HomeMy WebLinkAboutNC0027103_Inspection_20110121A'irA
NCDENR
North Carolina Department of "Environment and Natural Resources
Division of Water Quality
Beverly Eaves Perdue - Coleen H. Sullins Dee Freeman
Governor Director Secretary
January 21, 2011
Mr. McDuffie Cummings, Town Manager
Town of Pembroke
P.O. Box 866
Pembroke, NC 28372
Subject: COMPLIANCE EVALUATION INSPECTION (CEI)
Town of Pembroke Wastewater Treatment Plant
NPDES Permit No. NC0027103
Robeson County
Dear Mr. Cummings:
Enclosed you will find a copy of the Compliance Evaluation Inspection (CEI) report for the routine
annual inspection that I performed on January 19, 2011 at the Town of Pembroke Wastewater Treatment
Plant, accompanied by Rhonda Locklear (ORC, WWTP), Jerry Brooks (Back -Up ORC), and Branyun
Bullard (WWTP Operator). - As part of the inspection, a tour. of the Wastewater Treatment Plant was
conducted. All observations are in Section D. Summary of Findings/Comments of this inspection report.
On the day of my inspection, the wastewater treatment plant appeared to be very well operated and
maintained, and it appeared to be in compliance with the NPDES permit. I appreciate the time and
professional courtesy that was extended by your staff during the inspection. No additional response is
necessary from your office to the DWQ-Fayetteville Regional Office concerning this CEI report. Please
contact me at (910) 433-3312 if you have any questions or comments.
Sincerely,
Dale Lopez
Environmental Specialist
/dl
Enclosures: EPA Water Compliance Inspection Report
Facility Site Review (checklist)
Regional Field Inspectors Check List for Field Parameters
Aerial view of the Town of Pembroke Wastewater Treatment Plant
Town of Pembroke Process Flow Diagram
cc: Rhonda Locklear, Town of Pembroke, (ORC WWTP)
f FRO Files (Mark Brantley)?
225 Green St, Suite 714, Fayette`riille; NC'28301:5043
Phone: 910-433-33001 FAX: 910-486-07071 Customer Service: 1-877-623-6748 One
Internet: www.ncwaterquality.org NOrthCarohna
An Equal Opportunity l Affirmative Action Employer N a i /Irak
United States Environmental Protection Agency
Washington, D.C. 20460
EPA
Water Compliance Inspection Report
Form Approved.
OMB No. 2040-0057
Approval expires 8-31-98
Section A: National Data System Coding (i.e., PCS)
Transaction Code NPDES yr/mo/day Inspection
1 I NI 2 151 31 NC0027103 111 121 11/01/19 117
Type Inspector Fac Type
18I CI 19I SI 20I II
Li
6e
1111 1111 1 1 1 1 111
Remarks
211111 1111111111111111 11111111 1111
Inspection Work Days Facility Self -Monitoring Evaluation Rating B1 QA ----Reserved---------
67I 2.0 169 701 4 I 711 I 72I N I 731 1 174 751 1 1 1 1 1 1 180
Section B: Facility Data
Name and Location of Facility Inspected (For Industrial Users discharging to POTW, also include
POTW name and NPDES permit Number)
Pembroke WWTP
NCSR 1339
Pembroke NC 28372
Entry Time/Date
10:45 AM 11/01/19
Permit Effective Date
09/10/01
Exit Time/Date
02:15 PM 11/01/19
Permit Expiration Date
14/07/31
Name(s) of Onsite Representative(s)/Titles(s)/Phone and Fax Number(s)
///
Rhonda Hagan Locklear/ORC/910-521-2989/
Other Facility Data
Name, Address of Responsible OfficiaUTitle/Phone and Fax Number
McDuffiue Cummings,PO Box 866 Pembroke NC Contacted
283720866//910-521-9758/9105210472 No
Section C: Areas Evaluated During Inspection (Check only those areas evaluated)
Permit Flow Measurement • Operations & Maintenance Records/Reports
Self -Monitoring Program • Sludge Handling Disposal • Facility Site Review • Effluent/Receiving Waters
Laboratory
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary)
(See attachment summary)
Name(s) and ature(s) of Inspector(s) Agency/Office/Phone and Fax Numbers Date
I
Dale Lopez FRO WQ//910-433-3300 Ext.712/ 1 RIbit
r
Signature of Management''Q A eviewer Agency/Office/Phone and Fax Numbers Date
ket ileD46/nAg-tirI/02 2 A i
EPA Form 3560-3 (Rev 9-94) Previous editions are obsolete.
