HomeMy WebLinkAboutWQ0042827_Application (FTSE)_20211006Permit Number WQ0042827
Program Category
Non -discharge
Permit Type
Gravity Sewer Extension.. Pump Stations, & Pressure Sewer Extensions
Primary Reviewer
dean. hunkele
Coastal SWRule
Permitted Flow
Facility
Central Files: APS _ SWP
9/23/2021
Permit Tracking Slip
Status
Project Type
In review
New Project
Version
Permit Classification
A
Individual
Permit Contact Affiliation
Facility Name Major/Minor Region
US Hwy 117 Regional Pump Station Minor Wilmington
Location Address County
Pander
Owner
Owner Name
Town of Burgaw
Facility Contact Affiliation
Owner Type
Government - Municipal
Owner Affiliation
James H.Gantt
109 N Walker St
Dates/Events Burgaw NC 2842552:
Scheduled
Ong Issue App Received Draft Initiated Issuance Public Notice Issue Effective Expiration
9/15/2021
McKIM&CREED
September 14, 2021
ENGINEERS
5iJ R VEYO RS
P L A N N E R S
M&C 04576-0012 (40)
Mr. Dean Hunkele
NC Department of Environmental Quality — Wilmington Regional Office
127 Cardinal Drive Extension
Wilmington, NC 28405
RE: Fast Track Application — Town of Burgaw
US Highway 117 Regional Pump Station & Force Main Project
New Permit Request
Dear Mr. Hunkele:
On behalf of the Town of Burgaw, we are pleased to submit this permit
application for the referenced project which includes the installation of
approximately 7,700 linear feet of 8-inch PVC sewer force main, 1,220 linear feet
of 8-inch PVC sanitary sewer and a new 450 GPM pump station to serve future
development in the Town. Note that this is a zero -flow application. Please find
enclosed the following documentation:
• One (1) hard and One (1) digital copy of application form.
• One (1) hard and One (1) digital copy of 8.5 x 11 color USGS topographic
map
• One (1) hard and One (1) digital copy of 8.5 x 11 street map
• One (1) hard and One (1) digital copy of Project Narrative
• $480 check (permit fee)
Please let me know if you have questions or would like to discuss. Thanks for
your assistance on this project.
Sincerely,
McKIM & CREED, INC.
243 North Fiona Stiee
Wilmington, NC 28401
s Powell, PE
910. 343. 1048
Fax 9I 0_251 8282
RECEIVEDMCDENR/pyy[•j
SEP 15 2021
Vyeter OtWty Reglmy
Operah aSeab"
wmvg Negmw Office
I:\04576\0012\40-Permit\FTSE
.v,.o mck�m creed rnm
State of North Carolina
DWR Department of Environmental Quality
Division of Water Resources
FAST TRACK SEWER SYSTEM EXTENSION APPLICATION
Division of Water Resources FTA 06-21 & SUPPORTING DOCUMENTATION
Application Number: yiNQdL(ar*'q (to be completed byDWR)
All items must be completed or the application will be returned
L APPLICANT INFORMATION
1. Applicant's name: Town of Bureaw (company, municipality, HOA, utility, etc.)
2. Applicant type: ❑ Individual ❑ Corporation ❑ General Partnership
❑ Federal ❑ State/County ® Municipal
3. Signature authority's name: James Gantt per 15A NCAC 02T .0106(b)
Title: Town Manager
4. Applicant's mailing address: 109 N Walker Street
City: Bureaw State: NC Zip: 28425-
5. Applicant's contact information:
Phone number: (9663-3440 Email Address: jganttna bur aw.gov
If. PROJECT INFORMATION:
❑ Privately -Owned Public Utility
❑ Other
1. Project name: US Highway 117 Regional Pump Station & Force Main
2. Application/Project status: ® Proposed (New Permit) ❑ Existing Permit/Project
If a modification, provide the existing permit number: W000_ and issued date: ,
For modifications, also attach a detailed narrative description as described in Item G of the checklist.
