HomeMy WebLinkAboutNC0086550_Bioassay Inspection_20090527•
William G. Ross Jr., Secretary
North Carolina Department of Environment and Natural Resources
Alan W. Klimek, P.E. Director
Division of Water Quality
May 27, 2009
Blake Proctor
Town of Fairmont
PO Box 248
Fairmont NC. 28340
SUBJECT: Bioassay Compliance Inspection
Town of Fairmont
Fairmont Regional WWTP
Permit No: NC0086550
Robeson County
Dear Mr. Lewis: •
Enclosed you will find a copy of the Bioassay Compliance Inspection for the inspection
conducted during the week of May 11, 2009. This inspection was a follow-up inspection of the.
February 17, 2009 Compliance Evaluation Inspection (please review the report dated February 18,
2009). In addition, an Aquatic Toxicity (AT) test and the below listed test parameters were
sampledto evaluate the biological effect of the facility's discharge on test organisms and
compliance with the limits page of the NPDES permit. As part of the inspection, a tour of the
Wastewater Treatment Plant was conducted. All observations and recommendations are in Section
D. Summary of Findings/Comments of this inspection report. The following laboratory test
parameters were performed on aliquot. samples that were collected by DWQ from a 24-hour DWQ
composite sampler on May 12, 2009. These chemistry parameters are required in the Fairmont
Wastewater Treatment Plant NPDES permit.
Analyses Parameters
Outfall 001 results
Total Suspended Solids (TSS)
16 mg/L
NH3 as N
0.56 mg/L
TKN as N
1.8 mg/L
NO2 plus NO3 as N
0.19 mg/L
Total Phosphorus as P
1.6 mg/L
BOD
2.6 mg/L
On May 12 and May 15, 2009, the DWQ-Fayetteville Regional Office collected Whole
Effluent Toxicity samples (WET) for use in a chronic Ceriodaphnia dubia Pass/Fail toxicity test.
The test using these samples resulted in a "Pass", that indicated that the effluent would not be
predicted to have water quality impacts on the receiving water. On the day of the wastewater
treatment plant walk through, the plant appeared to be in compliance with the NPDES permit
requirements. Concerning the plant operation as required by NPDES Permit in Section C (2.)
Proper Operation and Maintenance: "The permittee shall at all times provide the operation and
maintenance resources necessary to operate the existing facilities at optimum efficiency."
Aral
CDENR
1617 Mail Service Center Raleigh, NC 27699-1617 (919) 733-7015
Customer Service 1 800 623-7748
Mr. Proctor
May 27, 2009
Page 2
If you have any questions or comments concerning this report, please contact me at (910)
433-3312.
Dale Lopez
Environmental Specialist
/dl
Enclosures: EPA Water Compliance Inspection Report
cc: Johnny J. Britt, ORC
Central Files
Fayetteville Regional Office Files
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection
1 I NI 2 15I 31 NC0086550 - 11.1 121 09/05/11 117
Type Inspector Fac Type
18I BI 19I S) . 20II
1111111IIII.II66
Remarks
21111I IIII.I1111I1111.I.IIIII IIIIII'IIII•
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ---------------Reserved--------
671 5.0 169 70 13 I 71 I DI 72 I N I 731 I 174 751 I .I I I I I 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Fairmont Regional WWTP
Off US Hwy 74
Fairmont NC 28340
Entry Time/Date
11:00 AM 09/05/11
Permit Effective Date
04/10/01
Exit Time/Date
12:10 PM 09/05/11
Permit Expiration Date
09/07/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
/%/
Johnny J Britt/ORC/910-628-0064/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Johnny J Britt, PO Box 248 Fairmont NC Contacted
283400248/Superintendent/910-628-0064/ No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Facility Site Review -
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary) -
Name(s) and atuuree(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
Dale Lopez ¢ FRO WQ//910-433-3300 Ext.712/ joe
Signature of Management QnnA Reviewer Agency/Office/Phone and Fax Numbers %Date
12J j '9'`l.e:,,,ba. s/ a Er 0 .7
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Pege # 1
31
NPDES
NC0086550
111 121
yr/mo/day
09/05/11
Inspection Type
117 18I B
(cont.) 1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
This inspection was a follow-up of the Compliance Evaluation Inspection that was performed on
02/17/2009. On the CEI report dated 02/18/2009, in the Secondary Clarifier section, it was noted that
"There appears to be an accumulation of solids buildup in the center well". On the first day of this
inspection, 05/11/2009, it was observed that the centerwell of the Secondary Clarifier had a moderate
amount of green plants. Also, there was a small tree that was located in the trough that flowed to the
aeration basin. The ORC was asked to remove the vegetation. Two days later, this inspector observed
that all of the vegetation had been removed. Please be aware that #2 in Section C of Fairmont's NPDES
Permit states that "The Permittee shall at all times provide the operation and maintenance resources
necessary to operate the existing facilities at optimum efficiency".
Page # 2