March 7, 2008
Larry G. Hagan, Mayor
Town of Parkton
P.O. Box 55
Parkton, N.C. 28371
Subject: Wastewater Treatment Plant Compliance Evaluation Inspection
Permit Number NC0026921
Robeson County
Dear Mayor Hagan,
A compliance evaluation inspection was conducted on the town's wastewater treatment plant
February 28, 2008. The on -site inspection visit was conducted with the assistance of your Operator
in Responsible Charge (ORC) Terry Wagers. The attached report lists records, areas of operation,
and equipment that was inspected along with any pertaining recommendations.
If you have questions regarding the attached report or if this office can be of further assistance, I can
be reached at 910-433-3309.
Sincerely,
Don Register
Wastewater Treatment Consultant
Cc: Terry Wagers, ORC
Central Files
FRO, Files
NonrthCarolina
Naturally
North Carolina Division of Water Quality 225 Green Street — Suite 714 Fayetteville, NC 28301-5043 Phone (910) 433-3300 Customer Service
Internet: ncwaterquality.org FAX (910) 486-0707 1-877-623-6748
An Equal Opportunity/Affirmative Action Employer — 50% Recycled/10% Post Consumer Paper
United States Environmental Protection Agency
EPA Washington, D.C. 20460
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection
1 2 3 11 12 17
NI 151 I NC0026921 I I 08/02/28 I
Type Inspector Fac Type
18 19 20
ICI I SI I II
Remarks
211111111111111111111111111111111111111111111111166
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA Reserved
671 9 .0 169 701 31 711 1 721
NI 73 W 74 751
1 1 1 1 1 1 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Parkton WWTP
Loop Rd
Parkton NC 28371
Entry Time/Date
09:00 AM 08/02/28
Permit Effective Date
04/12/01
Exit Time/Date
11:00 AM 08/02/28
Permit Expiration Date
09/07/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Terry Moore Wagers/ORC/910-224-8014/
Other Facility Data
Name, Address of Responsible Official/Title/Phone and Fax Number
Larry G Hagin,PO Box 55 Parkton NC 28371//910-858-3360/ Contacted
No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
■ Permit ■ Flow Measurement ■ Operations & Maintenance ■ Records/Reports
■ Self -Monitoring Program ■ Sludge Handling Disposal ■ Facility Site Review ■ Compliance Schedules
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and Signaturf Inspector ,, Agency/Office/Phone and Fax Numbers Date J p ^-� D e
A /
Don Register / Point Source Compliance 0nit//910-433-3300 E
Signature of Manage ent Q A Reviewer Agency/Office/Phone and Fax Numbers Date
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page # 1
3
NPDES
NC0026921
11
12
yr/mo/day
•
08/02/28
Inspection Type
17 18
�cI
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
The plant appears to be well operated. The DMR's for the months of September - November were checked
against the lab reports and found to be in order. Keep up the good workiiillilliii
Page # 2
Permit: NC0026921 Owner - Facility: Parkton wwTP
Inspection Date: 02/28/2008 Inspection Type: Compliance Evaluation
Compliance Schedules
Is there a compliance schedule for this facility?
Is the facility compliant with the permit and conditions for the review period?
Comment:
Operations & Maintenance
Is the plant generally clean with acceptable housekeeping?
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge
Judge, and other that are applicable?
Comment: date of inspection ditch #1 MLSS - 1600 mg/I and blanket was <0.5'
#2 ditch MLSS - 4800 mg/I blanker was 3.5'
Yes No NA NE
n■nn
n n■n
Yes No NA NE
Recommend the solids be balanced between the two ditches
Permit
(If the present permit expires in 6 months or less). Has the permittee submitted a new application?
Is the facility as described in the permit?
# Are there any special conditions for the permit?
Is access to the plant site restricted to the general public?
Is the inspector granted access to all areas for inspection?