If new construction, but part of a master plan, provide the existing permit number: W000_
3. County where project is located: Pender County
4. Approximate Coordinates (Decimal Degrees): Latitude: 34.54917' Longitude:-77.90833°
5. Parcel ID (if applicable): 3229-47-8752-0000 (or Parcel ID to closest downstream sewer)
III. CONSULTANT INFORMATION:
1. Professional Engineer: Jesse Powell, PE License Number: 046997
Finn: McKim & Creed, Inc.
Mailing address: 243 N Front Street
City: Wilmington State: NC Zip: 28401-
Phone number: (9343-1048 Email Address: iess.powell@mckimcreed.com
IV. WASTEWATER TREATMENT FACILITY (WWTF) INFORMATION:
1. Facility Name: Wallace Regional Wastewater Treatment Plant Permit Number: NC0003450
Owner Name: Town of Wallace
V. RECEIVING DOWNSTREAM SEWER INFORMATION:
1. Permit Number(s): WQ0033521
2. Downstream (Receiving) Sewer Information: 20 inch ❑ Gravity ® Force Main
3. System Wide Collection System Permit Number(s) (if applicable): WQCS_
Owner Name(s): Town of Bureaw
FORM: FTA 06-21 Page 1 of 5
VI. GENERAL REQUIREMENTS
I. If the Applicant is a Privately -Owned Public Utility, has a Certificate of Public Convenience and Necessity been attached?
❑ Yes ❑ No ® N/A
2. If the Applicant is a Developer of lots to be sold, has a Developer's Operational Agreement (FORM: DEV) been attached?
❑ Yes ❑ No ® N/A
3. If the Applicant is a Home/Property Owners' Association, has an HOA/POA Operational Agreement (FORM: HOA) and
supplementary documentation as required by 15A NCAC 02T.0115(c) been attached?
❑ Yes ❑ No ® N/A
4. Origin of wastewater: (check all that apply):
❑ Residential (Individually Owned) ❑ Retail (stores, centers, malls) ❑ Car Wash
❑ Residential (Leased) ❑ Retail with food preparation/service ❑ Hotel and/or Motels
❑ School / preschool / day care ❑ Medical / dental / veterinary facilities ❑ Swimming Pool/Clubhouse
❑ Food and drink facilities ❑ Church ❑ Swimming Pool/Filter Backwash
❑ Businesses / offices / factories ❑ Nursing Home ❑ Other (Explain in Attachment)
5. Nature of wastewater: 0 % Domestic 0 % Commercial 0 % Industrial (See 15A NCAC 02T .0103(20))
If Industrial, is there a Pretreatment Program in effect? ❑ Yes ®No
6. Hasa flow reduction been approved under 15A NCAC 02T .0114(f) ❑ Yes ® No
➢ If yes, provide a copy of flow reduction approval letter with this application
7. Summarize wastewater generated by project:
Establishment Type (see 02T.0114(Q)
Daily Design Flow a.n
No. of Units
Flow
gall
GPD
gal/
GPD
gal/
GPD
gal/
GPD
gal/
GPD
gal/
GPD
Total
GPD
a See 15A NCAC 02T .0114(b). (d). (e)(1) and (e)(2) for caveats to wastewater design flow rates (i.e., minimum flow per
dwelling; proposed unknown non-residential development uses; public access facilities located near high public use areas;
and residential property located south or east of the Atlantic Intracoastal Waterway to be used as vacation rentals as defined
in G.S. 42A-4).
b Per 15A NCAC 02T .0114(c), design flow rates for establishments not identified [in table 15A NCAC 02T.01141 shall be
determined using available flow data, water using fixtures, occupancy or operation patterns, and other measured data.
8. Wastewater generated by project: 0 GPD (per 15A NCAC 02T .0114)
➢ Do not include future flows or previously permitted allocations
If permitted flow is zero, please indicate why:
® Pump Station/Force Main or Gravity Sewer where flow will be permitted in subsequent permits that connect to this line.
Please provide supplementary information indicating the approximate timeframe for permitting upstream sewers with flow.
