • ❑ ❑ ❑
Page# 5
Permit: NC0069841
Inspection Date: 09/16/2021
Owner - Facility: Crooked Creek WWTP #2
Inspection Type: Compliance Evaluation
Oxidation Ditches Yes No NA NE
Is the DO level acceptable?
Are settleometer results acceptable (> 30 minutes)?
Is the DO level acceptable?(1.0 to 3.0 mg/I)
Are settelometer results acceptable?(400 to 800 ml/I in 30 minutes)
Comment:
Secondary Clarifier
Is the clarifier free of black and odorous wastewater?
Is the site free of excessive buildup of solids in center well of circular clarifier?
Are weirs level?
Is the site free of weir blockage?
Is the site free of evidence of short-circuiting?
Is scum removal adequate?
Is the site free of excessive floating sludge?
Is the drive unit operational?
Is the return rate acceptable (low turbulence)?
Is the overflow clear of excessive solids/pin floc?
Is the sludge blanket level acceptable? (Approximately'/4 of the sidewall depth)
• ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
• ❑ ❑ ❑
Comment: At time of inspection effluent from (4) secondary clarifiers was clear with few visible
suspended solids.
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Comment:
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Filtration (High Rate Tertiary) Yes No NA NE
Type of operation: Down flow
Is the filter media present? • El El El
Is the filter surface free of clogging? ■ El El El
Is the filter free of growth? • El El El
Is the air scour operational? • ❑ El El
Page# 6
Permit: NC0069841
Inspection Date: 09/16/2021
Owner - Facility: Crooked Creek WWTP #2
Inspection Type: Compliance Evaluation
Filtration (High Rate Tertiary)
Is the scouring acceptable?
Is the clear well free of excessive solids and filter media?
Comment: Sand was starting to collect in clear well.
Disinfection - UV
Are extra UV bulbs available on site?
Are UV bulbs clean?
Is UV intensity adequate?
Is transmittance at or above designed level?
Is there a backup system on site?
Is effluent clear and free of solids?
Comment:
Yes No NA NE
• ❑ ❑ ❑
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
Effluent Sampling Yes No NA NE
Is composite sampling flow proportional? • El El El
Is sample collected below all treatment units? • ❑ El El
Is proper volume collected? • El El El
Is the tubing clean? • El ❑ ❑
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 ■ El El El
degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type • El El El
representative)?
Comment: At time of inspection effluent sampler was recorded at 3.6 Degrees Celsius.
Flow Measurement - Effluent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment: Flow meter was last calibrated on 9/15/2021 by CITI, LLC.
Pump Station - Effluent
Is the pump wet well free of bypass lines or structures?
Are all pumps present?
Yes No NA NE
Yes No NA NE
• ❑ ❑ ❑
Page# 7
Permit: NC0069841
Inspection Date: 09/16/2021
Owner - Facility: Crooked Creek WWTP #2
Inspection Type: Compliance Evaluation
Pump Station - Effluent Yes No NA NE
Are all pumps operable? • ❑ ❑ ❑
Are float controls operable? ■ ❑ ❑ ❑
Is SCADA telemetry available and operational? • ❑ ❑ ❑
Is audible and visual alarm available and operational? • ❑ ❑ ❑
Comment:
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up
power?
Is the generator fuel level monitored?
Comment:
Drying Beds
Is there adequate drying bed space?
Is the sludge distribution on drying beds appropriate?
Are the drying beds free of vegetation?
# Is the site free of dry sludge remaining in beds?
Is the site free of stockpiled sludge?
Is the filtrate from sludge drying beds returned to the front of the plant?
# Is the sludge disposed of through county landfill?
# Is the sludge land applied?
(Vacuum filters) Is polymer mixing adequate?
Comment: Drying beds not in use.
Yes No NA NE
• ❑ ❑ ❑
• ❑ ❑ ❑
▪ ❑ ❑ ❑
• ❑ ❑ ❑
Yes No NA NE
❑ ❑ ❑ •
❑ ❑ ❑ •
Solids Handling Equipment Yes No NA NE
Is the equipment operational? • ❑ ❑ ❑
Is the chemical feed equipment operational? ❑ ❑ El •
Is storage adequate? • ❑ ❑ ❑
Page# 8
Permit: NC0069841
Inspection Date: 09/16/2021
Owner - Facility: Crooked Creek WWTP #2
Inspection Type: Compliance Evaluation
Solids Handling Equipment
Is the site free of high level of solids in filtrate from filter presses or vacuum filters?
Is the site free of sludge buildup on belts and/or rollers of filter press?
Is the site free of excessive moisture in belt filter press sludge cake?
The facility has an approved sludge management plan?
Yes No NA NE
❑ ❑ • ❑
• ❑ ❑ ❑
Comment: Facility has 5 aerobic digesters that are used to thicken sludge. Sludge is hauled to
South Carolina for land application under South Carolina DHEC Permit #ND0089044.
Page# 9