Comment:
Drying Beds
■ nnn
■ nnn
Yes No NA NE
n n■n
■ nnn
n nn■
■ nnn
■ nnn
Yes No NA NE
Is there adequate drying bed space? ■ n n n
Is the sludge distribution on drying beds appropriate? ■ ❑ n ❑
Are the drying beds free of vegetation? ■ 11
# Is the site free of dry sludge remaining in beds? n ■ n n
Is the site free of stockpiled sludge? ■ n n n
Is the filtrate from sludge drying beds returned to the front of the plant? ■ ❑ ❑ ❑
# Is the sludge disposed of through county landfill? ■ n n n
# Is the sludge land applied? n n ■
(Vacuum filters) Is polymer mixing adequate? n n ■ n
Comment:
Bar Screens
Type of bar screen
Yes No NA NE
Page # 3
Permit: NC0026921 Owner -Facility: ParktonWWTP
Inspection Date: 02/28/2008 Inspection Type: Compliance Evaluation
Bar Screens
a.Manual
b.Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Comment: The disposal of the rags should be in the county landfill and not burned on
site.
Oxidation Ditches
Are the aerators operational?
Are the aerators free of excessive solids build up?
# Is the foam the proper color for the treatment process?
Does the foam cover less than 25% of the basin's surface?
Is the DO level acceptable?
Are settleometer results acceptable (> 30 minutes)?
Is the DO level acceptable?(1.0 to 3.0 mg/I)
Are settelometer results acceptable?(400 to 800 ml/I in 30 minutes)
Comment:
Standby Power
Is automatically activated standby power available?
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Comment: Power failure is connected to staff pagers who respond to the call. The
generator was not tested during the inspection because of fuel pump problem. Vendor
has been notified and is scheduled for the repair.
Disinfection -Gas
Are cylinders secured adequately?
Yes No NA NE
■
n
■ rmn
■ nnn
n orm
■ nnn
Yes No NA NE
■ nnn
■ nnn
■ nnn
■ nnn
■ nnn
n nn■
n nn■
n nn■
Yes No NA NE
n ■nn
n ■nn
■ nnn
n ■nn
■ nnn
■ nnn
■ nnn
Yes No NA NE
■ nnn
Page # 4
Permit: NC0026921 Owner - Facility: Parkton WWTP
Inspection Date: 02/28/2008 Inspection Type: Compliance Evaluation
Disinfection -Gas Yes No NA NE •
Are cylinders protected from direct sunlight? • n ❑ 11
Is there adequate reserve supply of disinfectant? ■ n n n
Is the level of chlorine residual acceptable? ■ n n n
Is the contact chamber free of growth, or sludge buildup? ■ n n n
Is there chlorine residual prior to de -chlorination? ■ n n n
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)? n n ■ n
If yes, then is there a Risk Management Plan on site? n n ■ n
If yes, then what is the EPA twelve digit ID Number? (1000- - )
If yes, then when was the RMP last updated?
Comment:
De -chlorination Yes No NA NE
Type of system ? Tablet
Is the feed ratio proportional to chlorine amount (1 to 1)? n n ■ n
Is storage appropriate for cylinders? n n ■ n
# Is de -chlorination substance stored away from chlorine containers? ■ n n n
Comment:
Are the tablets the proper size and type? ■ n n n
Are tablet de -chlorinators operational? ■ n n n
Number of tubes in use? 2
Comment:
Page # 5
ti
WQ
Mayor
Larry G. Hagin
Town Clerk/Finance Officer
Angela Young
Chief of Police
Kevin Wells
Attn: Mark Brantley
Town of ' Parkton
Post Office Box 55 • 28 West David Parnell St.
Parkton, North Carolina 28371
Office (910).858-3360
Fax (910) 858-9808
f ENR -FR
r., C07.
Alderman
Al McMillan
Alf Parnell
Willie Brisson
Fran Meinert
Benton Finley
DENR-FRO
AN 18 2007
This is in reference to the inspection conducted, on February 21, 2007 of Parkton's
WWTP permit number NC0026921 The,'followmg problems have been corrected.
1. The generator at the wwtp has been fixe
2.
3.
4.
5
Exhaust fan is in the process of being fixed A new motor h,.as,..,..,een or
The chlorine flow pacing system has been placed on an annual repair cycle.
WWTP exceeded 2 rngd, flow meter is gomg
to becalibrated twice ayear.
InreferencetoT/Iproblemhave ctd uttfrm, onaceTony HoneyoNCRWA to do a
smoke test for:the Town of Parkton
6 The Town has decided to go'with a tablet fee
orination`systern