❑ Flow has already been allocated in Permit Number: Issuance Date:
❑ Rehabilitation or replacement of existing sewers with no new flow expected
❑ Other (Explain):
FORM: FTA 06-21 Page 2 of 5
VIL GRAVITY SEWER DESIGN CRITERIA (If Applicable) - 02T.0305 & MDC (Gravity Sewers):
1. Summarize gravity sewer to be permitted:
Size (inches) Length (feet) Material
8 1220 PVC
➢ Section 11 & III of the MDC for Permitting of Gravity Sewers contains information related to design criteria
➢ Section III contains information related to minimum slopes for gravity sewer(s)
➢ Oversizing lines to meet minimum slope requirements is not allowed and a violation of the MDC
VIII. PUMP STATION DESIGN CRITERIA (If Applicable) — 02T .0305 & MDC (Pump Stations/Force Mains):
PROVIDE A SEPARATE COPY OF THIS PAGE FOR EACH PUMP STATION INCLUDED IN THIS PROJECT
1. Pump station number or name: Regional Pump Station No.2 (PS No.2)
2. Approximate Coordinates (Decimal Degrees): Latitude: 34.54917' Longitude:-77.90833°
3. Total number of pumps at the pump station: 2
3. Design flow of the pump station: 0.65 millions gallons per day (firm capacity)
➢ This should reflect the total GPM for the pump station with the largest pump out of service.
4. Operational point(s) per pump(s): 450/664 gallons per minute (GPM) at 183/113 feet total dynamic head (TDH)
5. Summarize the force main to be permitted (for this Pump Station):
Size (inches)
Length (feet)
Material
8
7700
PVC
If any portion of the force main is less than 4-inches in diameter, please identify the method of solids reduction per
MDCPSFM Section 2.01C.Lb. ❑ Grinder Pump ❑ Mechanical Bar Screen ❑ Other (please specify) _
6. Power reliability in accordance with 15A NCAC 02T.0305(h)(1):
® Standby power source or ❑ Standby pump
➢ Must have automatic activation and telemetry - 15A NCAC 02T.0305(h)(1)(B):
➢ Required for all pump stations with an average daily flow greater than or equal to 15,000 gallons per day
➢ Must be permanent to facility and may not be portable
Or if the pump station has an average daily flow less than 15,000 gallons per day 15A NCACO2T.0305(h)(1)(C):
❑ Portable power source with manual activation, quick -connection receptacle and telemetry -
or
❑ Portable pumping unit with plugged emergency pump connection and telemetry:
➢ Include documentation that the portable source is owned or contracted by the applicant and is compatible with the station.
➢ If the portable power source or pump is dedicated to multiple pump stations, an evaluation of all the pump stations' storage
capacities and the rotation schedule of the portable power source or pump, including travel timeframes, shall be provided
as part of this permit application in the case of a multiple station power outage.
FORM: FTA 06-21 Page 3 of 5
IX. SETBACKS & SEPARATIONS — (02B .0200 & 15A NCAC 02T.0305(f)):
1. Does the project comply with all separations/altematives found in 15A NCAC 02T .0305(f) & (a)? N Yes ❑ No
15A NCAC 02T.0305(f) contains minimum separations that shal I he provided for sewer systems:
Setback Parameter*
Separation Required
Storm sewers and other utilities not listed below (vertical)
18 inches
'Water mains (vertical - water over sewer preferred, including in benched trenches)
18 inches
'Water mains (horizontal)
10 feet
Reclaimed water lines (vertical - reclaimed over sewer)
18 inches
Reclaimed water lines (horizontal - reclaimed over sewer)
2 feet
**Any private or public water supply source, including any wells, WS-1 waters of Class 1 or
Class Il impounded reservoirs used as a source of drinking water, and associated wetlands.
100 feet
**Waters classified WS (except WS-I or WS-V), B, SA, ORW, HQW, or SB from normal
high water (or tide elevation) and wetlands associated with these waters (see item IX.2)
50 feet
**Any other stream, lake, impoundment, or ground water lowering and surface drainage
ditches, as well as wetlands associated with these waters or classified as WL.