Page # 1
NPDES
NC0027103 111 121
yr/mo/day
11/01/19
117
Inspection Type
18I C I
(cont.) 1
Section D: Summary of Finding/Comments (Attach additional sheets of narrative and checklists as necessary) •
- Enclosed you will find a copy of the Compliance Evaluation Inspection (CEI) report -for the routine annual
inspection that I performed on January 19, 2011 at the Town of Pembroke Wastewater Treatment Plant,
accompanied by Rhonda Locklear (ORC, WWTP), Jerry Brooks (Back -Up ORC),. and Branyun Bullard
(WWTP Operator). As part of the inspection, a tour of the Wastewater Treatment Plant was conducted.
All observations are in Section D. Summary of Findings/Comments of this inspection report. On the day of
my inspection, the wastewater treatment plant appeared to be very well operated and maintained, and it
appeared to be in compliance with the NPDES permit. I appreciate the time and professional courtesy that
was extended by your staff during the inspection. No additional response is necessary from your office to
the DWQ-Fayetteville Regional Office concerning this CEI report. Please contact me at (910) 433-3312 if
you have any questions or comments.
Page # 2
Permit: NC0027103 Owner - Facility: Pembroke VVVVfP
Inspection Date: 01/19/2011 Inspection Type: Compliance Evaluation
Operations & Maintenance Yes No NA NE
Is the plant.generally.clean with acceptable housekeeping? ■ ❑ ❑ n
Does the facility analyze process control parameters, for ex: MLSS, MCRT, Settleable Solids, pH, DO, Sludge ■ n n n
Judge, and other that are applicable?
Comment:
Permit Yes No NA NE
(If the present permit expires in 6 months or less). Has the permittee submitted a new application? n ' n ■ ❑
Is the facility as described in the permit? ■ ❑ n n
# Are there any special conditions for the permit? ■ n n n
Is access to the plant site restricted to the general public? ■ ❑ ❑ n
Is the inspector granted access to all areas for inspection? ■ n n n
Comment:
Record Keeping Yes No NA NE
Are records kept and maintained as required by the permit? ■ ❑ n n
Is all required information readily available, complete and current? ■ n ❑ n
Are all records maintained for 3 years (lab. reg. required 5 years)? ■ n n n
Are analytical results consistent with data reported on DMRs? ■ n ❑ n
Is the chain -of -custody complete? ■ n ❑ n
Dates, times and location of sampling ■
Name of individual performing the sampling ■
Results of analysis and calibration ■
Dates of analysis ■
Name of person performing analyses ■
Transported COCs ■
Are DMRs complete: do they include all permit parameters? ■ ❑ n ❑
Has the facility submitted its annual compliance report to users and DWQ? ■ ❑ n n
(If the facility is = or > 5 MGD permitted flow) Do they operate 24/7 with a certified operator on each shift? n n ■ n
Is the ORC visitation log available and current? ■ n n ❑
Is the ORC certified at grade equal to or higher than the facility classification? ■ ❑ n n
Is the backup operator certified at one grade less or greater than the facility classification? ■ n n n
Is a copy of the current NPDES permit available on site? ■ ❑ n n
Page # 3
i
Permit: NC0027103 Owner - Facility: Pembroke WWTP
Inspection Date: 01/19/2011 Inspection Type: Compliance Evaluation
Record Keeping
Facility has copy of previous year'sAnnual Report on file for review'?
Comment: The Back Up ORCs were Karen Dial, Jerry Brooks, and Gary Harris.
Effluent Pipe.
Is right of way to the outfall properly maintained?
Are the receiving water free of foam other than trace amounts and other debris?
If effluent (diffuser pipes are required) are they operating properly?
Comment:
Flow Measurement - Influent
# Is flow meter used for reporting?
Is flow meter calibrated annually?
Is the flow meter operational?
(If units are separated) Does the chart recorder match the flow meter?
Comment:
Aerobic Digester
Is the capacity, adequate?
Is the mixing, adequate?
Is the site free of excessive foaming in the tank?
# Is the odor acceptable?
# Is tankage available for properly waste sludge?
Comment: In order to avoid peak hours of electrical 'usage, a timer turned the aerator
on from 12 Midnight to 10 AM. Land application of the sludge was performed by Porter
Scientific. The last time that sludge was hauled was during November 2010.
Bar Screens
Type of bar screen
a.Manual
b. Mechanical
Are the bars adequately screening debris?
Is the screen free of excessive debris?
Is disposal of screening in compliance?
Is the unit in good condition?
Yes No NA NE
ODON
Yes No NA NE
■❑❑❑
■ ❑ ❑. ❑..
❑ ❑■❑-
Yes No NA NE
■ nnn
■ nnn
■ nnn
❑ ❑n■.
Yes No NA NE
■ nnn
n nn■
■ nnn
■ nnn
■ nnn
Yes No NA NE
■
■
■ nnn
■ n❑n.
■ n❑n'
■ nnn.
Page # 4
Permit: NC0027103 Owner - Facility: Pembroke WNTP
Inspection Date: 01/19/2011
Inspection Type: Compliance Evaluation
Bar Screens
Comment: Screenings were hauled to Robeson County Landfill. Routinely, a
wastewater level sensor activates the mechanical bar screen (with approximately one
inch openings) and the screenings conveyor belt.
Yes No NA NE
Grit Removal Yes No NA NE
Type of grit removal
a.Manual n
b. Mechanical ■
Is the grit free of excessive organic matter? ■ n n n
Is the grit free of excessive odor? ■ n n n
# Is disposal of grit in compliance? ■ n n n
Comment:
Secondary Clarifier Yes No NA NE
Is the clarifier free of black and odorous wastewater? • n n n
Is the site free of excessive buildup of solids in center well of circular clarifier? ■ n n n
Are weirs level? ■ n n n
Is the site free of weir blockage? ■ n n n
Is the site free of evidence of short-circuiting? ■ n n n
Is scum removal adequate? ■ n n n
Is the site free of excessive floating sludge? ■ n n n
Is the drive unit operational? ■ n n n
Is the return rate acceptable (low turbulence)? ■ n n n
Is the overflow clear of excessive solids/pin floc? ■ n n n
Is the sludge blanket level acceptable? (Approximately 1/4 of the sidewall depth) ■ n n n
Comment: There was approximately 1/2 foot of blanket in the clarifiers on the day of
this CEI. The scum trough skimmings flow to the aerobic digester. The center well of
the two clarifier was free of solids buildup.
Oxidation Ditches Yes No NA NE
Are the aerators operational? ■ n n n
Are the aerators free of excessive solids build up? ■ n n n
# Is the foam the proper color for the treatment process? ■ n n n
Does the foam cover less than 25% of the basin's surface? ■ n n n
Page # 5
Permit: NC0027103 Owner - Facility: Pembroke WNTP
Inspection Date: 01/19/2011
Inspection Type: Compliance Evaluation
Oxidation Ditches
Is the DO level acceptable?
Are settleometer results acceptable (> 30 minutes)?
Is the DO level acceptable?(1.0 to 3.0 mg/I)
Are settelometer results acceptable?(400 to 800 ml/I in 30 minutes)
Comment: The MLSS was 2,600 mg/L on the day of this CEI.
Disinfection -Gas Yes No NA NE
Are cylinders secured adequately? ■ n n ❑ .
Are cylinders protected from direct sunlight? ■ n n n
Is there adequate reserve supply of disinfectant? ■ n n n
Is the level of chlorine residual acceptable? ■ n n n
Is the contact chamber free of growth, or sludge buildup? ■ n ❑ n
Is there chlorine residual prior to de -chlorination? n n ■ n
Does the Stationary Source have more than 2500 Ibs of Chlorine (CAS No. 7782-50-5)? n n ■ n
If yes, then is there a Risk Management Plan on site? n n ■ n
If yes, then what is the EPA twelve digit ID Number? (1000- - )
If yes, then when was the RMP last updated?
Comment: One bag of lime was added per day (five days per week) to the splitter box
that was located immediately before the oxidation ditch.
De -chlorination
Type of system ?
Is the feed ratio proportional to chlorine amount (1 to 1)?
Is storage appropriate for cylinders?
# Is de -chlorination substance stored away from chlorine containers?
Comment:
Are the tablets the proper size and type?
Are tablet de -chlorinators operational?
Number of tubes in use?
Comment:
Standby Power
Is automatically activated standby power available?
Yes No NA NE
■ 000
■ nnn
■ nnn
■ nnn
Yes No NA NE
Gas
■ nnn
■ n•nn
■ nnn
n n■n
n n■n
Yes No NA NE
■ nnn
Page # 6
Permit: NC0027103 Owner - Facility: Pembroke VVVVTP
Inspection Date: 01/19/2011 Inspection Type: Compliance Evaluation
Standby Power
Is the generator tested by interrupting primary power source?