10 feet
Any building foundation (horizontal)
5 feet
Any basement (horizontal)
10 feet
Top slope of embankment or cuts of 2 feet or more vertical height
10 feet
Drainage systems and interceptor drains
5 feet
Any swimming pools
10 feet
Final earth grade (vertical)
36 inches
➢ If noncompliance with 02T.0305(f) or (g), see Section X.1 of this application
* 15A NCAC 02T.030560 contains alternatives where separations in 02T.0305(fl cannot be achieved. Please check "yes"
above if these alternatives are used and provide narrative information to explain.
**Stream classifications can be identified using the Division's NC Surface Water Classifications webpage
2. Does this project comply with the minimum separation requirements for water mains? N Yes ❑ No ❑ N/A
➢ If no, please refer to 15A NCAC 18C.0906(f) for documentation requirements and submit a separate document,
signed/sealed by an NC licensed PE, verifying the criteria outlined in that Rule.
3. Does the project comply with separation requirements for wetlands? N Yes [-]No ❑ N/A
➢ Please provide supplementary information identifying the areas of non-conformance.
➢ See the Division's draft separation requirements for situations where separation cannot be met.
➢ No variance is required if the alternative design criteria specified is utilized in design and construction.
4. Is the project located in a river basin subject to any State buffer rules? ❑ Yes Basin name: ❑ No
If yes, does the project comply with setbacks found in the river basin rules per 15A NCAC 02B .0200? ❑ Yes N No
➢ This includes Trout Buffered Streams per 15A NCAC 2B.0202
5. Does the project require coverage/authorization under a 404 Nationwide/individual permits ❑ Yes N No
or 401 Water Quality Certifications?
➢ Please provide the permit number/permitting status in the cover letter if coverage/authorization is required.
6. Does project comply with 15A NCAC 02T.0105(c)(6) (additional permits/certifications)? N Yes ❑ No
Per 15A NCAC 02T.0105(c)(6), directly related environmental permits or certification applications must be being prepared,
have been applied for, or have been obtained. Issuance of this permit is contingent on issuance of dependent permits (erosion
and sedimentation control plans, stormwater management plans, etc.).
7. Does this project include any sewer collection lines that are deemed "high -priority?" ❑ Yes N No
Per 15A NCAC 02T.0402, "high -priority sewer" means any aerial sewer, sewer contacting surface waters,
siphon, or sewers positioned parallel to streambanks that are subject to erosion that undermines or deteriorates the sewer.
Siphons and sewers suspended through interference/conflict boxes require a variance approval.
➢ If yes, include an attachment with details for each line, including type (aerial line, size, material, and location).
High priority lines shall be inspected by the permittee or its representative at least once every six -months and
inspections documented per 15A NCAC 02T.0403(a)(5) or the permittee's individual System -Wide Collection permit.
FORM: FTA 06-21 Page 4 of 5
X. CERTIFICATIONS:
1. Does the submitted system comply with 15A NCAC 02T, the Minimum Design Criteria for the Permitting of Pump Stations
and Force Mains (latest version), and the Gravity Sewer Minimum Design Criteria (latest version) as applicable?
® Yes ❑ No
If no, for projects requiring a single variance, complete and submit the Variance/Altemative Design Request application
(VADC 10-14) and supporting documents for review to the Central Office. Approval of the request will be issued
2. Professional Engineer's Certification:
1, l Jl � ��I✓1✓` \ attest that this application for V5 1n- � q [Yt• fww P J + ^ � wc-L
(Professional Engineer's name from Application Item 111.1.) (Project Name fli6rn Application Item 11.1) K�e11
has been reviewed by me and is accurate, complete and consistent with the information supplied in the plans,
specifications, engineering calculations, and all other supporting documentation to the best of my knowledge. I further
attest that to the best of my knowledge the proposed design has been prepared in accordance with the applicable regulations,
Minimum Design Criteria for Gravity Sewers (latest version), and the Minimum Design Criteria for the Fast -Track Permitting
of Pump Stations and Force Mains (latest version). Although other professionals may have developed certain portions of this
submittal package, inclusion of these materials under my signature and seal signifies that I have reviewed this material and
have judged it to be consistent with the proposed design.