Is the generator tested under load?
Was generator tested & operational during the inspection?
Do the generator(s) have adequate capacity to operate the entire wastewater site?
Is there an emergency agreement with a fuel vendor for extended run on back-up power?
Is the generator fuel level monitored?
Comment: The generator was routinely operated for approximately 15 minutes once
per week. The generator was tested under load approximately once per month.
Pumps-RAS-WAS
Are pumps in place?
Are pumps operational?
Are there adequate spare parts and supplies on site?
Comment:
Laboratory
Are field parameters performed by certified personnel or laboratory?
Are all other parameters(excluding field parameters) performed by a certified lab?
# Is the facility using a contract lab?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)?
Incubator (Fecal Coliform) set to 44.5 degrees Celsius+/- 0.2 degrees?
Incubator (BOD) set to 20.0 degrees Celsius +/- 1.0 degrees?
Comment: An IBM computer "Think Pad" was used to record and manage laboratory
test data.
Effluent Sampling
Is composite sampling flow proportional?
Is sample collected below all treatment units?
Is proper volume collected?
Is the tubing clean?
# Is proper temperature set for sample storage (kept at less than or equal to 6.0 degrees Celsius)?
Is the facility sampling performed as required by the permit (frequency, sampling type representative)?
Comment:
Yes No NA NE
!.❑❑❑
■ nnn
n n■n
■ nnn
■ nnn
■ nnn
Yes No NA NE
■ nnn
■ nnn
n nn■
Yes No NA NE
■ nnn
■ nnn
■ nnn
■ nnn
n nn■
n nn■
Yes No NA NE
■ nnn
■ nnn
■ nnn
■ nnn
■ nnn
■ nnn
Page # 7
Regional Field Inspectors Check List for Field Parameters
Name of site to be Inspected: Pembroke Date: 01-19-2011
Field certification # (if applicable): 552
NPDES #: NC0027103
Inspector:
. Region: FRO
I. Circle the parameter or parameters performed at this site.
Residual Chlorine
, Settleable Solids,
pH
DO
, Conductivity,
Temperature
II. Instrumentation:
A. Does the facility have the equipment necessary to analyze field parameters as circled above?
A pH meter
2. A Residual Chlorine meter
3. DO meter
4. A Cone for settleable solids
lAccumet XL25
HACH DR2800
HACH 550A
fes
Yes
Yes
No
No
No
Yes No
5. A thermometer or meter that measures temperature. fres No
HACH 550A1
6. Conductivity meter Yes No
III. Calibration/Analysis:
1. Is the pH meter calibrated with 2 buffers and
checked with a third buffer each day of use?
2. For Total Residual Chlorine, is a check standard
analyzed each day of use?
3. Is the air calibration of the DO meter performed..
each day of use?
4. For Settleable Solids, is 1 liter of sample
settled for 1 hour?
5. Is the temperature measuring device calibrated
annually against a certified thermometer?
01/06/2011
6. For Conductivity, is a calibration standard
analyzed each day of use?
'Yes
Yes
Yes
No
Yes No
Yes
Yes
No
IV. Documentation:
1. Is the date and time that the sample was collected documented?
2. Is the sample site documented?
3. Is the sample collector documented?
4. Is the analysis date and time documented?
5. Did the analyst sign the documentation?
6. Is record of calibration documented?
7. For Settleable Solids, is sample volume and
1 hour time settling time documented?
8. For Temperature, is the annual calibration of
the measuring device documented?
Comments: pH 4.0 exp date March 2011
pH 7.0 exp date January 2012
pH 10.0 exp date December 2011
pH millivolt reading of pH 7 buffer = -14 mV
1Yes
1Yes
'Yes
1Yes
NYes
1Yes
Yes
1Yes
No
No
No
No
No
Please submit a copy of this completed form to the Laboratory Certification Program.
DWQ Lab Certification
Chemistry Lab
Courier # 52-01-01
FIELD INSPECTOR CHECKLIST REV. 04/23/2002
Imagery Cate Jun 18, 2008
Attachment Order 2-b:
Town of Pembroke NC0027103
Process Flow Diagram
Generator
Waste Sludge
uuiu�u� riuw
.83 MGD
Return Activated Sludge
•
Influent
Pump Station
Digester
Return
Line,
Chlorine Contact