NOTE — In accordance with General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false
statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may
include a fine not to exceed $10,000, as well as civil penalties up to $25,000 per violation. Misrepresentation of the application
information, including failure to disclose any design non-compliance with the applicable Rules and design criteria, may subject
the North Carolina -licensed Professional Engineer to referral to the licensing board. (21 NCAC 56.0701)
North Carolina Professional Engineer's seal, signature, and date:
3. Applicant's Certification per 15A NCAC 02T .0106(b):
1, James H. Gantt, Town Manager , attest that this application for US Highway 117 Regional Pump Station & Force Main
(Signature Authority Name from Application Item I.3.) (Project Name from Application Item 11.1)
attest that this application has been reviewed by me and is accurate and complete to the best of my knowledge.
1 understand that if all required parts of this application are not completed and that if all required supporting documentation
and attachments are not included, this application package is subject to being returned as incomplete. I understand that any
discharge of wastewater from this non -discharge system to surface waters or the land will result in an immediate enforcement
action that may include civil penalties, injunctive relief, and/or criminal prosecution. I will make no claim against the Division
of Water Resources should a condition of this permit be violated. 1 also understand that if all required parts of this application
package are not completed and that if all required supporting information and attachments are not included, this application
package will be returned to me as incomplete.
NOTE — In accordance with General Statutes 143-215.6A and 143-215.6B, any person who knowingly makes any false
statement, representation, or certification in any application package shall be guilty of a Class 2 misdemeanor, which may
include a fine not to exceed $10,000 as well as civil penalties up to $25,000 per violation.
Signature:
IITiTtiul�lG<tZb�l
Date: 9/8/2021
Page 5 of 5
MUSGS O.S. xEP4OFTHE INERO0. Tx.,MJ MQOAOpA4EE
""OWNNT.SUSopo
GL iOE
-
--.
0.
pFORCE AIN1
la
.-
.7 L .1\ \
L
xe
-
BAIPVC
N I
IP.IP CTATIDNIF
i --
-
SEWER
-
CGRAVITY
_
27
p E
PUMP
_
STATOR TO BE REDIRECTEDTO
REOIRETATON
RATpNiOBE
PUMP
JPERMITTED
-
SEPPfUiELY)
_
is
J
.
YALE I:N,
+e.eeuna .
�oW
.. .,...
Qi
va. ..., �
IX �
.,,
�
...............,.,....,.......
,
e....
eupe�A BE
1
�i
e
w.
i-
x
y K
T
a art Supercenter
G G
"stoii' R „ NP tOfrs%"
r t
40
re �/
PROPOSED REGIONAL PUMPS STATION
A�•
5. • 3urc� w ��•F s r - ..
�
:
a 4'emomonai ��aittosprta'F ' • • • 1 ...
. y
Gosr
ogg l N
owat c < ~:�N $ k s 4000 ft
vMCIQM&CREED
PROJECT DESIGN NARRATIVE
TO: Town of Burgaw
FROM: Jess Powell, PE
DATE: September 14, 2021
RE: US HWY 117 Regional Pump Station and Force Main Project
Fast Track Sewer Permit - NCDEQ
M&CA: 04576-0012
I. Background
The Town of Burgaw has identified the need for a new regional wastewater pump station (PS No.
2) and force main to serve an unsewered area, east of US Highway 117. In addition to the new
wastewater pump station, the project will include redirecting flow from the existing White Tractor
Pump Station to the new station via a combination of approximately 2,600 linear feet of 8" gravity
sewer and 4" sewer force main.
The project will involve the design and permitting of:
✓ 450 GPM wastewater pump station
✓ 7,700 linear feet of 8-inch PVC sewer force main
✓ 1,340 linear feet of 4-inch PVC sewer force main
✓ 1,220 linear feet of 8-inch PVC sanitary sewer
Note that the 1,340 linear feet of 4-inch PVC sewer force main will be permitted separately as a
permit modification for White Tractor Pump Station.
The new 8-inch force main will manifold into an existing 20-inch force main that conveys the
Towri s wastewater to the Town of Wallace, North Carolina for treatment.
The basis of design for the proposed pump station and associated pipeline improvements are
detailed in the following sections.
H. Demands and Peak Hour Factors
04576-0012 1 September 2021
US HWY 117 Regional Pump Station and Force Main
Flow projections for PS No. 2 were developed based on information provided by the Town. There
are 400 residential units planned for development within the service area. In addition, an existing
pump station (White Tractor PS) currently flows into a small diameter gravity sewer which is
rapidly approaching the maximum capacity. To alleviate the flow on the receiving gravity sewer,
the flow will be redirected through a combination of force main and gravity sewer to ultimately be
served by the new regional pump station. The average daily flow is summarized as follows:
✓ Average Daily Flow (ADF) = 172,400 GPD
Additionally, as required by NCDEQ Minimum Design Criteria, peak hour factors were calculated
based on Residential Equivalent Units (REU) to be constructed within the station service area.
The NCDEQ formula as shown below was utilized in this calculation.
Peaking Factor Calculation
Service Area Population = P
Peak Factor = 18 + �P
4+�P
The peaking factor used in the pump station design is as follows:
✓ Peak Hour Factor (PHF) = 3.7
III. Pump and Force Main Sizing
Based on the average daily flows and PHF's the peak pump rate for PS No. 2 is provided below:
Table 1 —Flow Summary — Regional Pump Station No. 2
Average Daily Demand
Minimum Peak Pump
Design Pumping Rate
(GPD)
Peaking Factor
Rate (GPM)
(GPM)
172400
3.35
442
450
Hydraulic modeling was conducted for PS No. 2 to determine the pump operational
characteristics. Hydraulic results are as follows:
Table 2 — Hydraulic Modeling Results —All System Pumps ON
Flow (GPM)
Head (FT)
Pressure (PSI)
PS No. 2(Proposed)
450
183
82
PS No. 1 (Existing)
1 2600
157
68
04576-0012 2 September 2021
US HWY 117 Regional Pump Station and Force Main
Diameter
Velocity (FPS)
8"
2.93
20"
3.13
Table 3 — Hudraulic Modelinv Results — All Sustem Pumm nFF
Flow (GPM)
Head (FT)
Pressure (PSI)
PS No. 2 (Proposed)
664
113
87
PS No. 1 (Existing)
-
-
Diameter
Velocity (FPS)
8"
4.42
For the pumping conditions, a duplex, Myers 4VL/4VLX configuration with 60 HP motors, and
12.88-inch impellers will meet the conditions utilizing the 6-inch force main. The following
graphic provides system curves for the recommended Myers 4VL.
400
360
320
280
240
w
200
x
160
e0
80
40
0
0
Pump Curve
\(in Komi ., Stable FL.,,
Pre@red operali.! reeimr
1;.00 m
54
\ 59 6. 66 66
67
1288m
61 66 66
62
\ hp
JSp
hp
Flow - USgpm
04576-0012 3 September 2021
US HWY 117 Regional Pump Station and Force Main
IV. Summary of Recommended Pump Station and Force Main Sizing
Recommend sizing of the proposed Regional PS No. 2 is summarized in the following tables.
Pump Station
ADF
Station
Pump Rate
(GPD)
Configuration
(GPM)
TDH
Pump Selection
HP
RPM
Myers 4VL/4VLX
172,400
Duplex
450
183
12.88-Inch
60
1750
Impeller
Force Main
ADF (GPD)
Force Main Size
Flow (GPM)
Velocity (FPS)
172,400
8-inch
450
2.93
END OF MEMORANDUM
04576-0012 4 September 2021